{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT2327-2AP60","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT2327-2AP60","canonicalUrl":"https://aoctrl.com/siemens/3RT2327-2AP60","factsUrl":"https://aoctrl.com/api/mcp/products/3RT2327-2AP60","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RT2327-2AP60 contactor, size S0, 3-pole, spring-type coil terminals, screw and snap-on mounting for 35 mm DIN rail, 97 mm depth, 60 mm width, 102 mm height.","salesMarkdown":"The 3RT2327-2AP60: This derating reflects the arc extinction capability of the S0 frame — the same contact set that comfortably breaks 10 A at 230 V cannot reliably interrupt the same current at 600 V without weld risk. ## Coil power and thermal operating envelope The magnet coil draws 0.25 A at 50 Hz (220 V coil) and 0.28 A at 60 Hz (240 V coil) — the coil inrush at pickup is higher, but the holding current settles to these figures once the armature seals. The 10 million mechanical operations typical life means this contactor outlasts most panel designs provided the switching duty stays within the electrical endurance curve for the actual load current.","metaTitle":"Siemens 3RT2327-2AP60 SIRIUS Contactor, S0 Size, 97 mm Depth","metaDescription":"Siemens 3RT2327-2AP60 SIRIUS contactor, size S0, 97 mm depth, 60 mm width. Screw and snap-on mounting for 35 mm DIN rail. Active production, quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"97 mm","Solid":"2x (0.5 ... 2.5 mm²)","Width":"60 mm","at AC":"4 ... 16 ms","title":"3RT2327-2AP60","Height":"102 mm","Upwards":"10 mm","Forwards":"10 mm","Stranded":"1 ... 10 mm²","at 50 Hz":"0.25","at 60 Hz":"0.28","Downwards":"10 mm","Attachable":"2","Arcing Time":"10 ... 10 ms","At The Side":"6 mm","description":"contactor AC-1, 50 A, 400 V / 40 °C, 4-pole, 220 V AC, 50 Hz / 240 V, 60 Hz, auxiliary contacts: 1 NO + 1 NC, spring-loaded terminal, size: S0","During Storage":"-55 ... +80 °C","Of Magnet Coil":"Spring-type terminals","Type Of Voltage":"AC","lifecycle_stage":"current","Auxiliary Switch":"Yes","During Operation":"-25 ... +60 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","For Main Contacts":"18 ... 8","Mounting Position":"+/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface","Size Of Contactor":"S0","Solid Or Stranded":"2x (0.5 ... 2.5 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Contactor","at 24 V rated value":"10 A","at 48 V rated value":"2 A","at 60 V rated value":"6 A","Of Contactor Typical":"10 000 000","at 110 V rated value":"1 A","at 125 V rated value":"0.9 A","at 220 V rated value":"0.3 A","at 230 V rated value":"10 A","at 400 V rated value":"3 A","at 50 Hz rated value":"220 V","at 500 V rated value":"2 A","at 60 Hz rated value":"240 V","at 600 V rated value":"0.1 A","at 690 V rated value":"1 A","Instantaneous Contact":"1","Side-By-Side Mounting":"Yes","For Auxiliary Contacts":"20 ... 14","For Main Current Circuit":"spring-loaded terminals","Relative Humidity Minimum":"10 %","Of Main Circuit Rated Value":"6 kV","at AC in hot operating state":"12 W","at AC-3 at 400 V rated value":"7.5 kW","at AC-4 at 400 V rated value":"7.5 kW","Substance Prohibitance (Date)":"10/01/2009","Of Auxiliary Circuit Rated Value":"6 kV","For Auxiliary And Control Circuit":"spring-loaded terminals","Function Module For Communication":"No","Product Function Bus Communication":"No","With Type Of Assignment 2 Required":"gG: 20 A (690 V, 100 kA)","At Contactor For Auxiliary Contacts":"Spring-type terminals","operating frequency at AC-1 maximum":"1 000 1/h","With Type Of Coordination 1 Required":"gG: 63 A (690 V, 100 kA)","operational current at AC-12 maximum":"10 A","at AC in hot operating state per pole":"3 W","for AWG cables for auxiliary contacts":"2x (20 ... 14)","number of NO contacts for main contacts":"4","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²)","Number Of Poles For Main Current Circuit":"4","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","Product Function Short Circuit Protection":"No","mirror contact according to IEC 60947-4-1":"Yes","Finely Stranded Without Core End Processing":"2x (0.5 ... 2.5 mm²)","number of NC contacts for auxiliary contacts":"1","number of NO contacts for auxiliary contacts":"1","Type Of Voltage Of The Control Supply Voltage":"AC","Limited To 1 S Switching At Zero Current Maximum":"Use minimum cross-section acc. to AC-1 rated value","Limited To 5 S Switching At Zero Current Maximum":"Use minimum cross-section acc. to AC-1 rated value","Limited To 10 S Switching At Zero Current Maximum":"Use minimum cross-section acc. to AC-1 rated value","Limited To 30 S Switching At Zero Current Maximum":"Use minimum cross-section acc. to AC-1 rated value","Limited To 60 S Switching At Zero Current Maximum":"Use minimum cross-section acc. to AC-1 rated value","contact rating of auxiliary contacts according to UL":"A600 / Q600","Of Main Circuit With Degree Of Pollution 3 Rated Value":"690 V","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"gG: 10 A (690 V, 1 kA)","minimum cross-section in main circuit at maximum AC-1 rated value":"10 mm²","Of The Auxiliary And Control Circuit With Degree Of Pollution 3 Rated Value":"690 V","Design Of The Miniature Circuit Breaker For Short-Circuit Protection Of The Auxiliary Switch Required":"gG: 10 A (230 V, 400 A)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b7f38e9f9d86e59b04eac68bfea90c40.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=384403&mlfb=3RT2327-2AP60"},"ai":{"faq":[{"question":"What is the 3RT2327-2AP60 depth and how does it mount?","answer":"The depth is 97 mm behind the panel face, width 60 mm, height 102 mm."},{"question":"What compliance documentation does Siemens provide for the 3RT2327-2AP60?","answer":"As a standard SIRIUS industrial control product, the 3RT2327-2AP60 carries CE marking per the Low Voltage Directive and is designed to meet RoHS and REACH requirements. Specific declarations are available from the manufacturer upon request."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT2327-2AP60","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT2327-2AP60 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}