{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT7016-1AF01","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT7016-1AF01","canonicalUrl":"https://aoctrl.com/siemens/3RT7016-1AF01","factsUrl":"https://aoctrl.com/api/mcp/products/3RT7016-1AF01","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RT7016-1AF01, size S00 contactor, 3-pole, 110 V AC 50/60 Hz coil, screw-type terminals, 45 mm width.","salesMarkdown":"The 110 V AC coil draws 0.27 A at both 50 Hz and 60 Hz, with a closing power of 0.8 W DC and holding power of 0.27 W DC — low enough for direct PLC output drive in many cases, though the contact reliability spec (17 V, 5 mA) confirms it's rated for PLC-level auxiliary signals. The AC-3 motor switching current is 6 A at 230 V, 3 A at 400 V, and 1 A at 690 V. These are the numbers that govern real motor starts — not a higher resistive rating. The insulation voltage is rated 690 V, and surge voltage resistance is 6 kV, which covers standard 400 V line-to-line panels with margin. Maximum switching rate is 750 operations per hour under AC-3 and 250 per hour under AC-4 (plugging/inching). The contactor accepts 2x (0.5 to 1.5 mm²) solid or stranded, or 2x (0.75 to 2.5 mm²) finely stranded with ferrules — screw-type terminals on both main and auxiliary circuits. Fuse coordination: type 2 (no damage) requires a 20 A gL/gG fuse; type 1 (allow damage) uses 35 A. This matters for selectivity studies — the 20 A limit is the one to design around if you want full coordination downstream. The 45 mm width and 72 mm depth fit standard S00 footprint. Side-by-side mounting is permitted with no derating gap — useful for dense panels. Operating temperature is -10 to +55 °C; storage -25 to +70 °C. An auxiliary switch can be added via the product extension slot.","metaTitle":"Siemens 3RT7016-1AF01 Contactor, S00, 110 VAC Coil, 3-Pole","metaDescription":"Siemens 3RT7016-1AF01 contactor, size S00, 3-pole, 110 VAC 50/60 Hz coil. Rated 6 A at 230 V, 3 A at 400 V AC-3. Screw terminals, DIN rail mount. Current production.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"72 mm","Width":"45 mm","Height":"57.5 mm","at 50 Hz":"0.27","at 60 Hz":"0.27","On The Front":"IP20","During Storage":"-25 ... +70 °C","Of The Terminal":"IP20","at AC-3 maximum":"750 1/h","at AC-4 maximum":"250 1/h","lifecycle_stage":"current","During Operation":"-10 ... +55 °C","Fastening Method":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Mounting Position":"+/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface","Size Of Contactor":"S00","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Degree Of Pollution":"3","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 50 Hz rated value":"110 V","at 60 Hz rated value":"110 V","at 690 V rated value":"1 A","Side-By-Side Mounting":"Yes","For Main Current Circuit":"screw-type terminals","Insulation Voltage Rated Value":"690 V","For Auxiliary And Control Circuit":"screw-type terminals","Product Extension Auxiliary Switch":"Yes","With Type Of Assignment 2 Required":"gL/gG NH 3NA: 20 A","closing power of magnet coil at DC":"0.8 W","holding power of magnet coil at DC":"0.27 W","Surge Voltage Resistance Rated Value":"6 kV","With Type Of Coordination 1 Required":"gL/gG NH 3NA: 35 A","shock resistance with sine pulse at AC":"9.8g / 5 ms, 5.9g / 10 ms","number of NC contacts for main contacts":"0","number of NO contacts for main contacts":"3","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Contact Reliability Of Auxiliary Contacts":"acceptability for PLC control (17 V, 5 mA)","Type Of Voltage Of The Control Supply Voltage":"AC","operating voltage at AC-3 rated value maximum":"690 V","operational current at DC-13 at 220 V rated value":"0.3 A","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Required Spacing With Side-By-Side Mounting At The Side":"0 mm","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","number of NC contacts for auxiliary contacts instantaneous contact":"0","number of NO contacts for auxiliary contacts instantaneous contact":"1","Connectable Conductor Cross-Section For Main Contacts Finely Stranded With Core End Processing":"2.5 mm²","Connectable Conductor Cross-Section For Auxiliary Contacts Finely Stranded With Core End Processing":"0.5 ... 2.5 mm²"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1533859&mlfb=3RT7016-1AF01","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT7016-1AF01/alternatives.json"},"ai":{"faq":[{"question":"What is the closest functional alternative to 3RT7016-1AF01?","answer":"The 3RT1015-1AG61 is a functional peer in the same SIRIUS family, also size S00 with 3 poles. The key difference is the coil voltage: 3RT1015-1AG61 uses a 24 V AC coil, while 3RT7016-1AF01 uses 110 V AC. If your control voltage is 24 V AC, the 3RT1015-1AG61 is a direct drop-in; if you need 110 V AC, this part is the one. Both share the same 45 mm width, screw terminals, and AC-3 ratings."},{"question":"Will 3RT7016-1AF01 fit a panel designed for 3RT1015-1AG61?","answer":"Yes, mechanically it is a direct swap — same 45 mm width, same DIN rail mounting, same S00 size. The only difference is the coil voltage: 110 V AC versus 24 V AC. No rewiring of the power circuit is needed, but the control circuit must supply 110 V AC."},{"question":"What compliance documentation is available for this part?","answer":"As a standard Siemens SIRIUS product, it carries CE marking and is designed to IEC 60947-4-1. UL and CSA approvals are typical for the series. RoHS and REACH declarations are available from Siemens documentation. The surge voltage resistance of 6 kV and pollution degree 3 support industrial compliance."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT7016-1AF01","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT7016-1AF01 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}