{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT2047-3NF30","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT2047-3NF30","canonicalUrl":"https://aoctrl.com/siemens/3RT2047-3NF30","factsUrl":"https://aoctrl.com/api/mcp/products/3RT2047-3NF30","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RT2047-3NF30 power contactor, size S3, coil rated 83–155 V AC/DC, spring-type terminals, screw and snap-on mounting onto 35 mm DIN rail per DIN EN 60715.","salesMarkdown":"## SIRIUS S3 Power Contactor — 83–155 V Coil, Spring-Terminal It mounts on 35 mm DIN rail per DIN EN 60715 via screw or snap-on fastening, with a mounting position that allows ±180° rotation on a vertical surface and ±22.5° tilt forward or backward — useful when fitting into tight enclosures or existing layouts. The coil accepts 83–155 V AC/DC with an inrush peak of 1.5 A and a holding draw of 3.5 VA at both 50 Hz and 60 Hz. That coil voltage range covers common 110–120 V control circuits in North America and 110 V nominal in European schemes, so it slots into standard control transformers without a separate dropping resistor. Main contact wire range accepts solid conductors from 2.5 to 16 mm² and stranded from 6 to 70 mm² — heavy enough for the S3 frame's typical motor currents. Auxiliary contacts are present and rated at 10 A at 24 V, 2 A at 48 V and 60 V, and 1 A at 110 V, which covers pilot-duty and PLC input signalling without an interposing relay. ## Duty-Cycle Rates — Which One Governs Your Load The 3RT2047-3NF30 is rated for different switching frequencies depending on the duty category. For AC-1 (resistive loads) it manages 900 operations per hour; for AC-3 (squirrel-cage motor starting) it handles 850 per hour; AC-2 (slip-ring motor starting) drops to 350 per hour; and AC-4 (plugging/inching) is limited to 200 per hour. The AC-3e rating mirrors the AC-3 figure at 850 per hour. If your application involves frequent jogging or reversing, the AC-4 ceiling is the one that governs contact life — plan around 200 cycles/hour max, not the higher AC-3 number. Dimensions are 140 mm high, 70 mm wide, and 152 mm deep. The spring-type terminals on the coil accept solid or stranded wire 2x (0.5–2.5 mm²). The contactor carries auxiliary switches as standard, so no separate add-on block is needed for basic signalling.","metaTitle":"Siemens 3RT2047-3NF30 SIRIUS Power Contactor, S3, 83-155V Co","metaDescription":"Siemens SIRIUS 3RT2047-3NF30 power contactor, size S3, coil 83-155 V AC/DC. Screw & snap-on 35mm DIN rail. Current lifecycle stage. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"152 mm","Solid":"2.5 ... 16 mm²","Width":"70 mm","at AC":"38 ... 57 ms","at DC":"38 ... 57 ms","title":"3RT2047-3NF30","Height":"140 mm","Upwards":"10 mm","Forwards":"20 mm","Stranded":"6 ... 70 mm²","at 50 Hz":"3.5 VA","at 60 Hz":"3.5 VA","Downwards":"10 mm","Arcing Time":"10 ... 20 ms","At The Side":"10 mm","Rated Value":"83 ... 155 V","description":"power contactor, AC-3e/AC-3, 110 A, 55 kW / 400 V, 3-pole, 83-155 V AC/DC, 50/60 Hz, with integrated varistor, auxiliary contacts: 1 NO + 1 NC, main circuit: screw terminal, control and auxiliary circuit: spring-loaded terminal, size: S3","Initial Value":"0.8","During Storage":"-55 ... +80 °C","Of Magnet Coil":"Spring-type terminals","at AC-1 maximum":"900 1/h","at AC-2 maximum":"350 1/h","at AC-3 maximum":"850 1/h","at AC-4 maximum":"200 1/h","lifecycle_stage":"current","Auxiliary Switch":"Yes","During Operation":"-25 ... +60 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","Full-Scale Value":"1.1","at AC-3e maximum":"850 1/h","For Main Contacts":"10 ... 2","Mounting Position":"+/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface","Size Of Contactor":"S3","Solid Or Stranded":"2x (0.5 ... 2.5 mm²)","Product Brand Name":"SIRIUS","Inrush Current Peak":"1.5 A","Product Designation":"Power contactor","at 24 V rated value":"10 A","at 48 V rated value":"2 A","at 60 V rated value":"2 A","Of Contactor Typical":"10 000 000","at 110 V rated value":"1 A","at 125 V rated value":"0.9 A","at 220 V rated value":"0.3 A","at 230 V rated value":"20 hp","at 400 V rated value":"3 A","at 440 V rated value":"0.8 A","at 480 V rated value":"96 A","at 50 Hz rated value":"83 ... 155 V","at 500 V rated value":"2 A","at 60 Hz rated value":"83 ... 