{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT2046-1AQ20","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT2046-1AQ20","canonicalUrl":"https://aoctrl.com/siemens/3RT2046-1AQ20","factsUrl":"https://aoctrl.com/api/mcp/products/3RT2046-1AQ20","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS, power contactor, size S3, 3RT2046-1AQ20, screw-type terminals, 152 mm depth, 70 mm width, 140 mm height.","salesMarkdown":"## Integrator note — SIRIUS S3 contactor 3RT2046-1AQ20 It occupies a 70 mm width, 140 mm height, and 152 mm depth on the rail, with clearance requirements of 10 mm upwards, 10 mm downwards, 20 mm forwards, and 10 mm at the side. Wire range accepts 2.5 to 16 mm² solid conductors and 6 to 70 mm² stranded conductors on the main circuit. ## Duty-cycle switching frequencies and auxiliary contact ratings Maximum switching frequency varies by duty: 900 operations/hour at AC-1, 350 at AC-2, 850 at AC-3 (and AC-3e), and 250 at AC-4. Auxiliary switch contacts are rated at 10 A at 24 V, 2 A at 48 V and 60 V, 1 A at 110 V, 0.9 A at 125 V, 0.3 A at 220 V, 3 A at 400 V, and 0.8 A at 440 V. Arcing time is 10 to 20 ms, with a make time of 10 to 21 ms at AC. Mechanical endurance of the contactor is typically 10,000,000 operations.","metaTitle":"Siemens SIRIUS 3RT2046-1AQ20 Power Contactor, S3, 152 mm Dep","metaDescription":"Siemens SIRIUS 3RT2046-1AQ20 power contactor, size S3, screw terminals, 152 mm depth, 70 mm width. Active lifecycle. Sourced to order against RFQ. Wire range 2.5–16 mm² solid, 6–70","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"152 mm","Solid":"2.5 ... 16 mm²","Width":"70 mm","at AC":"10 ... 21 ms","Height":"140 mm","Upwards":"10 mm","Forwards":"20 mm","Stranded":"6 ... 70 mm²","at 50 Hz":"0.35","at 60 Hz":"0.41","Downwards":"10 mm","Arcing Time":"10 ... 20 ms","At The Side":"10 mm","During Storage":"-55 ... +80 °C","Of Magnet Coil":"Screw-type terminals","at AC-1 maximum":"900 1/h","at AC-2 maximum":"350 1/h","at AC-3 maximum":"850 1/h","at AC-4 maximum":"250 1/h","lifecycle_stage":"current","Auxiliary Switch":"Yes","During Operation":"-25 ... +60 °C","Fastening Method":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 60715","at AC-3e maximum":"850 1/h","For Main Contacts":"10 ... 2","Mounting Position":"+/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface","Size Of Contactor":"S3","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Power contactor","at 24 V rated value":"10 A","at 48 V rated value":"2 A","at 60 V rated value":"2 A","Of Contactor Typical":"10 000 000","at 110 V rated value":"1 A","at 125 V rated value":"0.9 A","at 220 V rated value":"0.3 A","at 230 V rated value":"20 hp","at 400 V rated value":"3 A","at 440 V rated value":"0.8 A","at 480 V rated value":"96 A","at 50 Hz rated value":"500 V","at 500 V rated value":"2 A","at 60 Hz rated value":"500 V","at 600 V rated value":"77 A","at 690 V rated value":"1 A","Side-By-Side Mounting":"Yes","at 1000 V rated value":"37 kW","For Auxiliary Contacts":"20 ... 14","For Main Current Circuit":"screw-type terminals","at 110/120 V rated value":"10 hp","at 200/208 V rated value":"30 hp","at 220/230 V rated value":"30 hp","at 460/480 V rated value":"75 hp","at 575/600 V rated value":"75 hp","Relative Humidity Minimum":"10 %","Of Main Circuit Rated Value":"8 kV","Safety-Related Switching On":"Yes","at AC-3 rated value maximum":"1 000 V","at AC in hot operating state":"19.8 W","at AC-2 at 400 V rated value":"45 kW","at AC-3e rated value maximum":"1 000 V","at AC-4 at 400 V rated value":"80 A","safety-related switching OFF":"Yes","Substance Prohibitance (Date)":"03/01/2017","at AWG cables for main contacts":"2x (10 ... 1/0), 1x (10 ... 2)","Of Auxiliary Circuit Rated Value":"6 kV","at AC-5a up to 690 V rated value":"114 A","at AC-5b up to 400 V rated value":"95 A","For Auxiliary And Control Circuit":"screw-type terminals","Function Module For Communication":"No","With Type Of Assignment 2 Required":"gG: 160 A (690 V, 100 kA), aM: 100 A (690 V, 100 kA), BS88: 125 A (415 V, 80 kA)","Without Load Current Share Typical":"25 W","At Contactor For Auxiliary Contacts":"Screw-type terminals","With Type Of Coordination 1 Required":"gG: 250 A (690 V, 100 kA), aM: 160 A (690 V, 100 kA), BS88: 200 A (415 V, 80 kA)","at AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14)","operational current at AC-12 maximum":"10 A","at AC in hot operating state per pole":"6.6 W","number of NO contacts for main contacts":"3","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","mirror contact according to IEC 60947-4-1":"Yes","with low demand rate according to SN 31920":"40 %","with high demand rate according to SN 31920":"73 %","Type Of Voltage Of The Control Supply Voltage":"AC","Limited To 1 S Switching At Zero Current Maximum":"1 725 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 5 S Switching At Zero Current Maximum":"1 297 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 10 S Switching At Zero Current Maximum":"946 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 30 S Switching At Zero Current Maximum":"610 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 60 S Switching At Zero Current Maximum":"486 A; Use minimum cross-section acc. to AC-1 rated value","contact rating of auxiliary contacts according to UL":"A600 / P600","Of Main Circuit With Degree Of Pollution 3 Rated Value":"1 000 V","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","Of Auxiliary Circuit With Degree Of Pollution 3 Rated Value":"690 V","For Short-Circuit Protection Of The Auxiliary Switch Required":"gG: 10 A (500 V, 1 kA)","minimum cross-section in main circuit at maximum AC-1 rated value":"50 mm²","number of NC contacts for auxiliary contacts instantaneous contact":"1","number of NO contacts for auxiliary contacts instantaneous contact":"1","Of The Contactor With Added Electronically Optimized Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/7d28fa7380658c541019ac8751bc4da6.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=629874&mlfb=3RT2046-1AQ20","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT2046-1AQ20/alternatives.json"},"ai":{"faq":[{"question":"What is 3RT2046-1AQ20's listed depth?","answer":"The depth is 152 mm."},{"question":"What wire sizes does 3RT2046-1AQ20 accept?","answer":"It accepts 2.5 to 16 mm² solid and 6 to 70 mm² stranded conductors on the main circuit."},{"question":"Will 3RT2046-1AQ20 drop into a panel specified around 3RT1054-1AB36 without rewiring?","answer":"Both are SIRIUS S3 contactors with screw terminals, so the footprint and mounting rail are identical; however, verify auxiliary contact configuration and coil voltage on your specific BOM before substitution."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT2046-1AQ20","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT2046-1AQ20 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}