{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT6016-1AR61","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT6016-1AR61","canonicalUrl":"https://aoctrl.com/siemens/3RT6016-1AR61","factsUrl":"https://aoctrl.com/api/mcp/products/3RT6016-1AR61","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS power contactor, Size S00, 3RT6016-1AR61, 13 kW at 400 V AC-3e, screw terminals, 45 mm width, 73 mm depth.","salesMarkdown":"The Siemens 3RT6016-1AR61 is a SIRIUS power contactor in the compact Size S00 frame, rated to switch a 13 kW motor at 400 V in AC-3e duty. The contactor also carries a 7.5 kW rating at 230 V and a 22 kW rating at 690 V, so it scales across common European supply voltages. The operating range covers most industrial panel environments, including near hot machinery. The degree of pollution is 3, meaning it's rated for conductive pollution in industrial atmospheres — no extra conformal coating needed for typical factory floor conditions. ## Switching performance Mechanical life is 30,000,000 operating cycles typical. Electrical switching frequency: up to 10,000 cycles per hour at AC general use, 1,000/h at AC-1 resistive, 750/h at AC-3 and AC-3e motor duty, and 250/h at AC-4 plugging/reversing.","metaTitle":"Siemens 3RT6016-1AR61 SIRIUS Power Contactor, 13 kW at 400 V","metaDescription":"Siemens 3RT6016-1AR61 SIRIUS power contactor, Size S00, 13 kW at 400 V AC-3e. Screw terminals, DIN rail mount. Active production. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"73 mm","Width":"45 mm","at AC":"10 000 1/h","Height":"57.5 mm","at 50 Hz":"0.25","at 60 Hz":"0.25","During Storage":"-55 ... +80 °C","at AC-1 maximum":"1 000 1/h","at AC-3 maximum":"750 1/h","at AC-4 maximum":"250 1/h","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 50022","at AC-3e maximum":"750 1/h","Mounting Position":"+/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface","Size Of Contactor":"S00","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), 2x 4 mm²","Product Brand Name":"SIRIUS","Degree Of Pollution":"3","Product Designation":"Power contactor","at 24 V rated value":"6 A","Of Contactor Typical":"30 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"10 A","at 400 V rated value":"3 A","at 50 Hz rated value":"400 V","at 60 Hz rated value":"440 V","at 690 V rated value":"1 A","Side-By-Side Mounting":"Yes","For Main Current Circuit":"screw-type terminals","at AC-3 rated value maximum":"690 V","at AC-3e rated value maximum":"690 V","Substance Prohibitance (Date)":"05/01/2012","at 40 °C minimum permissible":"4 mm²","at 60 °C minimum permissible":"2.5 mm²","Insulation Voltage Rated Value":"690 V","at 230 V at 60 °C rated value":"7.5 kW","at 400 V at 60 °C rated value":"13 kW","at 690 V at 60 °C rated value":"22 kW","for AWG cables for main contacts":"2x (20 ... 16), 2x (18 ... 14), 2x 12","For Auxiliary And Control Circuit":"screw-type terminals","Product Extension Auxiliary Switch":"Yes","With Type Of Assignment 2 Required":"gL/gG LV HRC 3NA, DIAZED 5SB, NEOZED 5SE: 20 A","Surge Voltage Resistance Rated Value":"6 kV","With Type Of Coordination 1 Required":"gL/gG LV HRC 3NA, DIAZED 5SB, NEOZED 5SE: 35 A","operational current at AC-12 maximum":"10 A","for AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 2x 12","number of NC contacts for main contacts":"0","number of NO contacts for main contacts":"3","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","at ambient temperature 40 °C rated value":"22 A","at ambient temperature 60 °C rated value":"20 A","Type Of Voltage Of The Control Supply Voltage":"AC","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Required Spacing With Side-By-Side Mounting At The Side":"0 mm","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","number of NC contacts for auxiliary contacts instantaneous contact":"0","number of NO contacts for auxiliary contacts instantaneous contact":"1"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=579891&mlfb=3RT6016-1AR61","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT6016-1AR61/alternatives.json"},"ai":{"faq":[{"question":"What is the closest functional second-source to 3RT6016-1AR61?","answer":"The 3RT6018-1AB02 is a peer in the same S00 frame size, but it has a different coil voltage and terminal type — 3RT6016-1AR61 uses a 24 V DC coil with screw terminals, while the 3RT6018-1AB02 uses a different coil. They share the same footprint and mounting, but the coil voltage must match the control circuit."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT6016-1AR61","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT6016-1AR61 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}