{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT7014-1AV02","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT7014-1AV02","canonicalUrl":"https://aoctrl.com/siemens/3RT7014-1AV02","factsUrl":"https://aoctrl.com/api/mcp/products/3RT7014-1AV02","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RT7014-1AV02, Size S00 contactor, 3-pole, AC coil, screw terminals, 6 A at 230 V AC-3, 45 mm wide, IP20.","salesMarkdown":"## Siemens 3RT7014-1AV02 — S00 Contactor, AC Coil, 3-Pole Rated operational current in AC-3 duty is 6 A at 230 V, 3 A at 400 V, and 1 A at 690 V — that's the motor-switching current for squirrel-cage motors. The AC-3 switching frequency maxes out at 750 operations per hour; for AC-4 (inching/plugging duty) it's 250 per hour, so keep that in mind if the application does frequent reversing. Coil draws 0.8 W on pickup and holds at 0.27 W DC — that's the holding power once the armature seats. The AC control voltage means you'll need to verify the coil matches your control transformer tap; no DC conversion inside this unit. Side-by-side mounting is allowed, so no derating for zero-gap stacking. That helps when the gland plate or busbar layout forces an odd angle. Terminals are screw-type for both main and auxiliary circuits, accepting 2x (0.5…1.5 mm²) solid/stranded or 2x (0.75…2.5 mm²) with ferrules. Pollution degree 3 — suitable for control panels in industrial environments where some conductive dust is present. ## Protection and Coordination For Type 2 coordination (contactor remains fully functional after a fault), use gL/gG 20 A. Both ratings call for NH 3NA fuses.","metaTitle":"Siemens 3RT7014-1AV02 Contactor, S00, 3-pole, AC Coil, 6 A a","metaDescription":"Siemens 3RT7014-1AV02 S00 contactor, 3-pole, AC coil, 6 A rated at 230 V. Active production. DIN rail mount. Available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"72 mm","Width":"45 mm","Height":"57.5 mm","at 50 Hz":"0.27","at 60 Hz":"0.27","On The Front":"IP20","During Storage":"-25 ... +70 °C","Of The Terminal":"IP20","at AC-3 maximum":"750 1/h","at AC-4 maximum":"250 1/h","lifecycle_stage":"current","During Operation":"-10 ... +55 °C","Fastening Method":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Mounting Position":"+/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface","Size Of Contactor":"S00","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Degree Of Pollution":"3","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 50 Hz rated value":"400 V","at 60 Hz rated value":"400 V","at 690 V rated value":"1 A","Side-By-Side Mounting":"Yes","For Main Current Circuit":"screw-type terminals","Insulation Voltage Rated Value":"690 V","For Auxiliary And Control Circuit":"screw-type terminals","Product Extension Auxiliary Switch":"Yes","With Type Of Assignment 2 Required":"gL/gG NH 3NA: 20 A","closing power of magnet coil at DC":"0.8 W","holding power of magnet coil at DC":"0.27 W","Surge Voltage Resistance Rated Value":"6 kV","With Type Of Coordination 1 Required":"gL/gG NH 3NA: 35 A","shock resistance with sine pulse at AC":"9.8g / 5 ms, 5.9g / 10 ms","number of NC contacts for main contacts":"0","number of NO contacts for main contacts":"3","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Contact Reliability Of Auxiliary Contacts":"acceptability for PLC control (17 V, 5 mA)","Type Of Voltage Of The Control Supply Voltage":"AC","operating voltage at AC-3 rated value maximum":"690 V","operational current at DC-13 at 220 V rated value":"0.3 A","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Required Spacing With Side-By-Side Mounting At The Side":"0 mm","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","number of NC contacts for auxiliary contacts instantaneous contact":"1","number of NO contacts for auxiliary contacts instantaneous contact":"0","Connectable Conductor Cross-Section For Main Contacts Finely Stranded With Core End Processing":"2.5 mm²","Connectable Conductor Cross-Section For Auxiliary Contacts Finely Stranded With Core End Processing":"0.5 ... 2.5 mm²"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1533854&mlfb=3RT7014-1AV02","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT7014-1AV02/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3RT7014-1AV02 and how do I get a price?","answer":"This part is sourced to order through independent distribution. Submit an RFQ for current availability and pricing — confirmed at quote time."},{"question":"What is 3RT7014-1AV02's depth and width?","answer":"Depth is 72 mm, width is 45 mm, height is 57.5 mm. It occupies a standard 45 mm DIN-rail slot."},{"question":"Will 3RT7014-1AV02 drop into a panel wired for a 3RT6018-1AB02?","answer":"Both are S00 frame contactors with the same 45 mm width and DIN-rail footprint, so the mechanical fit is the same. The key difference is the coil voltage — verify the 3RT7014-1AV02's AC coil matches your control voltage before swapping."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT7014-1AV02","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT7014-1AV02 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}