{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT6016-1BW41","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT6016-1BW41","canonicalUrl":"https://aoctrl.com/siemens/3RT6016-1BW41","factsUrl":"https://aoctrl.com/api/mcp/products/3RT6016-1BW41","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS power contactor, size S00, 48 V DC coil, screw terminals, 13 kW at 400 V AC-3, 45 x 57.5 x 73 mm.","salesMarkdown":"The 3RT6016-1BW41 is a Siemens SIRIUS size S00 power contactor with a 48 V DC coil, rated for switching three-phase motors up to 13 kW at 400 V AC-3 (the standard motor-duty category per IEC 60947-4-1). The 48 V DC coil draws 6 A at 24 V and 1 A at 110 V, so the control transformer or DC supply must be sized for the inrush, not just the hold-in current. The S00 frame is 45 mm wide, 57.5 mm tall, 73 mm deep. ## AC-3 motor power and switching frequency At AC-3 duty the contactor is rated for 7.5 kW at 230 V, 13 kW at 400 V, and 22 kW at 690 V — all at 60 °C ambient. The maximum switching rate at AC-3 is 750 operations per hour, which covers most pump, fan, and conveyor cycling. For resistive loads (AC-1) the rate climbs to 1 000 1/h, and for DC switching the coil circuit handles up to 10 000 1/h. RoHS compliance date is May 1, 2012, so it meets current EU substance restrictions.","metaTitle":"Siemens 3RT6016-1BW41 SIRIUS Contactor, 48 V DC Coil","metaDescription":"Siemens SIRIUS 3RT6016-1BW41 power contactor, size S00, 48 V DC coil, 13 kW at 400 V AC-3. Current production. Screw terminals, DIN rail mount.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"73 mm","Width":"45 mm","at DC":"10 000 1/h","title":"3RT6016-1BW41","Height":"57.5 mm","Rated Value":"48 V","description":"Contactor DC 48 V AC3 4 kW 400 V AUX contacts: 1 NO 3-pole, size S00 screw terminal","During Storage":"-55 ... +80 °C","at AC-1 maximum":"1 000 1/h","at AC-3 maximum":"750 1/h","at AC-4 maximum":"250 1/h","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 50022","at AC-3e maximum":"750 1/h","Mounting Position":"+/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface","Size Of Contactor":"S00","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), 2x 4 mm²","Product Brand Name":"SIRIUS","Degree Of Pollution":"3","Product Designation":"Power contactor","at 24 V rated value":"6 A","Of Contactor Typical":"30 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"10 A","at 400 V rated value":"3 A","at 690 V rated value":"1 A","Side-By-Side Mounting":"Yes","For Main Current Circuit":"screw-type terminals","at AC-3 rated value maximum":"690 V","at AC-3e rated value maximum":"690 V","Substance Prohibitance (Date)":"05/01/2012","at 40 °C minimum permissible":"4 mm²","at 60 °C minimum permissible":"2.5 mm²","Insulation Voltage Rated Value":"690 V","at 230 V at 60 °C rated value":"7.5 kW","at 400 V at 60 °C rated value":"13 kW","at 690 V at 60 °C rated value":"22 kW","for AWG cables for main contacts":"2x (20 ... 16), 2x (18 ... 14), 2x 12","For Auxiliary And Control Circuit":"screw-type terminals","Product Extension Auxiliary Switch":"Yes","With Type Of Assignment 2 Required":"gL/gG LV HRC 3NA, DIAZED 5SB, NEOZED 5SE: 20 A","closing power of magnet coil at DC":"4 W","holding power of magnet coil at DC":"4 W","Surge Voltage Resistance Rated Value":"6 kV","With Type Of Coordination 1 Required":"gL/gG LV HRC 3NA, DIAZED 5SB, NEOZED 5SE: 35 A","operational current at AC-12 maximum":"10 A","for AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 2x 12","number of NC contacts for main contacts":"0","number of NO contacts for main contacts":"3","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","at ambient temperature 40 °C rated value":"22 A","at ambient temperature 60 °C rated value":"20 A","Type Of Voltage Of The Control Supply Voltage":"DC","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Required Spacing With Side-By-Side Mounting At The Side":"0 mm","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","number of NC contacts for auxiliary contacts instantaneous contact":"0","number of NO contacts for auxiliary contacts instantaneous contact":"1"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/5203460ffeb1e1549876f9b57593f9e8.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=579898&mlfb=3RT6016-1BW41"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT6016-1BW41","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT6016-1BW41 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}