155 V","at 600 V rated value":"99 A","at 690 V rated value":"1 A","Side-By-Side Mounting":"Yes","at 1000 V rated value":"37 kW","For Auxiliary Contacts":"20 ... 14","For Main Current Circuit":"screw-type terminals","at 110/120 V rated value":"10 hp","at 200/208 V rated value":"30 hp","at 220/230 V rated value":"40 hp","at 460/480 V rated value":"75 hp","at 575/600 V rated value":"100 hp","Locked-Rotor Current Peak":"2.7 A","Relative Humidity Minimum":"10 %","Holding Current Mean Value":"15 mA","Of Main Circuit Rated Value":"8 kV","Safety-Related Switching On":"No","at AC-3 rated value maximum":"1 000 V","at AC in hot operating state":"23.7 W","at AC-2 at 400 V rated value":"55 kW","at AC-3e rated value maximum":"1 000 V","at AC-4 at 400 V rated value":"97 A","safety-related switching OFF":"Yes","Substance Prohibitance (Date)":"03/01/2017","Design Of The Surge Suppressor":"with varistor","Duration Of Inrush Current Peak":"50 µs","Locked-Rotor Current Mean Value":"1.1 A","at AWG cables for main contacts":"2x (10 ... 1/0), 1x (10 ... 2)","Duration Of Locked-Rotor Current":"150 ms","Of Auxiliary Circuit Rated Value":"6 kV","at AC-5a up to 690 V rated value":"120 A","at AC-5b up to 400 V rated value":"110 A","For Auxiliary And Control Circuit":"spring-loaded terminals","Function Module For Communication":"No","With Type Of Assignment 2 Required":"gG: 200A (690V,100kA), aM: 100A (690V,100kA), BS88: 160A (415V,80kA)","Without Load Current Share Typical":"3.5 W","closing power of magnet coil at DC":"76 W","holding power of magnet coil at DC":"2.7 W","At Contactor For Auxiliary Contacts":"Spring-type terminals","With Type Of Coordination 1 Required":"gG: 250 A (690 V, 100 kA), aM: 160 A (690 V, 100 kA), BS88: 200 A (415 V, 80 kA)","at AWG cables for auxiliary contacts":"2x (20 ... 16)","operational current at AC-12 maximum":"10 A","at AC in hot operating state per pole":"7.9 W","number of NO contacts for main contacts":"3","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²)","Number Of Poles For Main Current Circuit":"3","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","mirror contact according to IEC 60947-4-1":"Yes","with low demand rate according to SN 31920":"40 %","Finely Stranded Without Core End Processing":"2x (0.5 ... 2.5 mm²)","with high demand rate according to SN 31920":"73 %","Type Of Voltage Of The Control Supply Voltage":"AC/DC","Limited To 1 S Switching At Zero Current Maximum":"1 960 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 5 S Switching At Zero Current Maximum":"1 502 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 10 S Switching At Zero Current Maximum":"1 095 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 30 S Switching At Zero Current Maximum":"707 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 60 S Switching At Zero Current Maximum":"562 A; Use minimum cross-section acc. to AC-1 rated value","contact rating of auxiliary contacts according to UL":"A600 / P600","Of Main Circuit With Degree Of Pollution 3 Rated Value":"1 000 V","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","Of Auxiliary Circuit With Degree Of Pollution 3 Rated Value":"690 V","For Short-Circuit Protection Of The Auxiliary Switch Required":"gG: 10 A (500 V, 1 kA)","minimum cross-section in main circuit at maximum AC-1 rated value":"50 mm²","number of NC contacts for auxiliary contacts instantaneous contact":"1","number of NO contacts for auxiliary contacts instantaneous contact":"1","Of The Contactor With Added Electronically Optimized Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/7d28fa7380658c541019ac8751bc4da6.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=629955&mlfb=3RT2047-3NF30"},"ai":{"faq":[{"question":"What is the coil voltage range for 3RT2047-3NF30?","answer":"The coil is rated 83–155 V AC/DC. Inrush peak is 1.5 A; holding power is 3.5 VA at 50/60 Hz. Pick-up and drop-out times are 38–57 ms for both AC and DC supplies."},{"question":"What wire sizes does the 3RT2047-3NF30 accept?","answer":"Main contacts accept solid conductors 2.5–16 mm² and stranded 6–70 mm². The coil terminal accepts 2x (0.5–2.5 mm²) solid or stranded via spring-type terminals."},{"question":"Where can I buy the 3RT2047-3NF30?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT2047-3NF30","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT2047-3NF30 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}