{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT2544-1AB00","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT2544-1AB00","canonicalUrl":"https://aoctrl.com/siemens/3RT2544-1AB00","factsUrl":"https://aoctrl.com/api/mcp/products/3RT2544-1AB00","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RT2544-1AB00 contactor, Size S3, 24 VAC 50 Hz coil, screw-type terminals, 70 x 140 x 152 mm, DIN rail mount.","salesMarkdown":"## Panel fit and wiring capacity The 3RT2544-1AB00 is a Size S3 contactor from the SIRIUS family, measuring 70 mm wide by 140 mm high by 152 mm deep — the depth is the dimension that extends behind the DIN rail, so budget that into your enclosure back-panel layout. ## Coil and auxiliary contact ratings The magnet coil is rated 24 V at 50 Hz, drawing 0.38 A holding current — screw-type terminals on the coil, so wire it with standard control wiring. At AC-1 maximum switching frequency it handles 900 operations per hour — that's the resistive-load ceiling; for motor loads (AC-3) the rate will be lower, but the contactor is sized for the duty. ## Operating environment and clearances Arcing time is 10 to 20 ms, and the AC operating time (pick-up + drop-out) is 11 to 21 ms — fast enough for most sequencing applications but verify against your PLC cycle time if you're using the auxiliary contacts for feedback.","metaTitle":"Siemens 3RT2544-1AB00 SIRIUS Contactor, Size S3, 24 VAC Coil","metaDescription":"Siemens 3RT2544-1AB00 SIRIUS contactor, Size S3, 24 VAC 50 Hz coil, screw terminals, 70 mm wide, DIN rail mount. Active production, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"152 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Width":"70 mm","at AC":"11 ... 21 ms","Height":"140 mm","Upwards":"10 mm","Forwards":"0 mm","Stranded":"2x (6 ... 16 mm²), 2x (10 ... 50 mm²), 1x (10 ... 70 mm²)","at 50 Hz":"0.38","Backwards":"0 mm","Downwards":"10 mm","Arcing Time":"10 ... 20 ms","At The Side":"10 mm","During Storage":"-55 ... +80 °C","Of Magnet Coil":"Screw-type terminals","at AC-1 maximum":"900 1/h","lifecycle_stage":"current","Auxiliary Switch":"Yes","During Operation":"-25 ... +60 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","Mounting Position":"+/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface","Size Of Contactor":"S3","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Product Brand Name":"SIRIUS","Product Designation":"contactor","at 24 V rated value":"10 A","at 48 V rated value":"2 A","at 60 V rated value":"2 A","Of Contactor Typical":"10 000 000","at 110 V rated value":"1 A","at 125 V rated value":"0.9 A","at 220 V rated value":"0.3 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 440 V rated value":"1.8 A","at 50 Hz rated value":"24 V","at 500 V rated value":"2 A","at 600 V rated value":"0.1 A","at 690 V rated value":"1 A","Side-By-Side Mounting":"Yes","For Main Current Circuit":"screw-type terminals","Relative Humidity Minimum":"10 %","per NC contact rated value":"65 A","per NO contact rated value":"65 A","Of Main Circuit Rated Value":"8 kV","Substance Prohibitance (Date)":"09/01/2017","Of Auxiliary Circuit Rated Value":"6 kV","For Auxiliary And Control Circuit":"screw-type terminals","Function Module For Communication":"No","With Type Of Assignment 2 Required":"gR: 250 A (690 V, 100 kA)","at 24 V per NC contact rated value":"100 A","at 24 V per NO contact rated value":"100 A","At Contactor For Auxiliary Contacts":"Screw-type terminals","at 110 V per NC contact rated value":"100 A","at 110 V per NO contact rated value":"100 A","at 220 V per NC contact rated value":"7 A","at 220 V per NO contact rated value":"7 A","at 230 V per NC contact rated value":"18.5 kW","at 230 V per NO contact rated value":"18.5 kW","at 400 V per NC contact rated value":"30 kW","at 400 V per NO contact rated value":"30 kW","at 440 V per NC contact rated value":"0.42 A","at 440 V per NO contact rated value":"0.42 A","With Type Of Coordination 1 Required":"gG: 250 A (690 V, 100 kA)","operational current at AC-12 maximum":"10 A","for AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14)","number of NC contacts for main contacts":"2","number of NO contacts for main contacts":"2","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"4","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","at ambient temperature 40 °C rated value":"100 A","at ambient temperature 60 °C rated value":"90 A","mirror contact according to IEC 60947-4-1":"Yes","apparent holding power of magnet coil at AC":"19 VA","apparent pick-up power of magnet coil at AC":"296 VA","Type Of Voltage Of The Control Supply Voltage":"AC","for 3-phase AC motor at 460/480 V rated value":"25 hp","Limited To 1 S Switching At Zero Current Maximum":"880 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 5 S Switching At Zero Current Maximum":"880 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 10 S Switching At Zero Current Maximum":"691 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 30 S Switching At Zero Current Maximum":"437 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 60 S Switching At Zero Current Maximum":"344 A; Use minimum cross-section acc. to AC-1 rated value","contact rating of auxiliary contacts according to UL":"A600 / P600","Inductive Power Factor With Closing Power Of The Coil":"0.61","Of Main Circuit With Degree Of Pollution 3 Rated Value":"1 000 V","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","Of Auxiliary Circuit With Degree Of Pollution 3 Rated Value":"690 V","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gG: 10 A","minimum cross-section in main circuit at maximum AC-1 rated value":"35 mm²","number of NC contacts for auxiliary contacts instantaneous contact":"1","number of NO contacts for auxiliary contacts instantaneous contact":"1","AWG number as coded connectable conductor cross section for main contacts":"10 ... 2","Of The Contactor With Added Electronically Optimized Auxiliary Switch Block Typical":"5 000 000","power loss [W] at AC-3 at 400 V for rated value of the operational current per conductor":"3.5 W"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/fb918960dd2a48789b6a44ffa1363bda.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=630083&mlfb=3RT2544-1AB00","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT2544-1AB00/alternatives.json"},"ai":{"faq":[{"question":"What wire sizes does the 3RT2544-1AB00 accept on the main terminals?","answer":"The main power terminals accept stranded wire: two conductors from 6 to 16 mm², two from 10 to 50 mm², or a single conductor from 10 to 70 mm²."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT2544-1AB00","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT2544-1AB00 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}