{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT2037-1AH04","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT2037-1AH04","canonicalUrl":"https://aoctrl.com/siemens/3RT2037-1AH04","factsUrl":"https://aoctrl.com/api/mcp/products/3RT2037-1AH04","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS power contactor, 3RT2037-1AH04, size S2, 65 A at 480 V, screw terminals, 55 mm wide.","salesMarkdown":"The Siemens SIRIUS 3RT2037-1AH04 is a size S2 power contactor rated for 65 A at 480 V in AC-3 duty — the motor-switching rating that governs real load handling. The 65 A AC-3 rating at 480 V is the figure that decides whether this contactor handles a given motor load — AC-3 covers starting and disconnecting of squirrel-cage motors under full load. At 400 V the rated current drops to 3 A, so the 480 V figure is the high-side capability; at lower voltages the contactor carries higher currents. Size S2 means it fits the standard SIRIUS frame, so auxiliary blocks, overload relays, and busbar systems from the same S2 family mate directly without adapters. Depth is 174 mm, which is the dimension to watch when laying out gland plates or door clearance.","metaTitle":"Siemens 3RT2037-1AH04 SIRIUS Power Contactor, S2, 65 A at 48","metaDescription":"Siemens 3RT2037-1AH04 SIRIUS power contactor, size S2, 65 A rated at 480 V AC-3. Screw terminals, DIN rail mount. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"174 mm","Width":"55 mm","at AC":"10 ... 18 ms","Height":"114 mm","Upwards":"10 mm","Forwards":"10 mm","at 50 Hz":"0.37","Downwards":"10 mm","Arcing Time":"10 ... 20 ms","At The Side":"6 mm","During Storage":"-55 ... +80 °C","Of Magnet Coil":"Screw-type terminals","at AC-1 maximum":"800 1/h","at AC-2 maximum":"400 1/h","at AC-3 maximum":"700 1/h","at AC-4 maximum":"200 1/h","lifecycle_stage":"current","Auxiliary Switch":"No","During Operation":"-25 ... +60 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","at AC-3e maximum":"700 1/h","For Main Contacts":"18 ... 1","Mounting Position":"+/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface","Size Of Contactor":"S2","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Power contactor","at 24 V rated value":"6 A","at 48 V rated value":"2 A","at 60 V rated value":"2 A","Of Contactor Typical":"10 000 000","at 110 V rated value":"1 A","at 125 V rated value":"0.9 A","at 220 V rated value":"0.3 A","at 230 V rated value":"10 hp","at 400 V rated value":"3 A","at 440 V rated value":"0.6 A","at 480 V rated value":"65 A","at 50 Hz rated value":"48 V","at 500 V rated value":"2 A","at 600 V rated value":"52 A","at 690 V rated value":"1 A","Side-By-Side Mounting":"Yes","For Auxiliary Contacts":"20 ... 14","For Main Current Circuit":"screw-type terminals","at 110/120 V rated value":"5 hp","at 200/208 V rated value":"20 hp","at 220/230 V rated value":"20 hp","at 460/480 V rated value":"50 hp","at 575/600 V rated value":"50 hp","Relative Humidity Minimum":"10 %","Of Main Circuit Rated Value":"6 kV","at AC-3 rated value maximum":"690 V","at AC in hot operating state":"11.4 W","at AC-2 at 400 V rated value":"30 kW","at AC-3e rated value maximum":"690 V","at AC-4 at 400 V rated value":"55 A","safety-related switching OFF":"Yes","Substance Prohibitance (Date)":"10/01/2014","Of Auxiliary Circuit Rated Value":"6 kV","at AC-5a up to 690 V rated value":"70.4 A","at AC-5b up to 400 V rated value":"53.9 A","For Auxiliary And Control Circuit":"screw-type terminals","Function Module For Communication":"No","With Type Of Assignment 2 Required":"gG: 125A (690V,100kA), aM: 63A (690V,100kA), BS88: 100A (415V,80kA)","Without Load Current Share Typical":"16 W","At Contactor For Auxiliary Contacts":"Screw-type terminals","With Type Of Coordination 1 Required":"gG: 250 A (690 V, 100 kA), aM: 160 A (690 V, 100 kA), BS88: 200 A (415 V, 80 kA)","operational current at AC-12 maximum":"10 A","at AC in hot operating state per pole":"3.8 W","for AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14)","number of NO contacts for main contacts":"3","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","mirror contact according to IEC 60947-4-1":"Yes","with low demand rate according to SN 31920":"40 %","with high demand rate according to SN 31920":"73 %","Type Of Voltage Of The Control Supply Voltage":"AC","Limited To 1 S Switching At Zero Current Maximum":"1 055 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 5 S Switching At Zero Current Maximum":"730 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 10 S Switching At Zero Current Maximum":"520 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 30 S Switching At Zero Current Maximum":"336 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 60 S Switching At Zero Current Maximum":"272 A; Use minimum cross-section acc. to AC-1 rated value","contact rating of auxiliary contacts according to UL":"A600 / Q600","Of Main Circuit With Degree Of Pollution 3 Rated Value":"690 V","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","Of Auxiliary Circuit With Degree Of Pollution 3 Rated Value":"690 V","For Short-Circuit Protection Of The Auxiliary Switch Required":"gG: 10 A (500 V, 1 kA)","minimum cross-section in main circuit at maximum AC-1 rated value":"25 mm²","number of NC contacts for auxiliary contacts instantaneous contact":"2","number of NO contacts for auxiliary contacts instantaneous contact":"2","Of The Contactor With Added Electronically Optimized Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=270795&mlfb=3RT2037-1AH04","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT2037-1AH04/alternatives.json"},"ai":{"faq":[{"question":"What are the key dimensions for panel layout?","answer":"Width 55 mm, height 114 mm, depth 174 mm. Clearance: 10 mm upwards, forwards, and downwards; 6 mm at the sides."},{"question":"What is the AC-3 current rating at 480 V?","answer":"65 A at 480 V in AC-3 duty — this is the motor-switching rating that determines load capability."},{"question":"Does the 3RT2037-1AH04 mount on standard DIN rail?","answer":"Yes, screw and snap-on mounting onto 35 mm DIN rail per DIN EN 60715."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT2037-1AH04","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT2037-1AH04 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}