{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT2337-1AK60","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT2337-1AK60","canonicalUrl":"https://aoctrl.com/siemens/3RT2337-1AK60","factsUrl":"https://aoctrl.com/api/mcp/products/3RT2337-1AK60","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS contactor, S2 size, 3RT2337-1AK60, 110 VAC 50 Hz / 120 VAC 60 Hz coil, screw terminals, 10 A rated current at 24 V and 230 V, 75 mm width, 114 mm height, 130 mm depth.","salesMarkdown":"The 3RT2337-1AK60: Rated operational current hits 10 A at both 24 V and 230 V — that is the AC-1 resistive load curve. For motor duty (AC-3), the 690 V rating of 1 A tells you this contactor is sized for smaller motors; it is not a 7.5 kW class block. The 10 A at 230 V also covers resistive heater banks or lighting contactor applications on single-phase 230 V lines. Arcing time runs 10 to 20 ms, and the main contacts close in 10 to 18 ms — fast enough for most PLC-driven sequences. ## Mounting and wiring — panel integration That covers most DIN-rail layouts without special brackets. The contactor accepts 2x (0.5 to 1.5 mm²) solid or 2x (0.75 to 2.5 mm²) stranded per terminal — standard panel wire sizes. Two auxiliary switch blocks can be attached on top (attachable auxiliary switches: 2).","metaTitle":"Siemens 3RT2337-1AK60 SIRIUS Contactor S2, 110 VAC coil","metaDescription":"Siemens 3RT2337-1AK60 SIRIUS contactor, S2 size, 110 VAC 50 Hz / 120 VAC 60 Hz coil, screw terminals, 10 A rated current at 24 V and 230 V. Active lifecycle, available to order. DI","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"130 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Width":"75 mm","at AC":"10 ... 18 ms","title":"3RT2337-1AK60","Height":"114 mm","Upwards":"10 mm","Forwards":"10 mm","at 50 Hz":"0.36","at 60 Hz":"0.39","Downwards":"10 mm","Attachable":"2","Arcing Time":"10 ... 20 ms","At The Side":"6 mm","description":"contactor AC-1, 110 A, 400 V / 40 °C, 4-pole, 110 V AC, 50 Hz / 120 V, 60 Hz, auxiliary contacts: 1 NO + 1 NC, screw terminal, size: S2","During Storage":"-55 ... +80 °C","Of Magnet Coil":"Screw-type terminals","Type Of Voltage":"AC","lifecycle_stage":"current","Auxiliary Switch":"Yes","During Operation":"-40 ... +70 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","For Main Contacts":"18 ... 1","Mounting Position":"+/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface","Size Of Contactor":"S2","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Contactor","at 24 V rated value":"10 A","at 48 V rated value":"2 A","at 60 V rated value":"6 A","Of Contactor Typical":"10 000 000","at 110 V rated value":"1 A","at 125 V rated value":"0.9 A","at 220 V rated value":"0.3 A","at 230 V rated value":"10 A","at 400 V rated value":"3 A","at 50 Hz rated value":"110 V","at 500 V rated value":"2 A","at 60 Hz rated value":"120 V","at 600 V rated value":"0.1 A","at 690 V rated value":"1 A","Instantaneous Contact":"1","Side-By-Side Mounting":"Yes","For Auxiliary Contacts":"20 ... 14","For Main Current Circuit":"screw-type terminals","Relative Humidity Minimum":"10 %","Of Main Circuit Rated Value":"6 kV","at AC in hot operating state":"38.8 W","Substance Prohibitance (Date)":"10/01/2014","at AWG cables for main contacts":"2x (18 ... 2), 1x (18 ... 1)","Of Auxiliary Circuit Rated Value":"6 kV","For Auxiliary And Control Circuit":"screw-type terminals","Function Module For Communication":"No","Product Function Bus Communication":"No","With Type Of Assignment 2 Required":"gR: 80 A (690 V, 100 kA)","At Contactor For Auxiliary Contacts":"Screw-type terminals","operating frequency at AC-1 maximum":"700 1/h","With Type Of Coordination 1 Required":"gG: 160 A (690 V, 100 kA)","at AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14)","operational current at AC-12 maximum":"10 A","at AC in hot operating state per pole":"9.7 W","number of NO contacts for main contacts":"4","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"4","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","Product Function Short Circuit Protection":"No","mirror contact according to IEC 60947-4-1":"Yes","Finely Stranded Without Core End Processing":"0.5 ... 2.5 mm²","number of NC contacts for auxiliary contacts":"1","number of NO contacts for auxiliary contacts":"1","Type Of Voltage Of The Control Supply Voltage":"AC","Limited To 1 S Switching At Zero Current Maximum":"Use minimum cross-section acc. to AC-1 rated value","Limited To 5 S Switching At Zero Current Maximum":"Use minimum cross-section acc. to AC-1 rated value","Limited To 10 S Switching At Zero Current Maximum":"Use minimum cross-section acc. to AC-1 rated value","Limited To 30 S Switching At Zero Current Maximum":"Use minimum cross-section acc. to AC-1 rated value","Limited To 60 S Switching At Zero Current Maximum":"Use minimum cross-section acc. to AC-1 rated value","contact rating of auxiliary contacts according to UL":"A600 / P600","Of Main Circuit With Degree Of Pollution 3 Rated Value":"690 V","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"gG: 10 A (690 V, 1 kA)","minimum cross-section in main circuit at maximum AC-1 rated value":"35 mm²","Of The Auxiliary And Control Circuit With Degree Of Pollution 3 Rated Value":"690 V","Design Of The Miniature Circuit Breaker For Short-Circuit Protection Of The Auxiliary Switch Required":"gG: 10 A (230 V, 400 A)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/ca192699cf31b1a6b3427c82809b93b4.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=695146&mlfb=3RT2337-1AK60"},"ai":{"faq":[{"question":"Where can I buy 3RT2337-1AK60 and how do I get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent industrial-automation distribution. Submit a request for quote to confirm availability and current pricing."},{"question":"What is 3RT2337-1AK60's listed depth?","answer":"The depth is 130 mm, with a width of 75 mm and height of 114 mm — the S2 frame dimensions."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT2337-1AK60","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT2337-1AK60 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}