{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT2045-1NF34","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT2045-1NF34","canonicalUrl":"https://aoctrl.com/siemens/3RT2045-1NF34","factsUrl":"https://aoctrl.com/api/mcp/products/3RT2045-1NF34","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RT2045-1NF34 power contactor, Size S3, 83-155 VAC 50/60 Hz coil, screw-type terminals, 70 mm width, 140 mm height, 195 mm depth.","salesMarkdown":"The 3RT2045-1NF34: The 83-155 VAC 50/60 Hz coil means it pulls in reliably across a sagging line — the dropout threshold is 0.8× rated, so on a 120 VAC control circuit it holds in down to about 96 V before the armature drops. Coil inrush peaks at 1.5 A, but the sealed holding draw is only 3.5 VA at both 50 and 60 Hz — the PLC output driving this contactor sees a brief surge then a light steady load. Mechanical life is rated 10 million operations typical — the limiting factor in a real panel is the electrical endurance under the specific duty cycle, not the mechanical count. ## Wire range and terminal access — S3 frame Main power terminals accept solid wire 2.5 to 16 mm² or stranded 6 to 70 mm² — the screw-type terminals handle the full range without lug adapters, but the larger stranded sizes need a ferrule for consistent torque. ## Switching frequency and duty-cycle limits Maximum switching rate depends on the duty category: 1 000 operations/hour in AC-3 and AC-3e, 900 in AC-1, 400 in AC-2, and 300 in AC-4 — the AC-4 limit is the binding constraint for reversing or plugging applications. Auxiliary switch block is included — the contactor ships with at least one built-in auxiliary contact, so you don't need a separate side-mount for basic feedback to the PLC.","metaTitle":"Siemens 3RT2045-1NF34 SIRIUS Power Contactor, S3 Frame","metaDescription":"Siemens 3RT2045-1NF34 SIRIUS power contactor, S3 frame, 83-155 VAC coil, screw terminals. Current production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"195 mm","Solid":"2.5 ... 16 mm²","Width":"70 mm","at AC":"38 ... 57 ms","at DC":"38 ... 57 ms","title":"3RT2045-1NF34","Height":"140 mm","Upwards":"10 mm","Forwards":"20 mm","Stranded":"6 ... 70 mm²","at 50 Hz":"3.5 VA","at 60 Hz":"3.5 VA","Downwards":"10 mm","Arcing Time":"10 ... 20 ms","At The Side":"10 mm","Rated Value":"83 ... 155 V","description":"power contactor, AC-3e/AC-3, 80 A, 37 kW / 400 V, 3-pole, 83-155 V AC/DC, 50/60 Hz, with integrated varistor, auxiliary contacts: 2 NO + 2 NC, screw terminal, size: S3, removable auxiliary switch","Initial Value":"0.8","During Storage":"-55 ... +80 °C","Of Magnet Coil":"Screw-type terminals","at AC-1 maximum":"900 1/h","at AC-2 maximum":"400 1/h","at AC-3 maximum":"1 000 1/h","at AC-4 maximum":"300 1/h","lifecycle_stage":"current","Auxiliary Switch":"Yes","During Operation":"-25 ... +60 °C","Fastening Method":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 60715","Full-Scale Value":"1.1","at AC-3e maximum":"1 000 1/h","For Main Contacts":"10 ... 2","Mounting Position":"+/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface","Size Of Contactor":"S3","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Product Brand Name":"SIRIUS","Inrush Current Peak":"1.5 A","Product Designation":"Power contactor","at 24 V rated value":"6 A","at 48 V rated value":"2 A","at 60 V rated value":"2 A","Of Contactor Typical":"10 000 000","at 110 V rated value":"1 A","at 125 V rated value":"0.9 A","at 220 V rated value":"0.3 A","at 230 V rated value":"15 hp","at 400 V rated value":"3 A","at 440 V rated value":"0.8 A","at 480 V rated value":"77 A","at 50 Hz rated value":"83 ... 155 V","at 500 V rated value":"2 A","at 60 Hz rated value":"83 ... 155 V","at 600 V rated value":"62 A","at 690 V rated value":"1 A","Side-By-Side Mounting":"Yes","at 1000 V rated value":"37 kW","For Auxiliary Contacts":"20 ... 14","For Main Current Circuit":"screw-type terminals","at 110/120 V rated value":"7.5 hp","at 200/208 V rated value":"25 hp","at 220/230 V rated value":"30 hp","at 460/480 V rated value":"60 hp","at 575/600 V rated value":"60 hp","Locked-Rotor Current Peak":"2.7 A","Relative Humidity Minimum":"10 %","Holding Current Mean Value":"15 mA","Of Main Circuit Rated Value":"8 kV","Safety-Related Switching On":"No","at AC-3 rated value maximum":"1 000 V","at AC in hot operating state":"15.9 W","at AC-2 at 400 V rated value":"37 kW","at AC-3e rated value maximum":"1 000 V","at AC-4 at 400 V rated value":"66 A","safety-related switching OFF":"Yes","Substance Prohibitance (Date)":"03/01/2017","Design Of The Surge Suppressor":"with varistor","Duration Of Inrush Current Peak":"50 µs","Locked-Rotor Current Mean Value":"1.1 A","at AWG cables for main contacts":"2x (10 ... 1/0), 1x (10 ... 2)","Duration Of Locked-Rotor Current":"150 ms","Of Auxiliary Circuit Rated Value":"6 kV","at AC-5a up to 690 V rated value":"110 A","at AC-5b up to 400 V rated value":"80 A","For Auxiliary And Control Circuit":"screw-type terminals","Function Module For Communication":"No","With Type Of Assignment 2 Required":"gG: 160A (690V,100kA), aM: 80A (690V,100kA), BS88: 125A (415V,80kA)","Without Load Current Share Typical":"3.5 W","closing power of magnet coil at DC":"76 W","holding power of magnet coil at DC":"2.7 W","At Contactor For Auxiliary Contacts":"Screw-type terminals","With Type Of Coordination 1 Required":"gG: 250 A (690 V, 100 kA), aM: 160 A (690 V, 100 kA), BS88: 200 A (415 V, 80 kA)","at AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14)","operational current at AC-12 maximum":"10 A","at AC in hot operating state per pole":"5.3 W","number of NO contacts for main contacts":"3","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","mirror contact according to IEC 60947-4-1":"Yes","with low demand rate according to SN 31920":"40 %","with high demand rate according to SN 31920":"73 %","Type Of Voltage Of The Control Supply Voltage":"AC/DC","Limited To 1 S Switching At Zero Current Maximum":"1 500 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 5 S Switching At Zero Current Maximum":"1 186 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 10 S Switching At Zero Current Maximum":"851 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 30 S Switching At Zero Current Maximum":"538 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 60 S Switching At Zero Current Maximum":"423 A; Use minimum cross-section acc. to AC-1 rated value","contact rating of auxiliary contacts according to UL":"A600 / P600","Of Main Circuit With Degree Of Pollution 3 Rated Value":"1 000 V","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","Of Auxiliary Circuit With Degree Of Pollution 3 Rated Value":"690 V","For Short-Circuit Protection Of The Auxiliary Switch Required":"gG: 10 A (500 V, 1 kA)","minimum cross-section in main circuit at maximum AC-1 rated value":"50 mm²","number of NC contacts for auxiliary contacts instantaneous contact":"2","number of NO contacts for auxiliary contacts instantaneous contact":"2","Of The Contactor With Added Electronically Optimized Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/7d28fa7380658c541019ac8751bc4da6.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=629808&mlfb=3RT2045-1NF34"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT2045-1NF34","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT2045-1NF34 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}