{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT2035-1AH20","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT2035-1AH20","canonicalUrl":"https://aoctrl.com/siemens/3RT2035-1AH20","factsUrl":"https://aoctrl.com/api/mcp/products/3RT2035-1AH20","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS, power contactor, Size S2, 3RT2035-1AH20, 48 V 50 Hz coil, screw-type terminals, 3-pole main contacts with auxiliary switch, screw and snap-on mounting on 35 mm DIN rail.","salesMarkdown":"## SIRIUS Size S2 power contactor — 48 V 50 Hz coil, screw terminals The main contact configuration is 3-pole, and an auxiliary switch is integrated. Physical dimensions: 114 mm height, 55 mm width, 130 mm depth. ## Switching frequency and contact ratings Maximum switching frequency varies by duty: 1 200 1/h at AC-1, 750 1/h at AC-2, 1 000 1/h at AC-3 and AC-3e, and 300 1/h at AC-4. The AC-3 and AC-3e ratings (1 000 1/h) cover standard motor starting duty; the AC-4 rating (300 1/h) reflects the more severe inching/plugging duty cycle. Auxiliary contact ratings are voltage-dependent: 10 A at 24 V, 2 A at 48 V and 60 V, 1 A at 110 V, 0.9 A at 125 V, 0.3 A at 220 V, 3 A at 400 V, 0.6 A at 440 V, and 40 A at 480 V. The motor horsepower rating at 230 V is 7.5 hp. Arcing time is 10 to 20 ms, with switching time (at AC) of 10 to 18 ms. Power factor at 50 Hz is 0.36, at 60 Hz is 0.39. Main contact wire sizes: 2x (0.5 to 1.5 mm²) or 2x (0.75 to 2.5 mm²) solid or stranded.","metaTitle":"Siemens SIRIUS 3RT2035-1AH20 Power Contactor, Size S2, 48V 5","metaDescription":"Siemens SIRIUS 3RT2035-1AH20 power contactor, Size S2. 48V 50Hz coil, screw terminals, 3-pole main contacts with auxiliary switch. Current lifecycle stage. Quoted to order against","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"130 mm","Width":"55 mm","at AC":"10 ... 18 ms","Height":"114 mm","Upwards":"10 mm","Forwards":"10 mm","at 50 Hz":"0.36","at 60 Hz":"0.39","Downwards":"10 mm","Arcing Time":"10 ... 20 ms","At The Side":"6 mm","During Storage":"-55 ... +80 °C","Of Magnet Coil":"Screw-type terminals","at AC-1 maximum":"1 200 1/h","at AC-2 maximum":"750 1/h","at AC-3 maximum":"1 000 1/h","at AC-4 maximum":"300 1/h","lifecycle_stage":"current","Auxiliary Switch":"Yes","During Operation":"-25 ... +60 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","at AC-3e maximum":"1 000 1/h","For Main Contacts":"18 ... 1","Mounting Position":"+/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface","Size Of Contactor":"S2","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Power contactor","at 24 V rated value":"10 A","at 48 V rated value":"2 A","at 60 V rated value":"2 A","Of Contactor Typical":"10 000 000","at 110 V rated value":"1 A","at 125 V rated value":"0.9 A","at 220 V rated value":"0.3 A","at 230 V rated value":"7.5 hp","at 400 V rated value":"3 A","at 440 V rated value":"0.6 A","at 480 V rated value":"40 A","at 50 Hz rated value":"48 V","at 500 V rated value":"2 A","at 60 Hz rated value":"48 V","at 600 V rated value":"41 A","at 690 V rated value":"1 A","Side-By-Side Mounting":"Yes","For Auxiliary Contacts":"20 ... 14","For Main Current Circuit":"screw-type terminals","at 110/120 V rated value":"3 hp","at 200/208 V rated value":"10 hp","at 220/230 V rated value":"15 hp","at 460/480 V rated value":"30 hp","at 575/600 V rated value":"40 hp","Relative Humidity Minimum":"10 %","Of Main Circuit Rated Value":"6 kV","at AC-3 rated value maximum":"690 V","at AC in hot operating state":"6.6 W","at AC-2 at 400 V rated value":"18.5 kW","at AC-3e rated value maximum":"690 V","at AC-4 at 400 V rated value":"35 A","safety-related switching OFF":"Yes","Substance Prohibitance (Date)":"10/01/2014","Of Auxiliary Circuit Rated Value":"6 kV","at AC-5a up to 690 V rated value":"52.8 A","at AC-5b up to 400 V rated value":"33.2 A","For Auxiliary And Control Circuit":"screw-type terminals","Function Module For Communication":"No","With Type Of Assignment 2 Required":"gG: 80A (690V,100kA), aM: 50A (690V,100kA), BS88: 63A (415V,80kA)","Without Load Current Share Typical":"17.2 W","At Contactor For Auxiliary Contacts":"Screw-type terminals","With Type Of Coordination 1 Required":"gG: 160 A (690 V, 100 kA), aM: 80 A (690 V, 100 kA), BS88: 125 A (415 V, 80 kA)","operational current at AC-12 maximum":"10 A","at AC in hot operating state per pole":"2.2 W","for AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14)","number of NO contacts for main contacts":"3","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","mirror contact according to IEC 60947-4-1":"Yes","with low demand rate according to SN 31920":"40 %","with high demand rate according to SN 31920":"73 %","Type Of Voltage Of The Control Supply Voltage":"AC","Limited To 1 S Switching At Zero Current Maximum":"843 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 5 S Switching At Zero Current Maximum":"596 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 10 S Switching At Zero Current Maximum":"400 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 30 S Switching At Zero Current Maximum":"241 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 60 S Switching At Zero Current Maximum":"196 A; Use minimum cross-section acc. to AC-1 rated value","contact rating of auxiliary contacts according to UL":"A600 / P600","Of Main Circuit With Degree Of Pollution 3 Rated Value":"690 V","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","Of Auxiliary Circuit With Degree Of Pollution 3 Rated Value":"690 V","For Short-Circuit Protection Of The Auxiliary Switch Required":"gG: 10 A (500 V, 1 kA)","minimum cross-section in main circuit at maximum AC-1 rated value":"16 mm²","number of NC contacts for auxiliary contacts instantaneous contact":"1","number of NO contacts for auxiliary contacts instantaneous contact":"1","Of The Contactor With Added Electronically Optimized Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$66.04","priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=328847&mlfb=3RT2035-1AH20","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT2035-1AH20/alternatives.json"},"ai":{"faq":[{"question":"What are the key dimensions of 3RT2035-1AH20?","answer":"The 3RT2035-1AH20 measures 114 mm height, 55 mm width, and 130 mm depth."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT2035-1AH20","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT2035-1AH20 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}