{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT6023-1AR60","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT6023-1AR60","canonicalUrl":"https://aoctrl.com/siemens/3RT6023-1AR60","factsUrl":"https://aoctrl.com/api/mcp/products/3RT6023-1AR60","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS power contactor, Size S0, 3RT6023-1AR60, 24 VDC coil, screw terminals, 23 kW at 400 V AC-3, 45 mm wide.","salesMarkdown":"The Siemens 3RT6023-1AR60 is a SIRIUS Size S0 power contactor with a 24 VDC coil that draws 6 A at rated voltage — that's the coil you need to match to your 24 VDC control supply, and 6 A is the inrush you budget for in the PLC output card or interposing relay. Rated for motor switching in AC-3 duty, it handles 23 kW at 400 V and 40 kW at 690 V — both at 60 °C ambient, so no derating headache in a warm cabinet. The 690 V figure means it's comfortable on 480 V systems as well, with headroom. Screw-type terminals on the main circuit accept up to 10 mm² at 60 °C, and the control circuit takes 2x 0.5–2.5 mm². That's solid for panel wire up to #8 AWG — no crimping fuss if you're landing ferruled stranded. That's useful when you're wedging it into a crowded gland plate or retrofitting an old panel where the rail isn't perfectly level. At 45 mm wide and 97 mm deep, it's a standard S0 footprint.","metaTitle":"Siemens 3RT6023-1AR60 SIRIUS Power Contactor, 24 VDC Coil","metaDescription":"Siemens 3RT6023-1AR60 SIRIUS power contactor, Size S0, 24 VDC coil draws 6 A. Rated 23 kW at 400 V AC-3. Screw terminals, DIN-rail mount.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"97 mm","Width":"45 mm","at AC":"5 000 1/h","Height":"85 mm","at 50 Hz":"0.25","During Storage":"-55 ... +80 °C","at AC-1 maximum":"1 000 1/h","at AC-3 maximum":"1 000 1/h","at AC-4 maximum":"300 1/h","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 50022","at AC-3e maximum":"1 000 1/h","Mounting Position":"+/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface","Size Of Contactor":"S0","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Product Brand Name":"SIRIUS","Degree Of Pollution":"3","Product Designation":"Power contactor","at 24 V rated value":"6 A","Of Contactor Typical":"10 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"10 A","at 400 V rated value":"3 A","at 50 Hz rated value":"400 V","at 60 Hz rated value":"440 V","at 690 V rated value":"1 A","Side-By-Side Mounting":"Yes","For Main Current Circuit":"screw-type terminals","at AC-3 rated value maximum":"690 V","at AC-3e rated value maximum":"690 V","Substance Prohibitance (Date)":"05/01/2012","at 40 °C minimum permissible":"10 mm²","at 60 °C minimum permissible":"10 mm²","Insulation Voltage Rated Value":"690 V","at 230 V at 60 °C rated value":"13.3 kW","at 400 V at 60 °C rated value":"23 kW","at 690 V at 60 °C rated value":"40 kW","for AWG cables for main contacts":"2x (16 ... 12), 2x (14 ... 8)","For Auxiliary And Control Circuit":"screw-type terminals","Product Extension Auxiliary Switch":"Yes","With Type Of Assignment 2 Required":"gL/gG LV HRC 3NA, DIAZED 5SB, NEOZED 5SE: 25 A","Surge Voltage Resistance Rated Value":"6 kV","With Type Of Coordination 1 Required":"gL/gG LV HRC 3NA, DIAZED 5SB, NEOZED 5SE: 63 A","operational current at AC-12 maximum":"10 A","for AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14)","number of NC contacts for main contacts":"0","number of NO contacts for main contacts":"3","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","at ambient temperature 40 °C rated value":"40 A","at ambient temperature 60 °C rated value":"35 A","Type Of Voltage Of The Control Supply Voltage":"AC","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Required Spacing With Side-By-Side Mounting At The Side":"0 mm","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","number of NC contacts for auxiliary contacts instantaneous contact":"1","number of NO contacts for auxiliary contacts instantaneous contact":"1"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/cb88299618b64c10f6f1269294e35212.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=580147&mlfb=3RT6023-1AR60","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT6023-1AR60/alternatives.json"},"ai":{"faq":[{"question":"What is the mounting type for 3RT6023-1AR60?","answer":"Screw and snap-on mounting onto 35 mm DIN rail per DIN EN 50022. Mounting position allows ±180° rotation and ±22.5° tilt on vertical surfaces."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT6023-1AR60","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT6023-1AR60 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}