{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT7014-1AQ02","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT7014-1AQ02","canonicalUrl":"https://aoctrl.com/siemens/3RT7014-1AQ02","factsUrl":"https://aoctrl.com/api/mcp/products/3RT7014-1AQ02","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RT7014-1AQ02, size S00 contactor, 3-pole, 3 NO main contacts, AC-3 rated 6 A at 230 V, 3 A at 400 V, 1 A at 690 V, screw terminals, IP20, snap-on DIN rail.","salesMarkdown":"The Siemens 3RT7014-1AQ02 is a size S00 contactor with three normally-open main contacts, rated for AC-3 duty at 6 A at 230 V, 3 A at 400 V, and 1 A at 690 V. The AC-3 rating means it's designed for switching squirrel-cage motors — the most common induction motor load in industrial panels — up to those currents. The 690 V rating covers 480 V and 575 V line supplies common in North American and marine installations. The control coil is AC-powered. Closing power draw is 0.8 W DC; holding power drops to 0.27 W DC. That low holding power means the coil runs cool in a sealed panel — less heat to manage in a crowded DIN-rail row. The S00 footprint — 45 mm wide, 57.5 mm tall, 72 mm deep — fits standard 45 mm-wide DIN-rail slots. IP20 on the front and at the terminals — finger-safe for a closed panel, but not washdown-rated. Keep it inside a cabinet. Insulation voltage rated 690 V; surge voltage resistance 6 kV. For type 2 coordination (no-weld after fault), the recommended backup fuse is a 20 A gL/gG NH 3NA. For type 1 coordination (allow weld but clear fault), a 35 A gL/gG NH 3NA. That's the fuse size the panel designer needs to spec upstream. Maximum switching frequency: 750 operations per hour at AC-3, 250 at AC-4. AC-4 is plugging/reversing duty — harder on the contacts, so the lower rate reflects that. If your application cycles faster than 250/h under reversing loads, this contactor will overheat.","metaTitle":"Siemens 3RT7014-1AQ02 Contactor, S00, 3-Pole, 6 A at 230 V","metaDescription":"Siemens 3RT7014-1AQ02 contactor, size S00, 3 NO main contacts, 6 A at 230 V AC-3, 690 V insulation, IP20, screw terminals, current production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"72 mm","Width":"45 mm","Height":"57.5 mm","at 50 Hz":"0.27","at 60 Hz":"0.27","On The Front":"IP20","During Storage":"-25 ... +70 °C","Of The Terminal":"IP20","at AC-3 maximum":"750 1/h","at AC-4 maximum":"250 1/h","lifecycle_stage":"current","During Operation":"-10 ... +55 °C","Fastening Method":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Mounting Position":"+/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface","Size Of Contactor":"S00","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Degree Of Pollution":"3","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 50 Hz rated value":"380 V","at 60 Hz rated value":"380 V","at 690 V rated value":"1 A","Side-By-Side Mounting":"Yes","For Main Current Circuit":"screw-type terminals","Insulation Voltage Rated Value":"690 V","For Auxiliary And Control Circuit":"screw-type terminals","Product Extension Auxiliary Switch":"Yes","With Type Of Assignment 2 Required":"gL/gG NH 3NA: 20 A","closing power of magnet coil at DC":"0.8 W","holding power of magnet coil at DC":"0.27 W","Surge Voltage Resistance Rated Value":"6 kV","With Type Of Coordination 1 Required":"gL/gG NH 3NA: 35 A","shock resistance with sine pulse at AC":"9.8g / 5 ms, 5.9g / 10 ms","number of NC contacts for main contacts":"0","number of NO contacts for main contacts":"3","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Contact Reliability Of Auxiliary Contacts":"acceptability for PLC control (17 V, 5 mA)","Type Of Voltage Of The Control Supply Voltage":"AC","operating voltage at AC-3 rated value maximum":"690 V","operational current at DC-13 at 220 V rated value":"0.3 A","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Required Spacing With Side-By-Side Mounting At The Side":"0 mm","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","number of NC contacts for auxiliary contacts instantaneous contact":"1","number of NO contacts for auxiliary contacts instantaneous contact":"0","Connectable Conductor Cross-Section For Main Contacts Finely Stranded With Core End Processing":"2.5 mm²","Connectable Conductor Cross-Section For Auxiliary Contacts Finely Stranded With Core End Processing":"0.5 ... 2.5 mm²"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1533851&mlfb=3RT7014-1AQ02","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT7014-1AQ02/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3RT7014-1AQ02?","answer":"Submit an RFQ through this listing. The part is sourced to order via independent distribution; pricing and stock are confirmed at quote time."},{"question":"Will 3RT7014-1AQ02 drop into a panel that was specified around 3RT6015-1AF02 without rewiring?","answer":"Both are size S00 contactors with the same 45 mm width and screw-terminal main/auxiliary connections, so the mechanical footprint and terminal layout are compatible. The 3RT7014-1AQ02 is AC-coil only; if the original panel used a DC-coil variant, the control circuit wiring differs and the coil supply must be verified."},{"question":"What is 3RT7014-1AQ02's listed depth (72 mm) on this component line?","answer":"The depth is 72 mm. That's the dimension from the DIN-rail mounting surface to the front of the contactor — important for enclosure depth clearance."},{"question":"What is 3RT7014-1AQ02's listed width (45 mm) on this component line?","answer":"The width is 45 mm, which is the standard single-module width for size S00 contactors on 35 mm DIN rail."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT7014-1AQ02","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT7014-1AQ02 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}