{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT7014-1AV01","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT7014-1AV01","canonicalUrl":"https://aoctrl.com/siemens/3RT7014-1AV01","factsUrl":"https://aoctrl.com/api/mcp/products/3RT7014-1AV01","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RT7014-1AV01, size S00 contactor, 3-pole, AC control supply, screw terminals, 45 mm width, IP20 front.","salesMarkdown":"## What It Is & Key Ratings It has three main poles for switching three-phase loads and an AC-operated magnet coil. The control supply voltage type is AC, so it is intended for panels with an AC control transformer or direct line-voltage control circuits. Rated operational current in AC-3 duty (squirrel-cage motors) is 6 A at 230 V, 3 A at 400 V, and 1 A at 690 V. These ratings define the motor load it can switch: up to roughly 2.2 kW at 400 V three-phase. The IP20 protection on the front and terminals means it requires an enclosure for dust and moisture protection, typical for panel-mounted gear. Side-by-side mounting is permitted, so multiple contactors can be ganged without spacing. Dimensions are 45 mm wide, 57.5 mm high, and 72 mm deep — the 45 mm width matches the standard S00 footprint, fitting alongside other SIRIUS components on the rail. The screw-type terminals on both main and auxiliary circuits accept 2x (0.5 to 1.5 mm²) solid/stranded or 2x (0.75 to 2.5 mm²) finely stranded with ferrule. ## Coordination & Auxiliary Contacts For type of coordination 1 (no damage to the contactor under short circuit), the required fuse is gL/gG 35 A. For type of coordination 2 (contactor remains usable after clearing), the fuse is gL/gG 20 A. This matters when designing a motor branch circuit for selectivity or restart capability after a fault. The product extension for auxiliary switches is available, meaning add-on blocks can be snapped on for additional N.O./N.C. contacts. The main contacts are 3 N.O. with no N.C. main contacts. Coil power consumption is 0.8 W closing and 0.27 W holding at DC, which is low enough for direct PLC output drive with a suitable interposing relay. The magnet coil closing power at DC is 0.8 W, holding power 0.27 W. ## Environmental & Mechanical Limits The contactor withstands sine-pulse shock of 9.8g at 5 ms and 5.9g at 10 ms, adequate for most industrial machinery but not extreme mobile equipment. Maximum switching frequency is 750 operations per hour in AC-3 and 250 in AC-4.","metaTitle":"Siemens 3RT7014-1AV01 SIRIUS Contactor, 3-Pole, AC Coil, 690","metaDescription":"Siemens 3RT7014-1AV01 SIRIUS contactor, size S00, 3-pole, AC control voltage, rated operational current 6A at 230V AC-3, 690V insulation voltage, IP20, current lifecycle stage.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"72 mm","Width":"45 mm","Height":"57.5 mm","at 50 Hz":"0.27","at 60 Hz":"0.27","On The Front":"IP20","During Storage":"-25 ... +70 °C","Of The Terminal":"IP20","at AC-3 maximum":"750 1/h","at AC-4 maximum":"250 1/h","lifecycle_stage":"current","During Operation":"-10 ... +55 °C","Fastening Method":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Mounting Position":"+/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface","Size Of Contactor":"S00","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Degree Of Pollution":"3","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 50 Hz rated value":"400 V","at 60 Hz rated value":"400 V","at 690 V rated value":"1 A","Side-By-Side Mounting":"Yes","For Main Current Circuit":"screw-type terminals","Insulation Voltage Rated Value":"690 V","For Auxiliary And Control Circuit":"screw-type terminals","Product Extension Auxiliary Switch":"Yes","With Type Of Assignment 2 Required":"gL/gG NH 3NA: 20 A","closing power of magnet coil at DC":"0.8 W","holding power of magnet coil at DC":"0.27 W","Surge Voltage Resistance Rated Value":"6 kV","With Type Of Coordination 1 Required":"gL/gG NH 3NA: 35 A","shock resistance with sine pulse at AC":"9.8g / 5 ms, 5.9g / 10 ms","number of NC contacts for main contacts":"0","number of NO contacts for main contacts":"3","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Contact Reliability Of Auxiliary Contacts":"acceptability for PLC control (17 V, 5 mA)","Type Of Voltage Of The Control Supply Voltage":"AC","operating voltage at AC-3 rated value maximum":"690 V","operational current at DC-13 at 220 V rated value":"0.3 A","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Required Spacing With Side-By-Side Mounting At The Side":"0 mm","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","number of NC contacts for auxiliary contacts instantaneous contact":"0","number of NO contacts for auxiliary contacts instantaneous contact":"1","Connectable Conductor Cross-Section For Main Contacts Finely Stranded With Core End Processing":"2.5 mm²","Connectable Conductor Cross-Section For Auxiliary Contacts Finely Stranded With Core End Processing":"0.5 ... 2.5 mm²"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1533853&mlfb=3RT7014-1AV01","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT7014-1AV01/alternatives.json"},"ai":{"faq":[{"question":"What is the closest functional second-source to the 3RT7014-1AV01?","answer":"Within the same SIRIUS S00 family, the 3RT7014-1AN22 is a close peer. The key difference is the control voltage type: the -1AV01 has an AC coil, while the -1AN22 uses a DC coil. For a panel already wired for AC control, the -1AV01 is the direct fit; swapping to a DC coil variant would require changing the control supply."},{"question":"Will the 3RT7014-1AV01 drop into a panel specified for the 3RT7014-1AN22 without rewiring?","answer":"Mechanically yes — both are S00 size with the same 45 mm width and DIN-rail mounting. Electrically no, unless the control circuit is AC. The -1AV01 requires an AC control supply; the -1AN22 requires DC. If the panel has a 24 VDC control bus, the -1AN22 is the correct choice."},{"question":"What compliance documentation is available for the 3RT7014-1AV01?","answer":"The contactor carries IP20 protection on front and terminals, a rated insulation voltage of 690 V, and surge voltage resistance of 6 kV. It is designed for pollution degree 3 environments. Standard Siemens documentation includes the CE declaration of conformity and RoHS/REACH compliance statements available through the manufacturer's support portal."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT7014-1AV01","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT7014-1AV01 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}