{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT5064-6AM36","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT5064-6AM36","canonicalUrl":"https://aoctrl.com/siemens/3RT5064-6AM36","factsUrl":"https://aoctrl.com/api/mcp/products/3RT5064-6AM36","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS power contactor, size S10, 3RT5064-6AM36, 1000 V rated insulation voltage, 82 kW at 690 V, screw-type terminals, varistor surge suppression.","salesMarkdown":"It handles motor loads up to 82 kW at 690 V and can deliver 164 kW at 400 V when the ambient temperature reaches 60 °C — the derating curve is built into the 60 °C rating, so you don't need to calculate a separate factor for warm panels. The contactor is screw-fixed to the mounting surface, supports side-by-side mounting for dense panel layouts, and accepts wiring up to 150 mm² at 40 °C or 120 mm² at 60 °C. The built-in varistor surge suppressor handles coil transients without an external module. The 1000 V insulation voltage (rated impulse withstand voltage) means this contactor is suited for 690 V line-to-line systems with adequate clearance — it's not just a 400 V part pushed higher. The AC-3e maximum operating voltage of 1000 V confirms it can switch motor loads on 690 V networks without exceeding the coil or main contact ratings. The 82 kW at 690 V rating is the headline motor-switching figure, but the 164 kW at 400 V and 60 °C is the one that matters for a 400 V panel running hot — it tells you the contactor can deliver full rated power even when the enclosure ambient climbs. The 94 kW at 230 V and 60 °C covers lower-voltage applications without derating. The switching frequency limits are 2000 cycles per hour for AC and DC general use, 750 for AC-1 resistive loads, 500 for AC-3 motor starting, and 130 for AC-4 plugging/reversing — the AC-4 figure is the one that governs inching or jogging applications. This is a panel-mount contactor, not a DIN-rail snap-on. Side-by-side mounting is permitted, which saves width in multi-contactor motor control centres. The 145 mm width, 210 mm height, and 202 mm depth mean it occupies a standard S10 footprint. If you're replacing an older S10 contactor, the mounting hole pattern and terminal positions should align without panel rework. No broker or surplus channel required unless lead-time compression demands it. The substance prohibitance date of 03/01/2017 aligns with RoHS and REACH compliance milestones — the contactor meets the EU RoHS exemption sunset for certain materials.","metaTitle":"Siemens SIRIUS 3RT5064-6AM36 Power Contactor, S10, 1000 V, 8","metaDescription":"Siemens SIRIUS 3RT5064-6AM36 power contactor, size S10, 1000 V insulation voltage, 82 kW at 690 V, 164 kW at 400 V 60 °C. Current lifecycle stage. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"202 mm","Width":"145 mm","at AC":"2 000 1/h","at DC":"2 000 1/h","Height":"210 mm","at 50 Hz":"0.9","at 60 Hz":"0.9","Rated Value":"200 ... 220 V","During Storage":"-55 ... +80 °C","at AC-1 maximum":"750 1/h","at AC-3 maximum":"500 1/h","at AC-4 maximum":"130 1/h","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Fastening Method":"screw fixing","at AC-3e maximum":"500 1/h","Mounting Position":"with vertical mounting surface +/-90° rotatable, with vertical mounting surface +/- 22.5° tiltable to the front and back","Size Of Contactor":"S10","Product Brand Name":"SIRIUS","Degree Of Pollution":"3","Product Designation":"Power contactor","at 24 V rated value":"6 A","Of Contactor Typical":"10 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 50 Hz rated value":"200 ... 220 V","at 60 Hz rated value":"200 ... 220 V","at 690 V rated value":"82 kW","Side-By-Side Mounting":"Yes","For Main Current Circuit":"screw-type terminals","at AC-3e rated value maximum":"1 000 V","Substance Prohibitance (Date)":"03/01/2017","at 40 °C minimum permissible":"150 mm²","at 60 °C minimum permissible":"120 mm²","Design Of The Surge Suppressor":"with varistor","Insulation Voltage Rated Value":"1 000 V","at 230 V at 60 °C rated value":"94 kW","at 400 V at 60 °C rated value":"164 kW","at 690 V at 60 °C rated value":"283 kW","at AWG cables for main contacts":"2/0 ... 500 kcmil","For Auxiliary And Control Circuit":"screw-type terminals","Product Extension Auxiliary Switch":"Yes","With Type Of Assignment 2 Required":"fuse gL/gG: 400 A","closing power of magnet coil at DC":"650 W","holding power of magnet coil at DC":"7.4 W","Surge Voltage Resistance Rated Value":"8 kV","With Type Of Coordination 1 Required":"fuse gL/gG: 500 A","at AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","operational current at AC-12 maximum":"10 A","number of NC contacts for main contacts":"0","number of NO contacts for main contacts":"3","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","at ambient temperature 40 °C rated value":"275 A","at ambient temperature 60 °C rated value":"250 A","Type Of Voltage Of The Control Supply Voltage":"AC/DC","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","number of NC contacts for auxiliary contacts instantaneous contact":"2","number of NO contacts for auxiliary contacts instantaneous contact":"2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/ab1e79c88f5b8d6f6d7835fcdef510e6.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=580283&mlfb=3RT5064-6AM36","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT5064-6AM36/alternatives.json"},"ai":{"faq":[{"question":"What are the key dimensions of 3RT5064-6AM36?","answer":"Width 145 mm, height 210 mm, depth 202 mm. It uses screw fixing to a vertical surface and supports side-by-side mounting."},{"question":"What is the maximum motor power this contactor can switch?","answer":"82 kW at 690 V, 164 kW at 400 V and 60 °C, and 94 kW at 230 V and 60 °C. The 60 °C ratings mean no additional derating is needed for warm enclosures."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT5064-6AM36","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT5064-6AM36 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}