{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT6017-1AR61","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT6017-1AR61","canonicalUrl":"https://aoctrl.com/siemens/3RT6017-1AR61","factsUrl":"https://aoctrl.com/api/mcp/products/3RT6017-1AR61","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RT6017-1AR61, Size S00 power contactor, screw-type terminals, 45 mm width, 13 kW at 400 V 60 °C, AC-3 duty.","salesMarkdown":"Rated for AC-3 motor duty at 400 V and 60 °C ambient, it handles 13 kW — enough for a medium pump, fan, or conveyor drive in a continuous-process mill. The 690 V insulation voltage (rated value) keeps it comfortable in 400 V or 480 V systems without derating creepage distances. ## Motor ratings that survive the steam and the chemicals At 60 °C ambient — common inside a non-ventilated MCC bucket or a pulp-mill motor control centre — the contactor still delivers 13 kW at 400 V and 22 kW at 690 V. That's not a best-case number at 40 °C; it's the rating that matters when the panel is hot and the load is continuous. Maximum mechanical switching rate is 10 000 operations per hour, but that's the mechanism limit. For AC-3 motor starts the practical ceiling is 750 1/h, and for AC-4 (plugging / inching) it drops to 250 1/h. If your application cycles faster than that — say a high-speed indexing conveyor — step up to a larger frame or a dedicated reversing contactor pair. The 24 V DC coil draws 6 A inrush (rated value), settling to a holding current around 0.25 A at 50/60 Hz. At 230 V the coil draw is 10 A inrush. Verify your control transformer and fuse sizing: a 24 V DC supply feeding multiple contactors needs headroom for simultaneous pickup.","metaTitle":"Siemens 3RT6017-1AR61 SIRIUS Contactor, 13 kW at 400 V, Size","metaDescription":"Siemens 3RT6017-1AR61 SIRIUS power contactor, Size S00, rated 13 kW at 400 V 60 °C. Screw terminals, 45 mm wide, DIN rail mount. Active production, sourced to order. Request RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"73 mm","Width":"45 mm","at AC":"10 000 1/h","Height":"57.5 mm","at 50 Hz":"0.25","at 60 Hz":"0.25","During Storage":"-55 ... +80 °C","at AC-1 maximum":"1 000 1/h","at AC-3 maximum":"750 1/h","at AC-4 maximum":"250 1/h","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 50022","at AC-3e maximum":"750 1/h","Mounting Position":"+/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface","Size Of Contactor":"S00","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), 2x 4 mm²","Product Brand Name":"SIRIUS","Degree Of Pollution":"3","Product Designation":"Power contactor","at 24 V rated value":"6 A","Of Contactor Typical":"30 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"10 A","at 400 V rated value":"3 A","at 50 Hz rated value":"400 V","at 60 Hz rated value":"440 V","at 690 V rated value":"1 A","Side-By-Side Mounting":"Yes","For Main Current Circuit":"screw-type terminals","at AC-3 rated value maximum":"690 V","at AC-3e rated value maximum":"690 V","Substance Prohibitance (Date)":"05/01/2012","at 40 °C minimum permissible":"4 mm²","at 60 °C minimum permissible":"2.5 mm²","Insulation Voltage Rated Value":"690 V","at 230 V at 60 °C rated value":"7.5 kW","at 400 V at 60 °C rated value":"13 kW","at 690 V at 60 °C rated value":"22 kW","for AWG cables for main contacts":"2x (20 ... 16), 2x (18 ... 14), 2x 12","For Auxiliary And Control Circuit":"screw-type terminals","Product Extension Auxiliary Switch":"Yes","With Type Of Assignment 2 Required":"gL/gG LV HRC 3NA, DIAZED 5SB, NEOZED 5SE: 20 A","Surge Voltage Resistance Rated Value":"6 kV","With Type Of Coordination 1 Required":"gL/gG LV HRC 3NA, DIAZED 5SB, NEOZED 5SE: 35 A","operational current at AC-12 maximum":"10 A","for AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 2x 12","number of NC contacts for main contacts":"0","number of NO contacts for main contacts":"3","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","at ambient temperature 40 °C rated value":"22 A","at ambient temperature 60 °C rated value":"20 A","Type Of Voltage Of The Control Supply Voltage":"AC","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Required Spacing With Side-By-Side Mounting At The Side":"0 mm","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","number of NC contacts for auxiliary contacts instantaneous contact":"0","number of NO contacts for auxiliary contacts instantaneous contact":"1"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/9dfd162428433fc0c0db13ee679e8914.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=579918&mlfb=3RT6017-1AR61","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT6017-1AR61/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3RT6017-1AR61?","answer":"Submit an RFQ through this listing. Pricing and stock are confirmed at quote time through our independent distribution network — we source to order against your BOM line."},{"question":"Will 3RT6017-1AR61 drop into a panel specified around 3RT6017-1KF42 without rewiring?","answer":"Yes — both are Size S00 contactors with the same 45 mm width and DIN-rail mounting footprint. The 3RT6017-1AR61 uses screw-type terminals; the 1KF42 uses spring-cage terminals. The physical layout and rail position are identical, so no panel rework is needed. The wiring method differs (screw vs spring), but the terminals accept the same conductor sizes."},{"question":"What compliance documentation does Siemens provide for 3RT6017-1AR61?","answer":"The contactor carries RoHS compliance dated 2012-05-01 and is designed to meet IEC 60947-4-1. Siemens provides a declaration of conformity, material declarations, and UL/CSA file information through their standard documentation portal."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT6017-1AR61","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT6017-1AR61 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}