{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT2038-1AK64","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT2038-1AK64","canonicalUrl":"https://aoctrl.com/siemens/3RT2038-1AK64","factsUrl":"https://aoctrl.com/api/mcp/products/3RT2038-1AK64","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RT2038-1AK64 power contactor, Size S2, 65 A at 480 V AC-3, 3-pole, screw-type coil terminals, screw and snap-on mounting on 35 mm DIN rail.","salesMarkdown":"## 65 A AC-3 switching in an S2 frame The 3RT2038-1AK64: That 65 A figure at 480 V is the rating that decides the motor FLA it can handle; for a 480 V motor, this contactor covers loads up to roughly 65 A full-load current without derating. ## Switching frequency and coil ratings Maximum switching rates are duty-dependent: 700 operations per hour in AC-1 (resistive loads), 500/h in AC-3 and AC-3e (motor starting), 350/h in AC-2 (slip-ring motors), and 150/h in AC-4 (plugging/inching). ## Environmental limits and mechanical life The contactor is rated for 10 million mechanical operations typical, which for most panel applications outlasts the electrical contact life under load. These are the minimum air gaps needed to avoid arc flashover between contactors mounted side-by-side on the same DIN rail.","metaTitle":"Siemens 3RT2038-1AK64 SIRIUS Contactor, 65 A AC-3, S2 Size","metaDescription":"Siemens 3RT2038-1AK64 SIRIUS power contactor, 65 A at 480 V AC-3, S2 frame, screw terminals, DIN rail mount. Active production, sourced per RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"174 mm","Width":"55 mm","at AC":"10 ... 18 ms","title":"3RT2038-1AK64","Height":"114 mm","Upwards":"10 mm","Forwards":"10 mm","at 50 Hz":"0.36","at 60 Hz":"0.39","Downwards":"10 mm","Arcing Time":"10 ... 20 ms","At The Side":"6 mm","description":"power contactor, AC-3e/AC-3, 80 A, 37 kW / 400 V, 3-pole, 110 V AC, 50 Hz / 120 V, 60 Hz, auxiliary contacts: 2 NO + 2 NC, screw terminal, size: S2, removable auxiliary switch","During Storage":"-55 ... +80 °C","Of Magnet Coil":"Screw-type terminals","at AC-1 maximum":"700 1/h","at AC-2 maximum":"350 1/h","at AC-3 maximum":"500 1/h","at AC-4 maximum":"150 1/h","lifecycle_stage":"current","Auxiliary Switch":"No","During Operation":"-25 ... +60 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","at AC-3e maximum":"500 1/h","For Main Contacts":"18 ... 1","Mounting Position":"+/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface","Size Of Contactor":"S2","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Power contactor","at 24 V rated value":"6 A","at 48 V rated value":"2 A","at 60 V rated value":"2 A","Of Contactor Typical":"10 000 000","at 110 V rated value":"1 A","at 125 V rated value":"0.9 A","at 220 V rated value":"0.3 A","at 230 V rated value":"15 hp","at 400 V rated value":"3 A","at 440 V rated value":"0.6 A","at 480 V rated value":"65 A","at 50 Hz rated value":"110 V","at 500 V rated value":"2 A","at 60 Hz rated value":"120 V","at 600 V rated value":"62 A","at 690 V rated value":"1 A","Side-By-Side Mounting":"Yes","For Auxiliary Contacts":"20 ... 14","For Main Current Circuit":"screw-type terminals","at 110/120 V rated value":"5 hp","at 200/208 V rated value":"20 hp","at 220/230 V rated value":"25 hp","at 460/480 V rated value":"50 hp","at 575/600 V rated value":"60 hp","Relative Humidity Minimum":"10 %","Of Main Circuit Rated Value":"6 kV","at AC-3 rated value maximum":"690 V","at AC in hot operating state":"17.1 W","at AC-2 at 400 V rated value":"37 kW","at AC-3e rated value maximum":"690 V","at AC-4 at 400 V rated value":"55 A","safety-related switching OFF":"Yes","Substance Prohibitance (Date)":"10/01/2014","Of Auxiliary Circuit Rated Value":"6 kV","at AC-5a up to 690 V rated value":"79.2 A","at AC-5b up to 400 V rated value":"66.4 A","For Auxiliary And Control Circuit":"screw-type terminals","Function Module For Communication":"No","With Type Of Assignment 2 Required":"gG: 160A (690V,100kA), aM: 80A (690V,100kA), BS88: 125A (415V,80kA)","Without Load Current Share Typical":"18.5 W","At Contactor For Auxiliary Contacts":"Screw-type terminals","With Type Of Coordination 1 Required":"gG: 250 A (690 V, 100 kA), aM: 160 A (690 V, 100 kA), BS88: 200 A (415 V, 80 kA)","operational current at AC-12 maximum":"10 A","at AC in hot operating state per pole":"5.7 W","for AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14)","number of NO contacts for main contacts":"3","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","mirror contact according to IEC 60947-4-1":"Yes","with low demand rate according to SN 31920":"40 %","with high demand rate according to SN 31920":"73 %","Type Of Voltage Of The Control Supply Voltage":"AC","Limited To 1 S Switching At Zero Current Maximum":"1 298 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 5 S Switching At Zero Current Maximum":"898 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 10 S Switching At Zero Current Maximum":"640 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 30 S Switching At Zero Current Maximum":"414 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 60 S Switching At Zero Current Maximum":"333 A; Use minimum cross-section acc. to AC-1 rated value","contact rating of auxiliary contacts according to UL":"A600 / Q600","Of Main Circuit With Degree Of Pollution 3 Rated Value":"690 V","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","Of Auxiliary Circuit With Degree Of Pollution 3 Rated Value":"690 V","For Short-Circuit Protection Of The Auxiliary Switch Required":"gG: 10 A (500 V, 1 kA)","minimum cross-section in main circuit at maximum AC-1 rated value":"35 mm²","number of NC contacts for auxiliary contacts instantaneous contact":"2","number of NO contacts for auxiliary contacts instantaneous contact":"2","Of The Contactor With Added Electronically Optimized Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/23bbb30ffb900fe17f9b7cf140374e53.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=513941&mlfb=3RT2038-1AK64"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT2038-1AK64","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT2038-1AK64 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}