{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT6016-1AM22","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT6016-1AM22","canonicalUrl":"https://aoctrl.com/siemens/3RT6016-1AM22","factsUrl":"https://aoctrl.com/api/mcp/products/3RT6016-1AM22","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS Size S00 power contactor, 3RT6016-1AM22, 13 kW at 400 V 60 °C, screw terminals, DIN rail snap-on.","salesMarkdown":"## DIN rail footprint and panel fit The 3RT6016-1AM22: The 45 mm width and 73 mm depth fit a standard 35 mm DIN rail enclosure. Mounting position is flexible: ±180° rotation on a vertical surface, plus ±22.5° tilt forward/backward. ## Switching capacity and thermal limits Rated operational current at AC-3 duty is 6 A at 24 V, 10 A at 230 V, and 3 A at 400 V. The contactor handles 7.5 kW at 230 V and 13 kW at 400 V (60 °C). For higher-voltage systems, it delivers 22 kW at 690 V. Operating temperature spans -25 to +60 °C; storage range is -55 to +80 °C. Mechanical life is rated at 30 million operations, with switching frequencies up to 10 000 cycles per hour at AC.","metaTitle":"Siemens 3RT6016-1AM22 SIRIUS Power Contactor, 13 kW at 400 V","metaDescription":"Siemens SIRIUS 3RT6016-1AM22 power contactor, Size S00, 13 kW at 400 V 60 °C. Screw terminals, DIN rail mount. Active production. Quoted on request.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"73 mm","Width":"45 mm","at AC":"10 000 1/h","Height":"57.5 mm","at 50 Hz":"0.25","at 60 Hz":"0.25","During Storage":"-55 ... +80 °C","at AC-1 maximum":"1 000 1/h","at AC-3 maximum":"750 1/h","at AC-4 maximum":"250 1/h","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 50022","at AC-3e maximum":"750 1/h","Mounting Position":"+/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface","Size Of Contactor":"S00","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), 2x 4 mm²","Product Brand Name":"SIRIUS","Degree Of Pollution":"3","Product Designation":"Power contactor","at 24 V rated value":"6 A","Of Contactor Typical":"30 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"10 A","at 400 V rated value":"3 A","at 50 Hz rated value":"208 V","at 60 Hz rated value":"208 V","at 690 V rated value":"1 A","Side-By-Side Mounting":"Yes","For Main Current Circuit":"screw-type terminals","at AC-3 rated value maximum":"690 V","at AC-3e rated value maximum":"690 V","Substance Prohibitance (Date)":"05/01/2012","at 40 °C minimum permissible":"4 mm²","at 60 °C minimum permissible":"2.5 mm²","Insulation Voltage Rated Value":"690 V","at 230 V at 60 °C rated value":"7.5 kW","at 400 V at 60 °C rated value":"13 kW","at 690 V at 60 °C rated value":"22 kW","for AWG cables for main contacts":"2x (20 ... 16), 2x (18 ... 14), 2x 12","For Auxiliary And Control Circuit":"screw-type terminals","Product Extension Auxiliary Switch":"Yes","With Type Of Assignment 2 Required":"gL/gG LV HRC 3NA, DIAZED 5SB, NEOZED 5SE: 20 A","Surge Voltage Resistance Rated Value":"6 kV","With Type Of Coordination 1 Required":"gL/gG LV HRC 3NA, DIAZED 5SB, NEOZED 5SE: 35 A","operational current at AC-12 maximum":"10 A","for AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 2x 12","number of NC contacts for main contacts":"0","number of NO contacts for main contacts":"3","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","at ambient temperature 40 °C rated value":"22 A","at ambient temperature 60 °C rated value":"20 A","Type Of Voltage Of The Control Supply Voltage":"AC","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Required Spacing With Side-By-Side Mounting At The Side":"0 mm","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","number of NC contacts for auxiliary contacts instantaneous contact":"1","number of NO contacts for auxiliary contacts instantaneous contact":"0"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/a426fcc6323670f066362c1475635a72.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=723069&mlfb=3RT6016-1AM22","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT6016-1AM22/alternatives.json"},"ai":{"faq":[{"question":"What are the key power ratings for 3RT6016-1AM22?","answer":"At 400 V 60 °C it is rated for 13 kW motor load; at 690 V 60 °C it delivers 22 kW. At 230 V 60 °C it handles 7.5 kW."},{"question":"What compliance documentation does this brand provide for 3RT6016-1AM22?","answer":"RoHS compliance is documented with a substance prohibition date of 05/01/2012. The contactor is rated for pollution degree 3 and insulation voltage 690 V."},{"question":"Where can I buy 3RT6016-1AM22 and how is it quoted?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT6016-1AM22","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT6016-1AM22 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}