{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT6017-1AH02","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT6017-1AH02","canonicalUrl":"https://aoctrl.com/siemens/3RT6017-1AH02","factsUrl":"https://aoctrl.com/api/mcp/products/3RT6017-1AH02","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS power contactor, Size S00, screw terminals, 48 V 50/60 Hz coil, 13 kW at 400 V 60°C, screw and snap-on DIN rail mount.","salesMarkdown":"Its coil pulls in at 48 V, 50/60 Hz, making it a straight match for panels with a 48 V control transformer — common in older European installations or systems where 24 VDC isn't the standard. Rated for motor duty, it handles 13 kW at 400 V and 60 °C ambient, and up to 22 kW at 690 V at the same temperature. That 60 °C rating matters out here in the grease — a contactor near a hot motor or inside a crowded panel sees real heat, not the ideal 40 °C lab number. The 400 V figure is the one most European line feeds will hit. The AC-3 and AC-3e switching frequency maxes at 750 operations per hour, which covers most start-stop conveyor and pump cycles. If you're cycling faster than that — say a rapid-reversing application — step up to the AC-4 rating of 250 ops/h. The contactor measures 45 mm wide, 57.5 mm tall, and 73 mm deep — a compact footprint that fits tightly on a DIN rail alongside other S00 devices. Fastening is screw-and-snap-on onto 35 mm rail per DIN EN 50022, so it clips in place without tools and stays put with the screw for vibration resistance. Mounting position is flexible: it can sit flat on a vertical surface, rotate ±180°, or tilt ±22.5° forward or back. That helps when you're squeezing it into a tight gland-plate layout or an angled sub-panel. Terminals accept 2x 0.5 to 2.5 mm² solid or stranded, or 2x 4 mm² — enough for the motor leads on a 13 kW load. At 60 °C ambient, the minimum permissible conductor is 2.5 mm²; at 40 °C it drops to 4 mm². That's a real-world derating factor when the panel is near the process heat.","metaTitle":"Siemens 3RT6017-1AH02 SIRIUS Contactor, 48 V Coil","metaDescription":"Siemens 3RT6017-1AH02 SIRIUS power contactor, Size S00, 48 V 50/60 Hz coil. Rated 13 kW at 400 V 60°C. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"73 mm","Width":"45 mm","at AC":"10 000 1/h","Height":"57.5 mm","at 50 Hz":"0.25","at 60 Hz":"0.25","During Storage":"-55 ... +80 °C","at AC-1 maximum":"1 000 1/h","at AC-3 maximum":"750 1/h","at AC-4 maximum":"250 1/h","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Fastening Method":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","at AC-3e maximum":"750 1/h","Mounting Position":"+/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface","Size Of Contactor":"S00","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), 2x 4 mm²","Product Brand Name":"SIRIUS","Degree Of Pollution":"3","Product Designation":"Power contactor","at 24 V rated value":"6 A","Of Contactor Typical":"30 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"10 A","at 400 V rated value":"3 A","at 50 Hz rated value":"48 V","at 60 Hz rated value":"48 V","at 690 V rated value":"1 A","Side-By-Side Mounting":"Yes","For Main Current Circuit":"screw-type terminals","at AC-3 rated value maximum":"690 V","at AC-3e rated value maximum":"690 V","Substance Prohibitance (Date)":"05/01/2012","at 40 °C minimum permissible":"4 mm²","at 60 °C minimum permissible":"2.5 mm²","Insulation Voltage Rated Value":"690 V","at 230 V at 60 °C rated value":"7.5 kW","at 400 V at 60 °C rated value":"13 kW","at 690 V at 60 °C rated value":"22 kW","at AWG cables for main contacts":"2x (20 ... 16), 2x (18 ... 14), 2x 12","For Auxiliary And Control Circuit":"screw-type terminals","Product Extension Auxiliary Switch":"Yes","With Type Of Assignment 2 Required":"gL/gG LV HRC 3NA, DIAZED 5SB, NEOZED 5SE: 20 A","Surge Voltage Resistance Rated Value":"6 kV","With Type Of Coordination 1 Required":"gL/gG LV HRC 3NA, DIAZED 5SB, NEOZED 5SE: 35 A","at AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 2x 12","operational current at AC-12 maximum":"10 A","number of NC contacts for main contacts":"0","number of NO contacts for main contacts":"3","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","at ambient temperature 40 °C rated value":"22 A","at ambient temperature 60 °C rated value":"20 A","Type Of Voltage Of The Control Supply Voltage":"AC","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Required Spacing With Side-By-Side Mounting At The Side":"0 mm","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","number of NC contacts for auxiliary contacts instantaneous contact":"1","number of NO contacts for auxiliary contacts instantaneous contact":"0"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/3ebe8580d1996f9ae33eafdd70caa7d6.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=579911&mlfb=3RT6017-1AH02","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT6017-1AH02/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT6017-1AH02","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT6017-1AH02 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}