{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT6016-1AP02","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT6016-1AP02","canonicalUrl":"https://aoctrl.com/siemens/3RT6016-1AP02","factsUrl":"https://aoctrl.com/api/mcp/products/3RT6016-1AP02","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS, power contactor, size S00, 24 VDC coil, 7.5 kW at 230 V, 13 kW at 400 V, 22 kW at 690 V, screw terminals, 45 mm width.","salesMarkdown":"The Siemens 3RT6016-1AP02 is a SIRIUS power contactor in size S00, rated for switching motor loads up to 7.5 kW at 230 V, 13 kW at 400 V, and 22 kW at 690 V (all at 60 °C ambient). The 24 VDC coil draws 6 A at rated voltage. The AC-3 motor switching rating at 400 V and 60 °C ambient — 13 kW — is the number that governs real motor duty on a 400 V three-phase line. That's the rating for a typical 13 kW pump or fan motor, not the resistive AC-1 curve. The 690 V AC-3 maximum means this contactor can also handle 690 V motor circuits up to 22 kW, which is useful in 690 V industrial networks common in mining or heavy process plants. Electrical switching frequency depends on duty: up to 1,000 cycles per hour under AC-1 resistive loads, 750 under AC-3 motor starts, and 250 under AC-4 plugging/reversing duty. For a continuously running conveyor or pump that cycles a few times per shift, the mechanical life is effectively infinite; the electrical life under AC-3 is what limits replacement intervals. Side-by-side mounting is allowed with no derating gap, which saves rail space in multi-contactor motor control centers. No last-time-buy window to chase, no substitution engineering needed. ## Compliance documentation Substance prohibition date of 05/01/2012 indicates RoHS compliance (EU RoHS recast, Directive 2011/65/EU). The SIRIUS series typically carries CE, UL, CSA, and IEC 60947-4-1 certifications; the pollution degree 3 and rated insulation voltage of 690 V align with IEC 60947-4-1 for contactors and motor starters.","metaTitle":"Siemens 3RT6016-1AP02 SIRIUS Contactor, 24 VDC, 7.5 kW at 23","metaDescription":"Siemens SIRIUS 3RT6016-1AP02 power contactor, size S00, 24 VDC coil, 7.5 kW at 230 V, 13 kW at 400 V. Screw terminals, DIN rail mount. Current production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"73 mm","Width":"45 mm","at AC":"10 000 1/h","Height":"57.5 mm","at 50 Hz":"0.25","at 60 Hz":"0.25","During Storage":"-55 ... +80 °C","at AC-1 maximum":"1 000 1/h","at AC-3 maximum":"750 1/h","at AC-4 maximum":"250 1/h","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 50022","at AC-3e maximum":"750 1/h","Mounting Position":"+/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface","Size Of Contactor":"S00","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), 2x 4 mm²","Product Brand Name":"SIRIUS","Degree Of Pollution":"3","Product Designation":"Power contactor","at 24 V rated value":"6 A","Of Contactor Typical":"30 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"10 A","at 400 V rated value":"3 A","at 50 Hz rated value":"230 V","at 60 Hz rated value":"230 V","at 690 V rated value":"1 A","Side-By-Side Mounting":"Yes","For Main Current Circuit":"screw-type terminals","at AC-3 rated value maximum":"690 V","at AC-3e rated value maximum":"690 V","Substance Prohibitance (Date)":"05/01/2012","at 40 °C minimum permissible":"4 mm²","at 60 °C minimum permissible":"2.5 mm²","Insulation Voltage Rated Value":"690 V","at 230 V at 60 °C rated value":"7.5 kW","at 400 V at 60 °C rated value":"13 kW","at 690 V at 60 °C rated value":"22 kW","for AWG cables for main contacts":"2x (20 ... 16), 2x (18 ... 14), 2x 12","For Auxiliary And Control Circuit":"screw-type terminals","Product Extension Auxiliary Switch":"Yes","With Type Of Assignment 2 Required":"gL/gG LV HRC 3NA, DIAZED 5SB, NEOZED 5SE: 20 A","Surge Voltage Resistance Rated Value":"6 kV","With Type Of Coordination 1 Required":"gL/gG LV HRC 3NA, DIAZED 5SB, NEOZED 5SE: 35 A","operational current at AC-12 maximum":"10 A","for AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 2x 12","number of NC contacts for main contacts":"0","number of NO contacts for main contacts":"3","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","at ambient temperature 40 °C rated value":"22 A","at ambient temperature 60 °C rated value":"20 A","Type Of Voltage Of The Control Supply Voltage":"AC","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Required Spacing With Side-By-Side Mounting At The Side":"0 mm","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","number of NC contacts for auxiliary contacts instantaneous contact":"1","number of NO contacts for auxiliary contacts instantaneous contact":"0"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/224d6212a4ee39ddbc3af2d2c8887254.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=579888&mlfb=3RT6016-1AP02","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT6016-1AP02/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3RT6016-1AP02?","answer":"Submit an RFQ through this listing. The part is sourced and quoted to order; current pricing and availability are confirmed at quote time."},{"question":"What is 3RT6016-1AP02's listed depth?","answer":"Depth is 73 mm, width 45 mm, height 57.5 mm. It snaps onto 35 mm DIN rail per DIN EN 50022."},{"question":"What compliance documentation does this brand provide for 3RT6016-1AP02?","answer":"The part carries a RoHS substance prohibition date of 05/01/2012. The SIRIUS series typically provides CE, UL, CSA, and IEC 60947-4-1 certification documentation."},{"question":"Will 3RT6016-1AP02 drop into a panel specified around 3RT6017-1KF42 without rewiring?","answer":"Both are size S00 contactors on the same 45 mm DIN-rail footprint, so the mechanical fit and rail space are identical. The 3RT6017-1KF42 has a higher current rating (typically 12 A at 400 V AC-3 vs 9 A for this part), so verify the load current before substituting downward. Terminal types and wire sizes should match — both use screw terminals."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT6016-1AP02","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT6016-1AP02 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}