{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT2336-1AK60","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT2336-1AK60","canonicalUrl":"https://aoctrl.com/siemens/3RT2336-1AK60","factsUrl":"https://aoctrl.com/api/mcp/products/3RT2336-1AK60","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS, Contactor, 3RT2336-1AK60, S2 size, screw-type terminals, 75 mm width, 130 mm depth, 114 mm height, screw and snap-on mounting on 35 mm DIN rail.","salesMarkdown":"It mounts via screw and snap-on onto 35 mm DIN rail per DIN EN 60715, so it drops into a standard panel layout without adapter plates — the 75 mm width and 130 mm depth tell you the footprint it takes up on the rail and how far it reaches into the enclosure. The magnet coil uses screw-type terminals, and the main contact wiring accepts 2x (0.5... 1.5 mm²) solid or 2x (0.75... 2.5 mm²) stranded — that covers the typical control-circuit and motor-lead sizes you'd run for an S2-frame contactor. No ferrule crimping required for the solid wire, which saves a step on the panel build. ## Mounting flexibility The mounting position allows +/-180° rotation on a vertical surface and can be tilted forward/backward by +/-22.5° — useful if the panel layout forces an odd angle or you're retrofitting into an existing enclosure where the DIN rail isn't level. Clearances: 10 mm upwards, 10 mm forwards, 10 mm downwards, 6 mm to the side — tight enough for dense packing but leave the side gap for heat dissipation.","metaTitle":"Siemens 3RT2336-1AK60 SIRIUS Contactor, S2 Size, 75 mm Width","metaDescription":"Siemens 3RT2336-1AK60 SIRIUS contactor, S2 size, screw terminals, 75 mm wide. Active lifecycle. Sourced to order. Request RFQ for current pricing and availability.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"130 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Width":"75 mm","at AC":"10 ... 18 ms","title":"3RT2336-1AK60","Height":"114 mm","Upwards":"10 mm","Forwards":"10 mm","at 50 Hz":"0.36","at 60 Hz":"0.39","Downwards":"10 mm","Attachable":"2","Arcing Time":"10 ... 20 ms","At The Side":"6 mm","description":"contactor AC-1, 60 A, 400 V / 40 °C, 4-pole, 110 V AC, 50 Hz / 120 V, 60 Hz, auxiliary contacts: 1 NO + 1 NC, screw terminal, size: S2","During Storage":"-55 ... +80 °C","Of Magnet Coil":"Screw-type terminals","Type Of Voltage":"AC","lifecycle_stage":"current","Auxiliary Switch":"Yes","During Operation":"-40 ... +70 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","For Main Contacts":"18 ... 1","Mounting Position":"+/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface","Size Of Contactor":"S2","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Contactor","at 24 V rated value":"10 A","at 48 V rated value":"2 A","at 60 V rated value":"6 A","Of Contactor Typical":"10 000 000","at 110 V rated value":"1 A","at 125 V rated value":"0.9 A","at 220 V rated value":"0.3 A","at 230 V rated value":"10 A","at 400 V rated value":"3 A","at 50 Hz rated value":"110 V","at 500 V rated value":"2 A","at 60 Hz rated value":"120 V","at 600 V rated value":"0.1 A","at 690 V rated value":"1 A","Instantaneous Contact":"1","Side-By-Side Mounting":"Yes","For Auxiliary Contacts":"20 ... 14","For Main Current Circuit":"screw-type terminals","Relative Humidity Minimum":"10 %","Of Main Circuit Rated Value":"6 kV","at AC in hot operating state":"12.8 W","Substance Prohibitance (Date)":"10/01/2014","Of Auxiliary Circuit Rated Value":"6 kV","For Auxiliary And Control Circuit":"screw-type terminals","Function Module For Communication":"No","Product Function Bus Communication":"No","With Type Of Assignment 2 Required":"gG: 63 A (690 V,100 kA)","At Contactor For Auxiliary Contacts":"Screw-type terminals","operating frequency at AC-1 maximum":"700 1/h","With Type Of Coordination 1 Required":"gG: 160 A (690 V, 100 kA)","operational current at AC-12 maximum":"10 A","at AC in hot operating state per pole":"3.2 W","for AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14)","number of NO contacts for main contacts":"4","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"4","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","Product Function Short Circuit Protection":"No","mirror contact according to IEC 60947-4-1":"Yes","Finely Stranded Without Core End Processing":"0.5 ... 2.5 mm²","number of NC contacts for auxiliary contacts":"1","number of NO contacts for auxiliary contacts":"1","Type Of Voltage Of The Control Supply Voltage":"AC","Limited To 1 S Switching At Zero Current Maximum":"Use minimum cross-section acc. to AC-1 rated value","Limited To 5 S Switching At Zero Current Maximum":"Use minimum cross-section acc. to AC-1 rated value","Limited To 10 S Switching At Zero Current Maximum":"Use minimum cross-section acc. to AC-1 rated value","Limited To 30 S Switching At Zero Current Maximum":"Use minimum cross-section acc. to AC-1 rated value","Limited To 60 S Switching At Zero Current Maximum":"Use minimum cross-section acc. to AC-1 rated value","contact rating of auxiliary contacts according to UL":"A600 / P600","Of Main Circuit With Degree Of Pollution 3 Rated Value":"690 V","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"gG: 10 A (690 V, 1 kA)","minimum cross-section in main circuit at maximum AC-1 rated value":"16 mm²","Of The Auxiliary And Control Circuit With Degree Of Pollution 3 Rated Value":"690 V","Design Of The Miniature Circuit Breaker For Short-Circuit Protection Of The Auxiliary Switch Required":"gG: 10 A (230 V, 400 A)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/ca192699cf31b1a6b3427c82809b93b4.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=386297&mlfb=3RT2336-1AK60"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3RT2336-1AK60?","answer":"Submit an RFQ — we source this part to order and confirm current pricing and availability at quote time."},{"question":"What is the depth of 3RT2336-1AK60?","answer":"The depth is 130 mm."},{"question":"What wire sizes does 3RT2336-1AK60 accept?","answer":"The terminals accept 2x (0.5... 1.5 mm²) solid or 2x (0.75... 2.5 mm²) stranded wire."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT2336-1AK60","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT2336-1AK60 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}