{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT2046-1AR64","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT2046-1AR64","canonicalUrl":"https://aoctrl.com/siemens/3RT2046-1AR64","factsUrl":"https://aoctrl.com/api/mcp/products/3RT2046-1AR64","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS S3 power contactor, 3RT2046-1AR64, screw-type terminals, auxiliary switch, 70 mm width, screw and snap-on mounting on 35 mm DIN rail.","salesMarkdown":"The Siemens 3RT2046-1AR64 is a SIRIUS S3 power contactor with screw-type main contact terminals and an integrated auxiliary switch block. The S3 frame size (70 mm wide, 140 mm high, 195 mm deep) fits standard panel layouts. Rated switching rates tell you the mechanical duty it can sustain: 900 cycles/hour for AC-1 resistive loads, 850 cycles/hour for AC-3 motor starting, and 250 cycles/hour for AC-4 plugging or inching. The AC-3e rating matches the AC-3 figure at 850 1/h. These are the limits for continuous cycling — exceeding them shortens contact life. The auxiliary contact block carries 6 A at 24 V, 2 A at 48 V or 60 V, 1 A at 110 V, 0.9 A at 125 V, 0.3 A at 220 V, and 3 A at 400 V. These are the rated values for the auxiliary circuit — use them to confirm compatibility with your PLC input or relay coil draw. ## Wire termination and clearance Main contact terminals accept solid conductors from 2.5 to 16 mm² and stranded conductors from 6 to 70 mm². Auxiliary terminals accept two conductors per clamp: 0.5–1.5 mm² or 0.75–2.5 mm² solid or stranded. These ranges cover most motor and control wiring in industrial panels. The arcing time is 10–20 ms, and the switching time (at AC) is 10–21 ms — these are the intervals the contactor needs to make or break the circuit cleanly.","metaTitle":"Siemens 3RT2046-1AR64 SIRIUS S3 Power Contactor, 70 mm","metaDescription":"Siemens SIRIUS S3 power contactor 3RT2046-1AR64. Screw terminals, auxiliary switch, screw & snap-on DIN rail mount. 850 1/h AC-3 switching rate. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"195 mm","Solid":"2.5 ... 16 mm²","Width":"70 mm","at AC":"10 ... 21 ms","Height":"140 mm","Upwards":"10 mm","Forwards":"20 mm","Stranded":"6 ... 70 mm²","at 50 Hz":"0.35","at 60 Hz":"0.41","Downwards":"10 mm","Arcing Time":"10 ... 20 ms","At The Side":"10 mm","During Storage":"-55 ... +80 °C","Of Magnet Coil":"Screw-type terminals","at AC-1 maximum":"900 1/h","at AC-2 maximum":"350 1/h","at AC-3 maximum":"850 1/h","at AC-4 maximum":"250 1/h","lifecycle_stage":"current","Auxiliary Switch":"Yes","During Operation":"-25 ... +60 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","at AC-3e maximum":"850 1/h","For Main Contacts":"10 ... 2","Mounting Position":"+/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface","Size Of Contactor":"S3","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Power contactor","at 24 V rated value":"6 A","at 48 V rated value":"2 A","at 60 V rated value":"2 A","Of Contactor Typical":"10 000 000","at 110 V rated value":"1 A","at 125 V rated value":"0.9 A","at 220 V rated value":"0.3 A","at 230 V rated value":"20 hp","at 400 V rated value":"3 A","at 440 V rated value":"0.8 A","at 480 V rated value":"96 A","at 50 Hz rated value":"400 V","at 500 V rated value":"2 A","at 60 Hz rated value":"400 ... 440 V","at 600 V rated value":"77 A","at 690 V rated value":"1 A","Side-By-Side Mounting":"Yes","at 1000 V rated value":"37 kW","For Auxiliary Contacts":"20 ... 14","For Main Current Circuit":"screw-type terminals","at 110/120 V rated value":"10 hp","at 200/208 V rated value":"30 hp","at 220/230 V rated value":"30 hp","at 460/480 V rated value":"75 hp","at 575/600 V rated value":"75 hp","Relative Humidity Minimum":"10 %","Of Main Circuit Rated Value":"8 kV","Safety-Related Switching On":"Yes","at AC-3 rated value maximum":"1 000 V","at AC in hot operating state":"19.8 W","at AC-2 at 400 V rated value":"45 kW","at AC-3e rated value maximum":"1 000 V","at AC-4 at 400 V rated value":"80 A","safety-related switching OFF":"Yes","Substance Prohibitance (Date)":"03/01/2017","Of Auxiliary Circuit Rated Value":"6 kV","at AC-5a up to 690 V rated value":"114 A","at AC-5b up to 400 V rated value":"95 A","For Auxiliary And Control Circuit":"screw-type terminals","Function Module For Communication":"No","With Type Of Assignment 2 Required":"gG: 160 A (690 V, 100 kA), aM: 100 A (690 V, 100 kA), BS88: 125 A (415 V, 80 kA)","Without Load Current Share Typical":"25 W","At Contactor For Auxiliary Contacts":"Screw-type terminals","With Type Of Coordination 1 Required":"gG: 250 A (690 V, 100 kA), aM: 160 A (690 V, 100 kA), BS88: 200 A (415 V, 80 kA)","operational current at AC-12 maximum":"10 A","at AC in hot operating state per pole":"6.6 W","for AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14)","number of NO contacts for main contacts":"3","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","mirror contact according to IEC 60947-4-1":"Yes","with low demand rate according to SN 31920":"40 %","with high demand rate according to SN 31920":"73 %","Type Of Voltage Of The Control Supply Voltage":"AC","Limited To 1 S Switching At Zero Current Maximum":"1 725 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 5 S Switching At Zero Current Maximum":"1 297 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 10 S Switching At Zero Current Maximum":"946 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 30 S Switching At Zero Current Maximum":"610 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 60 S Switching At Zero Current Maximum":"486 A; Use minimum cross-section acc. to AC-1 rated value","contact rating of auxiliary contacts according to UL":"A600 / P600","Of Main Circuit With Degree Of Pollution 3 Rated Value":"1 000 V","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","Of Auxiliary Circuit With Degree Of Pollution 3 Rated Value":"690 V","For Short-Circuit Protection Of The Auxiliary Switch Required":"gG: 10 A (500 V, 1 kA)","minimum cross-section in main circuit at maximum AC-1 rated value":"50 mm²","number of NC contacts for auxiliary contacts instantaneous contact":"2","number of NO contacts for auxiliary contacts instantaneous contact":"2","Of The Contactor With Added Electronically Optimized Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/7d28fa7380658c541019ac8751bc4da6.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=629877&mlfb=3RT2046-1AR64","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT2046-1AR64/alternatives.json"},"ai":{"faq":[{"question":"What is the depth of 3RT2046-1AR64?","answer":"The depth is 195 mm. Overall dimensions are 70 mm wide by 140 mm high by 195 mm deep."},{"question":"What wire sizes does 3RT2046-1AR64 accept on the main contacts?","answer":"Solid conductors from 2.5 to 16 mm² and stranded conductors from 6 to 70 mm². Auxiliary terminals accept 2x (0.5–1.5 mm²) or 2x (0.75–2.5 mm²)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT2046-1AR64","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT2046-1AR64 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}