{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT2317-2AP60","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT2317-2AP60","canonicalUrl":"https://aoctrl.com/siemens/3RT2317-2AP60","factsUrl":"https://aoctrl.com/api/mcp/products/3RT2317-2AP60","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS contactor, size S00, 3RT2317-2AP60, 5.5 kW AC-3 at 400 V, spring-loaded terminals, screw and snap-on 35 mm DIN rail.","salesMarkdown":"The Siemens SIRIUS 3RT2317-2AP60 is a size S00 contactor rated for 5.5 kW at 400 V in AC-3 duty — the standard motor-switching category for squirrel-cage induction motors. That 5.5 kW rating at 400 V tells you the motor load it can handle under normal starting and running conditions. The 12 A rated operational current at 400 V is the thermal limit for the main poles in that duty. Both the main current circuit and the magnet coil use spring-loaded (spring-type) terminals. The main contacts accept solid conductors 2x (0.5 to 2.5 mm²) or stranded 0.5 to 4 mm². Auxiliary contacts use the same spring-cage style, sized for 2x (0.5 to 2.5 mm²) solid. No screw torque to verify — just strip and insert. Relative humidity minimum 10%. RoHS compliance date is October 1, 2009, covering the EU RoHS substance restrictions.","metaTitle":"Siemens 3RT2317-2AP60 SIRIUS Contactor, 5.5 kW AC-3 at 400 V","metaDescription":"Siemens 3RT2317-2AP60 SIRIUS contactor, size S00. 5.5 kW AC-3 at 400 V, spring-loaded terminals. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"73 mm","Solid":"2x (0.5 ... 2.5 mm²)","Width":"45 mm","at AC":"7 ... 13 ms","title":"3RT2317-2AP60","Height":"70 mm","Upwards":"10 mm","Forwards":"10 mm","Stranded":"0.5 ... 4 mm²","at 50 Hz":"0.24","at 60 Hz":"0.24","Downwards":"10 mm","Attachable":"2","Arcing Time":"10 ... 15 ms","At The Side":"6 mm","description":"contactor AC-1, 22 A, 400 V / 40 °C, 4-pole, 220 V AC, 50 Hz / 240 V, 60 Hz, spring-loaded terminal, size: S00","During Storage":"-55 ... +80 °C","Of Magnet Coil":"Spring-type terminals","Type Of Voltage":"AC","lifecycle_stage":"current","Auxiliary Switch":"Yes","During Operation":"-25 ... +60 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","For Main Contacts":"20 ... 12","Mounting Position":"+/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface","Size Of Contactor":"S00","Solid Or Stranded":"2x (0,5 ... 4 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Contactor","Of Contactor Typical":"30 000 000","at 400 V rated value":"12 A","at 50 Hz rated value":"220 V","at 60 Hz rated value":"240 V","Side-By-Side Mounting":"Yes","For Auxiliary Contacts":"20 ... 12","For Main Current Circuit":"spring-loaded terminals","Relative Humidity Minimum":"10 %","Of Main Circuit Rated Value":"6 kV","at AC in hot operating state":"6.4 W","at AC-3 at 400 V rated value":"5.5 kW","at AC-4 at 400 V rated value":"4 kW","Substance Prohibitance (Date)":"10/01/2009","Of Auxiliary Circuit Rated Value":"6 kV","For Auxiliary And Control Circuit":"spring-loaded terminals","Function Module For Communication":"No","Product Function Bus Communication":"No","With Type Of Assignment 2 Required":"gG: 20 A (690 V, 100 kA)","At Contactor For Auxiliary Contacts":"Spring-type terminals","operating frequency at AC-1 maximum":"1 000 1/h","With Type Of Coordination 1 Required":"gG: 35 A (690 V, 100 kA)","at AC in hot operating state per pole":"1.6 W","for AWG cables for auxiliary contacts":"2x (20 ... 12)","number of NO contacts for main contacts":"4","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"4","Product Function Short Circuit Protection":"No","mirror contact according to IEC 60947-4-1":"Yes; with 3RH29","Finely Stranded Without Core End Processing":"2x (0.5 ... 2.5 mm²)","Type Of Voltage Of The Control Supply Voltage":"AC","Limited To 1 S Switching At Zero Current Maximum":"Use minimum cross-section acc. to AC-1 rated value","Limited To 5 S Switching At Zero Current Maximum":"Use minimum cross-section acc. to AC-1 rated value","Limited To 10 S Switching At Zero Current Maximum":"Use minimum cross-section acc. to AC-1 rated value","Limited To 30 S Switching At Zero Current Maximum":"Use minimum cross-section acc. to AC-1 rated value","Limited To 60 S Switching At Zero Current Maximum":"Use minimum cross-section acc. to AC-1 rated value","Of Main Circuit With Degree Of Pollution 3 Rated Value":"690 V","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"gG: 10 A (690 V, 1 kA)","minimum cross-section in main circuit at maximum AC-1 rated value":"4 mm²","Of The Auxiliary And Control Circuit With Degree Of Pollution 3 Rated Value":"690 V"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/2c4a178e24c7054fb3a53ce3964b9bf7.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=122035&mlfb=3RT2317-2AP60"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT2317-2AP60","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT2317-2AP60 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}