{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT5044-1AP00","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT5044-1AP00","canonicalUrl":"https://aoctrl.com/siemens/3RT5044-1AP00","factsUrl":"https://aoctrl.com/api/mcp/products/3RT5044-1AP00","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS S3 power contactor, 3RT5044-1AP00, screw-type terminals, 70 mm width, AC-3e rated to 1000 V, active lifecycle.","salesMarkdown":"It carries a rated insulation voltage of 1000 V and an AC-3e maximum rated voltage of 1000 V, so it handles 400 V and 690 V motor circuits without derating for voltage. The contactor is rated for AC-3e switching at up to 1000 operations per hour, and AC-4 duty at up to 300 operations per hour — the AC-4 figure governs plugging and inching applications where the contacts break full motor current at standstill. Motor power ratings are given at 60 °C ambient: 34 kW at 230 V, 59 kW at 400 V, and 102 kW at 690 V. The 60 °C ratings are the ones to use for a panel with elevated internal temperature — the contactor is rated for operation from -25 °C to +60 °C, with storage from -55 °C to +80 °C. Side-by-side mounting is permitted, which keeps the panel width compact when ganging multiple contactors. Dimensions are 70 mm wide, 146 mm high, and 139 mm deep — the 70 mm width is the critical panel-space number. Main circuit and auxiliary/control circuit terminals are screw-type, accepting 2x (2.5 to 16 mm²) solid or stranded, or 2x (10 to 1/0 AWG). The contactor supports auxiliary switch extension, so you can add a side-mounted block for status feedback without rewiring the main circuit.","metaTitle":"Siemens 3RT5044-1AP00 SIRIUS Power Contactor, S3 Size, 70 mm","metaDescription":"Siemens 3RT5044-1AP00 SIRIUS S3 power contactor, 70 mm wide, screw terminals, AC-3e rated to 1000 V. Active production, sourced to order. Request quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"139 mm","Width":"70 mm","at AC":"5 000 1/h","Height":"146 mm","at 50 Hz":"0.26","During Storage":"-55 ... +80 °C","at AC-1 maximum":"1 000 1/h","at AC-3 maximum":"1 000 1/h","at AC-4 maximum":"300 1/h","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Fastening Method":"screw and snap-on mounting onto 35 mm and 75 mm DIN rail","at AC-3e maximum":"1 000 1/h","Mounting Position":"+/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface","Size Of Contactor":"S3","Solid Or Stranded":"2x (2.5 ... 16 mm²)","Product Brand Name":"SIRIUS","Degree Of Pollution":"3","Product Designation":"Power contactor","at 24 V rated value":"6 A","Of Contactor Typical":"10 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 50 Hz rated value":"230 V","at 690 V rated value":"18.6 kW","Side-By-Side Mounting":"Yes","For Main Current Circuit":"screw-type terminals","at AC-3e rated value maximum":"1 000 V","Substance Prohibitance (Date)":"03/01/2017","at 40 °C minimum permissible":"35 mm²","at 60 °C minimum permissible":"35 mm²","Insulation Voltage Rated Value":"1 000 V","at 230 V at 60 °C rated value":"34 kW","at 400 V at 60 °C rated value":"59 kW","at 690 V at 60 °C rated value":"102 kW","at AWG cables for main contacts":"2x (10 ... 1/0)","For Auxiliary And Control Circuit":"screw-type terminals","Product Extension Auxiliary Switch":"Yes","With Type Of Assignment 2 Required":"fuse gL/gG: 125 A","Surge Voltage Resistance Rated Value":"6 kV","With Type Of Coordination 1 Required":"fuse gL/gG: 250 A","at AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","operational current at AC-12 maximum":"10 A","number of NC contacts for main contacts":"0","number of NO contacts for main contacts":"3","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","at ambient temperature 40 °C rated value":"100 A","at ambient temperature 60 °C rated value":"90 A","Finely Stranded Without Core End Processing":"2x (10 ... 35 mm²)","Type Of Voltage Of The Control Supply Voltage":"AC","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","number of NC contacts for auxiliary contacts instantaneous contact":"0","number of NO contacts for auxiliary contacts instantaneous contact":"0"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=580020&mlfb=3RT5044-1AP00","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT5044-1AP00/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3RT5044-1AP00?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What are the key dimensions of 3RT5044-1AP00?","answer":"Width is 70 mm, height is 146 mm, and depth is 139 mm. The 70 mm width is the panel-space-critical dimension for DIN-rail mounting."},{"question":"Will 3RT5044-1AP00 drop into a panel specified for 3RT5044-1BM40?","answer":"Both are SIRIUS S3-size contactors with the same mounting footprint on 35 mm or 75 mm DIN rail, so the panel cutout and rail position are identical. The 1AP00 uses screw-type terminals; verify that the 1BM40's terminal type (if spring-cage) does not require a different wiring method for your lugs."},{"question":"What compliance documentation does Siemens provide for 3RT5044-1AP00?","answer":"The part carries a substance prohibitance date of 03/01/2017, indicating RoHS and REACH compliance. It also has a rated insulation voltage of 1000 V per IEC standards."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT5044-1AP00","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT5044-1AP00 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}