{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT2336-1AV00","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT2336-1AV00","canonicalUrl":"https://aoctrl.com/siemens/3RT2336-1AV00","factsUrl":"https://aoctrl.com/api/mcp/products/3RT2336-1AV00","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS, 3RT2336-1AV00, Size S2 contactor, AC coil, screw-type terminals, 130 mm depth, 75 mm width.","salesMarkdown":"The Siemens 3RT2336-1AV00 is a SIRIUS-branded Size S2 contactor with an AC coil. It's a current-production part, so this is the standard catalog item — not an NRND or obsolete line. It mounts via screw or snap-on onto 35 mm DIN rail per DIN EN 60715, and the mounting position allows +/-180° rotation on a vertical surface plus +/-22.5° tilt forward/backward. That flexibility helps when you're squeezing it into a crowded panel. The main contact ratings are given across a range of voltages: at 24 V rated value it carries 10 A, at 230 V rated value also 10 A, and at 400 V rated value it handles 3 A. Mechanical life is listed at 10 million operations typical — that's a high-cycle part suited for frequent switching applications like conveyor or pump cycling, not a one-time disconnect. The coil is AC type with screw-type terminals, and the auxiliary switch is included (1 instantaneous contact). For the auxiliary contacts, the rated values span from 10 A at 24 V down to 0.1 A at 600 V — the 24 V 10 A rating is your key figure for interposing relays or PLC outputs. Wiring terminals accept solid or stranded conductors: 2x (0.5... 1.5 mm²) and 2x (0.75... 2.5 mm²). That's standard for control wiring — no need for special ferrules if you're using 1.5 mm² stranded. Dimensions are 114 mm height, 75 mm width, 130 mm depth — the depth is the dimension that often catches people when retrofitting into existing enclosures. ## Environmental range and storage That covers most industrial environments short of direct oven or freezer placement.","metaTitle":"Siemens 3RT2336-1AV00 SIRIUS Contactor, Size S2, 10A at 24V","metaDescription":"Siemens 3RT2336-1AV00 SIRIUS contactor, size S2. Active production. 10A at 24V AC coil. Screw/snap-on 35mm DIN rail. 130mm depth. Sourced to order via RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"130 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Width":"75 mm","at AC":"10 ... 18 ms","Height":"114 mm","Upwards":"10 mm","Forwards":"10 mm","at 50 Hz":"0.37","Downwards":"10 mm","Attachable":"2","Arcing Time":"10 ... 20 ms","At The Side":"6 mm","During Storage":"-55 ... +80 °C","Of Magnet Coil":"Screw-type terminals","Type Of Voltage":"AC","lifecycle_stage":"current","Auxiliary Switch":"Yes","During Operation":"-40 ... +70 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","For Main Contacts":"18 ... 1","Mounting Position":"+/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface","Size Of Contactor":"S2","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Contactor","at 24 V rated value":"10 A","at 48 V rated value":"2 A","at 60 V rated value":"6 A","Of Contactor Typical":"10 000 000","at 110 V rated value":"1 A","at 125 V rated value":"0.9 A","at 220 V rated value":"0.3 A","at 230 V rated value":"10 A","at 400 V rated value":"3 A","at 50 Hz rated value":"400 V","at 500 V rated value":"2 A","at 600 V rated value":"0.1 A","at 690 V rated value":"1 A","Instantaneous Contact":"1","Side-By-Side Mounting":"Yes","For Auxiliary Contacts":"20 ... 14","For Main Current Circuit":"screw-type terminals","Relative Humidity Minimum":"10 %","Of Main Circuit Rated Value":"6 kV","at AC in hot operating state":"12.8 W","Substance Prohibitance (Date)":"10/01/2014","Of Auxiliary Circuit Rated Value":"6 kV","For Auxiliary And Control Circuit":"screw-type terminals","Function Module For Communication":"No","Product Function Bus Communication":"No","With Type Of Assignment 2 Required":"gG: 63 A (690 V,100 kA)","At Contactor For Auxiliary Contacts":"Screw-type terminals","operating frequency at AC-1 maximum":"700 1/h","With Type Of Coordination 1 Required":"gG: 160 A (690 V, 100 kA)","operational current at AC-12 maximum":"10 A","at AC in hot operating state per pole":"3.2 W","for AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14)","number of NO contacts for main contacts":"4","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"4","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","Product Function Short Circuit Protection":"No","mirror contact according to IEC 60947-4-1":"Yes","Finely Stranded Without Core End Processing":"0.5 ... 2.5 mm²","number of NC contacts for auxiliary contacts":"1","number of NO contacts for auxiliary contacts":"1","Type Of Voltage Of The Control Supply Voltage":"AC","Limited To 1 S Switching At Zero Current Maximum":"Use minimum cross-section acc. to AC-1 rated value","Limited To 5 S Switching At Zero Current Maximum":"Use minimum cross-section acc. to AC-1 rated value","Limited To 10 S Switching At Zero Current Maximum":"Use minimum cross-section acc. to AC-1 rated value","Limited To 30 S Switching At Zero Current Maximum":"Use minimum cross-section acc. to AC-1 rated value","Limited To 60 S Switching At Zero Current Maximum":"Use minimum cross-section acc. to AC-1 rated value","contact rating of auxiliary contacts according to UL":"A600 / P600","Of Main Circuit With Degree Of Pollution 3 Rated Value":"690 V","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"gG: 10 A (690 V, 1 kA)","minimum cross-section in main circuit at maximum AC-1 rated value":"16 mm²","Of The Auxiliary And Control Circuit With Degree Of Pollution 3 Rated Value":"690 V","Design Of The Miniature Circuit Breaker For Short-Circuit Protection Of The Auxiliary Switch Required":"gG: 10 A (230 V, 400 A)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/ca192699cf31b1a6b3427c82809b93b4.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=97735&mlfb=3RT2336-1AV00","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT2336-1AV00/alternatives.json"},"ai":{"faq":[{"question":"What are the key mounting dimensions?","answer":"Height 114 mm, width 75 mm, depth 130 mm. It mounts on 35 mm DIN rail per DIN EN 60715, with 10 mm clearance needed above, below, and in front, and 6 mm at the sides."},{"question":"What wire sizes does the 3RT2336-1AV00 accept?","answer":"It accepts 2x (0.5... 1.5 mm²) or 2x (0.75... 2.5 mm²) solid or stranded conductors. That covers standard control wiring up to 2.5 mm²."},{"question":"What is the rated current for the main contacts at 230 V?","answer":"At 230 V rated value it carries 10 A. At 400 V rated value it carries 3 A."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT2336-1AV00","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT2336-1AV00 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}