{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT2027-4VB40","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT2027-4VB40","canonicalUrl":"https://aoctrl.com/siemens/3RT2027-4VB40","factsUrl":"https://aoctrl.com/api/mcp/products/3RT2027-4VB40","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS coupling contactor, size S0, order code 3RT2027-4VB40, rated 27 A at 480/600 V, screw and snap-on 35 mm DIN rail.","salesMarkdown":"The Siemens 3RT2027-4VB40 is a SIRIUS coupling contactor in size S0, built for switching loads in control panels where you need a compact, DIN-rail-mounted interface between a control circuit and a power circuit. It carries a 27 A rating at both 480 V and 600 V — that's the continuous current it can handle in AC-3 motor duty, so it's sized for moderate motor loads like pumps, small conveyors, or fans up to about 5 hp at 230 V. ## Switching ratings and coil Coil is 24 V DC rated. The magnet coil connection uses a ring cable lug — plan for that termination when wiring. Switching frequency varies by duty: up to 1,000 operations per hour at AC-1 (resistive), 750 ops/h at AC-2 and AC-3 (motor starting and running), and 250 ops/h at AC-4 (plugging/inching). The auxiliary switch is not included — this is a bare contactor.","metaTitle":"Siemens 3RT2027-4VB40 SIRIUS Coupling Contactor, S0, 27 A at","metaDescription":"Siemens 3RT2027-4VB40 SIRIUS coupling contactor, size S0, rated 27 A at 480/600 V. Current production. Screw and snap-on 35 mm DIN rail. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"107 mm","Width":"45 mm","at DC":"19 ... 21 ms","title":"3RT2027-4VB40","Height":"85 mm","Upwards":"10 mm","Forwards":"10 mm","Downwards":"10 mm","Arcing Time":"10 ... 10 ms","At The Side":"6 mm","Rated Value":"24 V","description":"power contactor, AC-3e/AC-3, 32 A, 15 kW / 400 V, 3-pole, 24 V DC, 0.7-1.25* Us, with integrated diode combination, auxiliary contacts: 1 NO + 1 NC, ring cable lug connection, size: S0","Initial Value":"0.7","During Storage":"-55 ... +80 °C","Of Magnet Coil":"Ring cable lug connection","at AC-1 maximum":"1 000 1/h","at AC-2 maximum":"750 1/h","at AC-3 maximum":"750 1/h","at AC-4 maximum":"250 1/h","lifecycle_stage":"current","Auxiliary Switch":"No","During Operation":"-25 ... +60 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","Full-Scale Value":"1.25","at AC-3e maximum":"750 1/h","Mounting Position":"+/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface","Size Of Contactor":"S0","Product Brand Name":"SIRIUS","Product Designation":"Coupling contactor","at 24 V rated value":"10 A","at 48 V rated value":"2 A","at 60 V rated value":"2 A","Of Contactor Typical":"10 000 000","at 110 V rated value":"1 A","at 125 V rated value":"0.9 A","at 220 V rated value":"0.3 A","at 230 V rated value":"5 hp","at 400 V rated value":"3 A","at 440 V rated value":"0.6 A","at 480 V rated value":"27 A","at 500 V rated value":"2 A","at 600 V rated value":"27 A","at 690 V rated value":"1 A","Side-By-Side Mounting":"Yes","For Main Current Circuit":"Ring cable lug connection","at 110/120 V rated value":"2 hp","at 200/208 V rated value":"10 hp","at 220/230 V rated value":"10 hp","at 460/480 V rated value":"20 hp","at 575/600 V rated value":"25 hp","Relative Humidity Minimum":"10 %","Of Main Circuit Rated Value":"6 kV","at AC-3 rated value maximum":"690 V","at AC in hot operating state":"6.3 W","at AC-2 at 400 V rated value":"15 kW","at AC-3e rated value maximum":"690 V","at AC-4 at 400 V rated value":"22 A","safety-related switching OFF":"Yes","Substance Prohibitance (Date)":"10/01/2009","Design Of The Surge Suppressor":"with diode assemblies","Of Auxiliary Circuit Rated Value":"6 kV","at AC-5a up to 690 V rated value":"44 A","at AC-5b up to 400 V rated value":"26.5 A","For Auxiliary And Control Circuit":"ring terminal lug connection","Function Module For Communication":"No","With Type Of Assignment 2 Required":"gG: 50A (690V,100kA), aM: 25A (690V, 100kA), BS88: 50A (415V, 80kA)","Without Load Current Share Typical":"4.5 W","closing power of magnet coil at DC":"4.5 W","holding power of magnet coil at DC":"4.5 W","At Contactor For Auxiliary Contacts":"Ring cable lug connection","With Type Of Coordination 1 Required":"gG: 125A (690V,100kA), aM: 50A (690V,100kA), BS88: 125A (415V,80kA)","operational current at AC-12 maximum":"10 A","at AC in hot operating state per pole":"2.3 W","number of NO contacts for main contacts":"3","reference code according to IEC 81346-2":"Q","Number Of Poles For Main Current Circuit":"3","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","mirror contact according to IEC 60947-4-1":"Yes","with low demand rate according to SN 31920":"40 %","with high demand rate according to SN 31920":"73 %","Type Of Voltage Of The Control Supply Voltage":"DC","Limited To 1 S Switching At Zero Current Maximum":"499 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 5 S Switching At Zero Current Maximum":"341 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 10 S Switching At Zero Current Maximum":"260 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 30 S Switching At Zero Current Maximum":"199 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 60 S Switching At Zero Current Maximum":"162 A; Use minimum cross-section acc. to AC-1 rated value","contact rating of auxiliary contacts according to UL":"A600 / P600","Of Main Circuit With Degree Of Pollution 3 Rated Value":"690 V","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","Of Auxiliary Circuit With Degree Of Pollution 3 Rated Value":"690 V","For Short-Circuit Protection Of The Auxiliary Switch Required":"gG: 10 A (500 V, 1 kA)","minimum cross-section in main circuit at maximum AC-1 rated value":"10 mm²","number of NC contacts for auxiliary contacts instantaneous contact":"1","number of NO contacts for auxiliary contacts instantaneous contact":"1","Of The Contactor With Added Electronically Optimized Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/e3a1a57775dd44591646c67d15782842.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=118575&mlfb=3RT2027-4VB40"},"ai":{"faq":[{"question":"What are the key electrical ratings?","answer":"Rated 27 A at both 480 V and 600 V. Coil is 24 V DC. Switching capacity at 230 V is 5 hp. Contact ratings at 24 V DC are 10 A."},{"question":"What are the physical dimensions?","answer":"Width 45 mm, height 85 mm, depth 107 mm. It is size S0 and mounts on 35 mm DIN rail."},{"question":"Does it include an auxiliary contact block?","answer":"No, the auxiliary switch is not included — this is a basic contactor without add-on blocks."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT2027-4VB40","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT2027-4VB40 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}