{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT2326-1AV00","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT2326-1AV00","canonicalUrl":"https://aoctrl.com/siemens/3RT2326-1AV00","factsUrl":"https://aoctrl.com/api/mcp/products/3RT2326-1AV00","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS contactor, Size S0, order code 3RT2326-1AV00, 60 mm wide, 97 mm deep, screw and snap-on mounting for 35 mm DIN rail.","salesMarkdown":"It mounts via screw or snap-on onto 35 mm DIN rail per DIN EN 60715, and the mounting position allows ±180° rotation on a vertical surface plus ±22.5° tilt forward or backward, giving panel builders flexibility in tight enclosures. Size S0 is the mechanical frame that governs terminal capacity and thermal dissipation — it accepts stranded conductors up to 10 mm² and solid conductors from 0.5 to 2.5 mm² on the main circuit, with auxiliary contacts wired through 0.5 to 1.5 mm² solid or stranded. The auxiliary switch is rated for AC coil voltage and carries a range of contact ratings depending on the switched voltage: 10 A at 24 V and 230 V, 6 A at 60 V, 3 A at 400 V, down to 0.1 A at 600 V. These are the make/break capacities for the auxiliary circuit — not the main motor current — and they determine whether this contactor can drive the PLC input or relay load you need to switch. The coil connection uses screw-type terminals. Arcing time is 10 to 10 ms at AC, with a switching frequency of 0.25 at 50 Hz. These numbers matter when laying out the gland plate and ensuring adequate fill factor — the 60 mm width and 97 mm depth are the dimensions that determine rail spacing in the enclosure.","metaTitle":"Siemens 3RT2326-1AV00 SIRIUS Contactor, Size S0, 60 mm wide","metaDescription":"Siemens 3RT2326-1AV00 SIRIUS contactor, Size S0, 60 mm wide, 97 mm deep. Screw and snap-on DIN rail mount. Rated for motor loads in control panels. Available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"97 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Width":"60 mm","at AC":"4 ... 16 ms","Height":"85 mm","Upwards":"10 mm","Forwards":"10 mm","Stranded":"1 ... 10 mm²","at 50 Hz":"0.25","Downwards":"10 mm","Attachable":"2","Arcing Time":"10 ... 10 ms","At The Side":"6 mm","During Storage":"-55 ... +80 °C","Of Magnet Coil":"Screw-type terminals","Type Of Voltage":"AC","lifecycle_stage":"current","Auxiliary Switch":"Yes","During Operation":"-25 ... +60 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","For Main Contacts":"16 ... 8","Mounting Position":"+/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface","Size Of Contactor":"S0","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Contactor","at 24 V rated value":"10 A","at 48 V rated value":"2 A","at 60 V rated value":"6 A","Of Contactor Typical":"10 000 000","at 110 V rated value":"1 A","at 125 V rated value":"0.9 A","at 220 V rated value":"0.3 A","at 230 V rated value":"10 A","at 400 V rated value":"3 A","at 50 Hz rated value":"400 V","at 500 V rated value":"2 A","at 600 V rated value":"0.1 A","at 690 V rated value":"1 A","Instantaneous Contact":"1","Side-By-Side Mounting":"Yes","For Auxiliary Contacts":"20 ... 14","For Main Current Circuit":"screw-type terminals","Relative Humidity Minimum":"10 %","Of Main Circuit Rated Value":"6 kV","at AC in hot operating state":"9.6 W","at AC-3 at 400 V rated value":"7.5 kW","at AC-4 at 400 V rated value":"7.5 kW","Substance Prohibitance (Date)":"10/01/2009","Of Auxiliary Circuit Rated Value":"6 kV","For Auxiliary And Control Circuit":"screw-type terminals","Function Module For Communication":"No","Product Function Bus Communication":"No","With Type Of Assignment 2 Required":"gG: 20 A (690 V, 100 kA)","At Contactor For Auxiliary Contacts":"Screw-type terminals","operating frequency at AC-1 maximum":"1 000 1/h","With Type Of Coordination 1 Required":"gG: 63 A (690 V, 100 kA)","operational current at AC-12 maximum":"10 A","at AC in hot operating state per pole":"2.4 W","for AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14)","number of NO contacts for main contacts":"4","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"4","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","Product Function Short Circuit Protection":"No","mirror contact according to IEC 60947-4-1":"Yes","number of NC contacts for auxiliary contacts":"1","number of NO contacts for auxiliary contacts":"1","Type Of Voltage Of The Control Supply Voltage":"AC","Limited To 1 S Switching At Zero Current Maximum":"Use minimum cross-section acc. to AC-1 rated value","Limited To 5 S Switching At Zero Current Maximum":"Use minimum cross-section acc. to AC-1 rated value","Limited To 10 S Switching At Zero Current Maximum":"Use minimum cross-section acc. to AC-1 rated value","Limited To 30 S Switching At Zero Current Maximum":"Use minimum cross-section acc. to AC-1 rated value","Limited To 60 S Switching At Zero Current Maximum":"Use minimum cross-section acc. to AC-1 rated value","contact rating of auxiliary contacts according to UL":"A600 / Q600","Of Main Circuit With Degree Of Pollution 3 Rated Value":"690 V","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"gG: 10 A (690 V, 1 kA)","minimum cross-section in main circuit at maximum AC-1 rated value":"10 mm²","Of The Auxiliary And Control Circuit With Degree Of Pollution 3 Rated Value":"690 V","Design Of The Miniature Circuit Breaker For Short-Circuit Protection Of The Auxiliary Switch Required":"gG: 10 A (230 V, 400 A)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b7f38e9f9d86e59b04eac68bfea90c40.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1283733&mlfb=3RT2326-1AV00","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT2326-1AV00/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3RT2326-1AV00?","answer":"Submit an RFQ through this listing. Pricing and stock are confirmed at quote time; the part is sourced and quoted to order against an RFQ through independent distribution."},{"question":"What is 3RT2326-1AV00's listed depth?","answer":"The depth is 97 mm, with a width of 60 mm and height of 85 mm."},{"question":"Will 3RT2326-1AV00 drop into a panel specified around 3RT2326-1BK80 without rewiring?","answer":"Both are Size S0 SIRIUS contactors sharing the same 60 mm width and DIN rail mounting footprint, so the mechanical fit is identical. Terminal capacity and auxiliary contact configuration should be verified against your specific wiring — the 1AV00 carries screw-type coil terminals and a single instantaneous auxiliary contact."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT2326-1AV00","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT2326-1AV00 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}