{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT2626-1AP05","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT2626-1AP05","canonicalUrl":"https://aoctrl.com/siemens/3RT2626-1AP05","factsUrl":"https://aoctrl.com/api/mcp/products/3RT2626-1AP05","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RT2626-1AP05 capacitor contactor, size S0, 45 mm width, screw-type terminals, 6 A at 230 V AC, 50 Hz rated coil.","salesMarkdown":"## SIRIUS capacitor contactor — panel fit and ratings The 3RT2626-1AP05: The coil is AC-operated with screw-type terminals, rated at 230 V, 50 Hz. Terminal capacity accepts solid conductors up to 4 mm² (2x) or stranded up to 10 mm² (2x), with a 1x 10 mm² solid at 40 °C ambient. ## What the switching ratings mean for capacitor duty Capacitor contactors are rated for the inrush current of a capacitor bank, not for motor starting. At 400 V, the 3 A rating covers about 2 kvar three-phase. The maximum switching frequency is 100 operations per hour across the voltage range from 230 V to 690 V. The arcing time is 10 ms, and the AC switching time is 4 to 16 ms.","metaTitle":"Siemens 3RT2626-1AP05 SIRIUS Capacitor Contactor, S0, 45 mm","metaDescription":"Siemens 3RT2626-1AP05 SIRIUS capacitor contactor, size S0, 45 mm wide, screw terminals, rated 6 A at 230 V AC. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"155 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), 2x 4 mm²","Width":"45 mm","at AC":"4 ... 16 ms","Height":"135 mm","at 24 V":"6 A","at 60 V":"2 A","Stranded":"2x (1 ... 2.5 mm²), 2x (2.5 ... 10 mm²)","at 110 V":"1 A","at 125 V":"0.9 A","at 220 V":"0.3 A","at 230 V":"6 A","at 400 V":"3 A","at 50 Hz":"0.8 ... 1.1","at 690 V":"1 A","at 40 °C":"1x 10 mm²","at 60 °C":"2x 10 mm²","Attachable":"0","Arcing Time":"10 ... 10 ms","1 Rated Value":"50 Hz","During Storage":"-55 ... +80 °C","Of Magnet Coil":"Screw-type terminals","Type Of Voltage":"AC","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 50022","at 230 V maximum":"100 1/h","at 240 V maximum":"100 1/h","at 400 V maximum":"100 1/h","at 480 V maximum":"100 1/h","at 500 V maximum":"100 1/h","at 600 V maximum":"100 1/h","at 690 V maximum":"100 1/h","Mounting Position":"+/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface","Size Of Contactor":"S0","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), 2x 4 mm²","Product Brand Name":"SIRIUS","Product Designation":"capacitor contactors","at 50 Hz rated value":"230 V","Instantaneous Contact":"1","For Main Current Circuit":"screw-type terminals","Relative Humidity Minimum":"10 %","Of Main Circuit Rated Value":"6 kV","Substance Prohibitance (Date)":"05/01/2014","For Grounded Parts At The Side":"10 mm","Of Auxiliary Circuit Rated Value":"6 kV","For Auxiliary And Control Circuit":"screw-type terminals","Product Extension Auxiliary Switch":"No","at AC at 230 V maximum permissible":"7 mA","At Contactor For Auxiliary Contacts":"Screw-type terminals","for AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 2x 12","With Side-By-Side Mounting At The Side":"10 mm","Electrical Endurance (Operating Cycles)":"200 000","number of NC contacts for main contacts":"0","number of NO contacts for main contacts":"3","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Contact Reliability Of Auxiliary Contacts":"0.00000001","mirror contact according to IEC 60947-4-1":"No","apparent holding power of magnet coil at AC":"9.8 VA","apparent pick-up power of magnet coil at AC":"77 VA","number of NC contacts for auxiliary contacts":"2","number of NO contacts for auxiliary contacts":"1","Type Of Voltage Of The Control Supply Voltage":"AC","contact rating of auxiliary contacts according to UL":"A600 / Q600","Inductive Power Factor With Closing Power Of The Coil":"0.82","Of Main Circuit With Degree Of Pollution 3 Rated Value":"690 V","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Inductive Power Factor With The Holding Power Of The Coil":"0.25","Of The Contactor With Added Auxiliary Switch Block Typical":"3 000 000","operational current of auxiliary contacts at AC-12 maximum":"10 A","Of Auxiliary Circuit With Degree Of Pollution 3 Rated Value":"690 V","For Short-Circuit Protection Of The Auxiliary Switch Required":"gG: 10 A (500 V, 1 kA)","AWG number as coded connectable conductor cross section for main contacts":"16 ... 8","For Short-Circuit Protection Of The Main Circuit With Type Of Coordination 1 Required":"gG: 63 A (690 V, 50 kA)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/36dd2efac410d81a7399adb948b76e7c.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=208759&mlfb=3RT2626-1AP05","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT2626-1AP05/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT2626-1AP05","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT2626-1AP05 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}