{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT6015-1AG02","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT6015-1AG02","canonicalUrl":"https://aoctrl.com/siemens/3RT6015-1AG02","factsUrl":"https://aoctrl.com/api/mcp/products/3RT6015-1AG02","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS, power contactor, size S00, 3RT6015-1AG02, screw-type terminals, AC-3 rated 690 V, 45 x 57.5 x 73 mm, snap-on DIN rail.","salesMarkdown":"It carries AC-3 and AC-3e ratings up to 690 V maximum, so it handles standard 400 V and 690 V motor circuits without derating. Motor power at 60 °C ambient — a realistic panel condition near drives or furnaces — reaches 6 kW at 230 V, 10.5 kW at 400 V, and 18 kW at 690 V, which covers a wide band of pump, fan, and conveyor motors in a single contactor footprint. Rated operational current at AC-1 (resistive) is 10 A at 230 V, 3 A at 400 V, and 1 A at 690 V. The AC-3 switching frequency maximum is 750 operations per hour, while AC-4 (plugging/inching) is limited to 250 operations per hour — respect that for reversing or jogging duty cycles. The S00 footprint — 45 mm width, 57.5 mm height, 73 mm depth — fits tight panel layouts; side-by-side mounting is permitted with no derating gap required. Main current circuit uses screw-type terminals accepting 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), or 2x 4 mm² solid/stranded conductors. Minimum permissible cross-section at 40 °C and 60 °C is 2.5 mm². For a BOM freeze or line-down replacement, the AC-3 ratings and S00 DIN-rail footprint are the fit criteria — verify the coil voltage variant matches your control circuit.","metaTitle":"Siemens 3RT6015-1AG02 SIRIUS Power Contactor, S00, 690 V AC-","metaDescription":"Siemens SIRIUS 3RT6015-1AG02 power contactor, size S00, screw terminals, rated 690 V AC-3/AC-3e, 6 kW at 400 V 60 °C. Snap-on 35 mm DIN rail. Current lifecycle stage. Quoted to ord","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"73 mm","Width":"45 mm","at AC":"10 000 1/h","title":"3RT6015-1AG02","Height":"57.5 mm","at 50 Hz":"0.25","at 60 Hz":"0.25","description":"Contactor AC 36 V 50/60 HZ AC3 3 kW 400 V AUX contacts: 1 NC 3-pole, size S00 screw terminal","During Storage":"-55 ... +80 °C","at AC-1 maximum":"1 000 1/h","at AC-3 maximum":"750 1/h","at AC-4 maximum":"250 1/h","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 50022","at AC-3e maximum":"750 1/h","Mounting Position":"+/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface","Size Of Contactor":"S00","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), 2x 4 mm²","Product Brand Name":"SIRIUS","Degree Of Pollution":"3","Product Designation":"Power contactor","at 24 V rated value":"6 A","Of Contactor Typical":"30 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"10 A","at 400 V rated value":"3 A","at 50 Hz rated value":"36 V","at 60 Hz rated value":"36 V","at 690 V rated value":"1 A","Side-By-Side Mounting":"Yes","For Main Current Circuit":"screw-type terminals","at AC-3 rated value maximum":"690 V","at AC-3e rated value maximum":"690 V","Substance Prohibitance (Date)":"05/01/2012","at 40 °C minimum permissible":"2.5 mm²","at 60 °C minimum permissible":"2.5 mm²","Insulation Voltage Rated Value":"690 V","at 230 V at 60 °C rated value":"6 kW","at 400 V at 60 °C rated value":"10.5 kW","at 690 V at 60 °C rated value":"18 kW","for AWG cables for main contacts":"2x (20 ... 16), 2x (18 ... 14), 2x 12","For Auxiliary And Control Circuit":"screw-type terminals","Product Extension Auxiliary Switch":"Yes","With Type Of Assignment 2 Required":"gL/gG LV HRC 3NA, DIAZED 5SB, NEOZED 5SE: 20 A","Surge Voltage Resistance Rated Value":"6 kV","With Type Of Coordination 1 Required":"gL/gG LV HRC 3NA, DIAZED 5SB, NEOZED 5SE: 35 A","operational current at AC-12 maximum":"10 A","for AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 2x 12","number of NC contacts for main contacts":"0","number of NO contacts for main contacts":"3","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","at ambient temperature 40 °C rated value":"18 A","at ambient temperature 60 °C rated value":"16 A","Type Of Voltage Of The Control Supply Voltage":"AC","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Required Spacing With Side-By-Side Mounting At The Side":"0 mm","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","number of NC contacts for auxiliary contacts instantaneous contact":"1","number of NO contacts for auxiliary contacts instantaneous contact":"0"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/db985561bc48a2aacd784381152dced6.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=580134&mlfb=3RT6015-1AG02"},"ai":{"faq":[{"question":"What is the depth of 3RT6015-1AG02?","answer":"73 mm depth, with a width of 45 mm and height of 57.5 mm. It snaps onto 35 mm DIN rail."},{"question":"What motor power can 3RT6015-1AG02 switch at 400 V?","answer":"10.5 kW at 400 V 60 °C ambient, and 6 kW at 230 V or 18 kW at 690 V under the same conditions."},{"question":"Where can I buy 3RT6015-1AG02 and what is the lead time?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"Will 3RT6015-1AG02 drop into a panel designed for 3RT6018-1AB02?","answer":"Both are S00 size contactors on the same 35 mm DIN-rail footprint, so the physical fit is identical. The difference is in current ratings — verify the load current against the 3RT6015's AC-3 ratings before swapping."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT6015-1AG02","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT6015-1AG02 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}