{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT2327-1AK60","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT2327-1AK60","canonicalUrl":"https://aoctrl.com/siemens/3RT2327-1AK60","factsUrl":"https://aoctrl.com/api/mcp/products/3RT2327-1AK60","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS contactor, size S0, 3RT2327-1AK60, 60 mm wide, 97 mm deep, auxiliary switch, screw-type coil terminals.","salesMarkdown":"The Siemens 3RT2327-1AK60 is a SIRIUS contactor in the S0 frame size, measuring 85 mm high, 60 mm wide, and 97 mm deep. This footprint slots into standard panel layouts alongside other S0 components without surprises — the 97 mm depth clears shallow enclosures and leaves room for front-access wiring. Main contacts accept stranded wire from 1 to 10 mm²; auxiliary terminals accept solid or stranded 2x (0.5–1.5 mm²) and 2x (0.75–2.5 mm²). The coil connection uses screw-type terminals — no special tooling needed. Mounting is via screw or snap-on onto 35 mm DIN rail per EN 60715; the contactor can be rotated ±180° on a vertical surface and tilted ±22.5° forward or backward, handy when a cabinet forces a non-level rail. ## Environmental tolerance That spans a mill's hot machine room and cold storage warehouse without derating concerns. The contactor also survives the typical vibration and humidity of a pulp and paper line — no special enclosure required beyond the usual IP-grade cabinet.","metaTitle":"Siemens 3RT2327-1AK60 SIRIUS Contactor, S0 Size, 97 mm Depth","metaDescription":"Current-production Siemens SIRIUS contactor, size S0, 60 mm wide, 97 mm deep. Auxiliary switch rated 10 A at 24 V AC and 230 V AC. Mounts on 35 mm DIN rail or screw. Sourced to ord","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"97 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Width":"60 mm","at AC":"4 ... 16 ms","title":"3RT2327-1AK60","Height":"85 mm","Upwards":"10 mm","Forwards":"10 mm","Stranded":"1 ... 10 mm²","at 50 Hz":"0.25","at 60 Hz":"0.28","Downwards":"10 mm","Attachable":"2","Arcing Time":"10 ... 10 ms","At The Side":"6 mm","description":"contactor AC-1, 50 A, 400 V / 40 °C, 4-pole, 110 V AC, 50 Hz / 120 V, 60 Hz, auxiliary contacts: 1 NO + 1 NC, screw terminal, size: S0","During Storage":"-55 ... +80 °C","Of Magnet Coil":"Screw-type terminals","Type Of Voltage":"AC","lifecycle_stage":"current","Auxiliary Switch":"Yes","During Operation":"-25 ... +60 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","For Main Contacts":"16 ... 8","Mounting Position":"+/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface","Size Of Contactor":"S0","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Contactor","at 24 V rated value":"10 A","at 48 V rated value":"2 A","at 60 V rated value":"6 A","Of Contactor Typical":"10 000 000","at 110 V rated value":"1 A","at 125 V rated value":"0.9 A","at 220 V rated value":"0.3 A","at 230 V rated value":"10 A","at 400 V rated value":"3 A","at 50 Hz rated value":"110 V","at 500 V rated value":"2 A","at 60 Hz rated value":"120 V","at 600 V rated value":"0.1 A","at 690 V rated value":"1 A","Instantaneous Contact":"1","Side-By-Side Mounting":"Yes","For Auxiliary Contacts":"20 ... 14","For Main Current Circuit":"screw-type terminals","Relative Humidity Minimum":"10 %","Of Main Circuit Rated Value":"6 kV","at AC in hot operating state":"12 W","at AC-3 at 400 V rated value":"7.5 kW","at AC-4 at 400 V rated value":"7.5 kW","Substance Prohibitance (Date)":"10/01/2009","Of Auxiliary Circuit Rated Value":"6 kV","For Auxiliary And Control Circuit":"screw-type terminals","Function Module For Communication":"No","Product Function Bus Communication":"No","With Type Of Assignment 2 Required":"gG: 20 A (690 V, 100 kA)","At Contactor For Auxiliary Contacts":"Screw-type terminals","operating frequency at AC-1 maximum":"1 000 1/h","With Type Of Coordination 1 Required":"gG: 63 A (690 V, 100 kA)","operational current at AC-12 maximum":"10 A","at AC in hot operating state per pole":"3 W","for AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14)","number of NO contacts for main contacts":"4","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"4","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","Product Function Short Circuit Protection":"No","mirror contact according to IEC 60947-4-1":"Yes","number of NC contacts for auxiliary contacts":"1","number of NO contacts for auxiliary contacts":"1","Type Of Voltage Of The Control Supply Voltage":"AC","Limited To 1 S Switching At Zero Current Maximum":"Use minimum cross-section acc. to AC-1 rated value","Limited To 5 S Switching At Zero Current Maximum":"Use minimum cross-section acc. to AC-1 rated value","Limited To 10 S Switching At Zero Current Maximum":"Use minimum cross-section acc. to AC-1 rated value","Limited To 30 S Switching At Zero Current Maximum":"Use minimum cross-section acc. to AC-1 rated value","Limited To 60 S Switching At Zero Current Maximum":"Use minimum cross-section acc. to AC-1 rated value","contact rating of auxiliary contacts according to UL":"A600 / Q600","Of Main Circuit With Degree Of Pollution 3 Rated Value":"690 V","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"gG: 10 A (690 V, 1 kA)","minimum cross-section in main circuit at maximum AC-1 rated value":"10 mm²","Of The Auxiliary And Control Circuit With Degree Of Pollution 3 Rated Value":"690 V","Design Of The Miniature Circuit Breaker For Short-Circuit Protection Of The Auxiliary Switch Required":"gG: 10 A (230 V, 400 A)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$242.95","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b7f38e9f9d86e59b04eac68bfea90c40.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=122567&mlfb=3RT2327-1AK60"},"ai":{"faq":[{"question":"What is the physical depth of this contactor?","answer":"The depth is 97 mm, as listed for the S0 frame."},{"question":"What wire sizes do the auxiliary terminals accept?","answer":"Auxiliary terminals accept solid wire 2x (0.5–1.5 mm²) and 2x (0.75–2.5 mm²)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT2327-1AK60","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT2327-1AK60 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}