{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT5036-1AP00","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT5036-1AP00","canonicalUrl":"https://aoctrl.com/siemens/3RT5036-1AP00","factsUrl":"https://aoctrl.com/api/mcp/products/3RT5036-1AP00","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS, power contactor, Size S2, 3RT5036-1AP00, screw-type terminals, 55 mm width, 690 V rated insulation voltage, snap-on DIN rail mounting.","salesMarkdown":"Motor power at 400 V and 60 °C is 38 kW; at 690 V and 60 °C it reaches 66 kW. Fastens with screws or snaps onto a 35 mm rail. Side-by-side mounting is allowed without derating. Dimensions: 112 mm high, 55 mm wide, 115 mm deep — that 55 mm width is the same as many SIRIUS S2 contactors, so it drops into existing panel layouts without re-spacing. ## Switching performance and auxiliary options Rated for 5 000 operating cycles per hour at AC, with AC-1 maximum 1 000 1/h, AC-3 maximum 800 1/h, and AC-4 maximum 300 1/h. The contactor supports an auxiliary switch extension (product extension auxiliary switch: yes), so you can add side-mounted blocks for feedback or interlocking without modifying the main wiring.","metaTitle":"Siemens 3RT5036-1AP00 SIRIUS Power Contactor, Size S2, 55 mm","metaDescription":"Siemens SIRIUS 3RT5036-1AP00 power contactor, Size S2, screw terminals, 55 mm wide, 690 V insulation. Active production. Sourced to order. RFQ for pricing.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"115 mm","Width":"55 mm","at AC":"5 000 1/h","Height":"112 mm","at 50 Hz":"0.36","During Storage":"-55 ... +80 °C","at AC-1 maximum":"1 000 1/h","at AC-3 maximum":"800 1/h","at AC-4 maximum":"300 1/h","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Fastening Method":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","at AC-3e maximum":"800 1/h","Mounting Position":"+/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface","Size Of Contactor":"S2","Solid Or Stranded":"2x (0.75 ... 16 mm²)","Product Brand Name":"SIRIUS","Degree Of Pollution":"3","Product Designation":"Power contactor","at 24 V rated value":"6 A","Of Contactor Typical":"10 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 50 Hz rated value":"230 V","at 690 V rated value":"11.4 kW","Side-By-Side Mounting":"Yes","For Main Current Circuit":"screw-type terminals","at AC-3e rated value maximum":"690 V","Substance Prohibitance (Date)":"03/01/2017","at 40 °C minimum permissible":"16 mm²","at 60 °C minimum permissible":"16 mm²","Insulation Voltage Rated Value":"690 V","at 230 V at 60 °C rated value":"22 kW","at 400 V at 60 °C rated value":"38 kW","at 690 V at 60 °C rated value":"66 kW","at AWG cables for main contacts":"2x (18 ... 2)","For Auxiliary And Control Circuit":"screw-type terminals","Product Extension Auxiliary Switch":"Yes","With Type Of Assignment 2 Required":"fuse gL/gG: 80 A","Surge Voltage Resistance Rated Value":"6 kV","With Type Of Coordination 1 Required":"fuse gL/gG: 160 A","at AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","operational current at AC-12 maximum":"10 A","number of NC contacts for main contacts":"0","number of NO contacts for main contacts":"3","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","at ambient temperature 40 °C rated value":"60 A","at ambient temperature 60 °C rated value":"55 A","Finely Stranded Without Core End Processing":"2x (0.75 ... 16 mm²)","Type Of Voltage Of The Control Supply Voltage":"AC","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","number of NC contacts for auxiliary contacts instantaneous contact":"0","number of NO contacts for auxiliary contacts instantaneous contact":"0"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/ddc648a2cff12517c056eb65925cbb64.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=580005&mlfb=3RT5036-1AP00","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT5036-1AP00/alternatives.json"},"ai":{"faq":[{"question":"Will 3RT5036-1AP00 drop into a panel that was specified around 3RT5035-1AH00 without rewiring?","answer":"Both are Size S2 contactors with the same 55 mm width and screw-terminal footprint, so the 3RT5036-1AP00 fits the same DIN-rail position and terminal layout. No rewiring of the panel is needed."},{"question":"What compliance documentation does this brand provide for 3RT5036-1AP00?","answer":"The contactor carries a RoHS compliance date of March 1, 2017. Full compliance documentation (RoHS, REACH, UL, IEC) is available from Siemens upon request."},{"question":"Where can I buy 3RT5036-1AP00 and how is it quoted?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT5036-1AP00","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT5036-1AP00 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}