{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT2327-2AK60","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT2327-2AK60","canonicalUrl":"https://aoctrl.com/siemens/3RT2327-2AK60","factsUrl":"https://aoctrl.com/api/mcp/products/3RT2327-2AK60","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RT2327-2AK60 contactor, size S0, AC coil, screw and snap-on mounting onto 35 mm DIN rail, 97 mm depth, 60 mm width, spring-type coil terminals.","salesMarkdown":"The auxiliary contact ratings cover the common control voltages you'll see on a lube skid or conveyor line: 10 A at 24 V, 10 A at 230 V, 3 A at 400 V, and 0.1 A at 600 V. The mechanical life is listed at 10 million operations typical, so this contactor will outlast the motor it's switching on most cyclic loads. If your panel sits next to a hot bearing housing or a steam line, the -25 to +60 window covers most plant-floor conditions. The arcing time is 10 ms, and the AC switching time is 4 to 16 ms — fast enough for standard motor starting, but if you need faster break for a solid-state load, you'll want a DC coil variant. That's tighter than some older contactor families, so you can pack these closer on the DIN rail. Just don't skimp on the side gap if you're running multiple contactors in a row — the 6 mm is the minimum for heat dissipation.","metaTitle":"Siemens 3RT2327-2AK60 SIRIUS Contactor, Size S0, 60 mm","metaDescription":"Siemens 3RT2327-2AK60 SIRIUS contactor, size S0, AC coil, screw and snap-on DIN rail mount, 97 mm depth, 60 mm width. Active lifecycle, quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"97 mm","Solid":"2x (0.5 ... 2.5 mm²)","Width":"60 mm","at AC":"4 ... 16 ms","Height":"102 mm","Upwards":"10 mm","Forwards":"10 mm","Stranded":"1 ... 10 mm²","at 50 Hz":"0.25","at 60 Hz":"0.28","Downwards":"10 mm","Attachable":"2","Arcing Time":"10 ... 10 ms","At The Side":"6 mm","During Storage":"-55 ... +80 °C","Of Magnet Coil":"Spring-type terminals","Type Of Voltage":"AC","lifecycle_stage":"current","Auxiliary Switch":"Yes","During Operation":"-25 ... +60 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","For Main Contacts":"18 ... 8","Mounting Position":"+/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface","Size Of Contactor":"S0","Solid Or Stranded":"2x (0.5 ... 2.5 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Contactor","at 24 V rated value":"10 A","at 48 V rated value":"2 A","at 60 V rated value":"6 A","Of Contactor Typical":"10 000 000","at 110 V rated value":"1 A","at 125 V rated value":"0.9 A","at 220 V rated value":"0.3 A","at 230 V rated value":"10 A","at 400 V rated value":"3 A","at 50 Hz rated value":"110 V","at 500 V rated value":"2 A","at 60 Hz rated value":"120 V","at 600 V rated value":"0.1 A","at 690 V rated value":"1 A","Instantaneous Contact":"1","Side-By-Side Mounting":"Yes","For Auxiliary Contacts":"20 ... 14","For Main Current Circuit":"spring-loaded terminals","Relative Humidity Minimum":"10 %","Of Main Circuit Rated Value":"6 kV","at AC in hot operating state":"12 W","at AC-3 at 400 V rated value":"7.5 kW","at AC-4 at 400 V rated value":"7.5 kW","Substance Prohibitance (Date)":"10/01/2009","Of Auxiliary Circuit Rated Value":"6 kV","For Auxiliary And Control Circuit":"spring-loaded terminals","Function Module For Communication":"No","Product Function Bus Communication":"No","With Type Of Assignment 2 Required":"gG: 20 A (690 V, 100 kA)","At Contactor For Auxiliary Contacts":"Spring-type terminals","operating frequency at AC-1 maximum":"1 000 1/h","With Type Of Coordination 1 Required":"gG: 63 A (690 V, 100 kA)","operational current at AC-12 maximum":"10 A","at AC in hot operating state per pole":"3 W","for AWG cables for auxiliary contacts":"2x (20 ... 14)","number of NO contacts for main contacts":"4","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²)","Number Of Poles For Main Current Circuit":"4","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","Product Function Short Circuit Protection":"No","mirror contact according to IEC 60947-4-1":"Yes","Finely Stranded Without Core End Processing":"2x (0.5 ... 2.5 mm²)","number of NC contacts for auxiliary contacts":"1","number of NO contacts for auxiliary contacts":"1","Type Of Voltage Of The Control Supply Voltage":"AC","Limited To 1 S Switching At Zero Current Maximum":"Use minimum cross-section acc. to AC-1 rated value","Limited To 5 S Switching At Zero Current Maximum":"Use minimum cross-section acc. to AC-1 rated value","Limited To 10 S Switching At Zero Current Maximum":"Use minimum cross-section acc. to AC-1 rated value","Limited To 30 S Switching At Zero Current Maximum":"Use minimum cross-section acc. to AC-1 rated value","Limited To 60 S Switching At Zero Current Maximum":"Use minimum cross-section acc. to AC-1 rated value","contact rating of auxiliary contacts according to UL":"A600 / Q600","Of Main Circuit With Degree Of Pollution 3 Rated Value":"690 V","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"gG: 10 A (690 V, 1 kA)","minimum cross-section in main circuit at maximum AC-1 rated value":"10 mm²","Of The Auxiliary And Control Circuit With Degree Of Pollution 3 Rated Value":"690 V","Design Of The Miniature Circuit Breaker For Short-Circuit Protection Of The Auxiliary Switch Required":"gG: 10 A (230 V, 400 A)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b7f38e9f9d86e59b04eac68bfea90c40.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=393318&mlfb=3RT2327-2AK60","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT2327-2AK60/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3RT2327-2AK60 and get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."},{"question":"Will 3RT2327-2AK60 drop into a panel specified for 3RT2015-2AP02 without rewiring?","answer":"Both are size S0 contactors with the same DIN-rail footprint, so mechanical fit is the same. The 3RT2327-2AK60 has an AC coil rated 110 V at 50 Hz / 120 V at 60 Hz, while the 3RT2015-2AP02 uses a different coil voltage — verify your control voltage matches before swapping. Wiring terminals are spring-type on both, so no lug change needed."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT2327-2AK60","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT2327-2AK60 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}