{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT7016-1AP01","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT7016-1AP01","canonicalUrl":"https://aoctrl.com/siemens/3RT7016-1AP01","factsUrl":"https://aoctrl.com/api/mcp/products/3RT7016-1AP01","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RT7016-1AP01 contactor, size S00, 3-pole, 230 V AC 50/60 Hz coil, screw terminals, IP20, 45 mm width, 72 mm depth.","salesMarkdown":"The Siemens 3RT7016-1AP01 is a SIRIUS size S00 contactor with three main poles, a 230 V AC 50/60 Hz coil, and screw-type terminals for both main and control circuits. It's rated for AC-3 switching up to 690 V, with a 400 V AC-3 rating of 6 A and a 690 V AC-3 rating of 1 A — so it handles motor loads up to about 3 kW at 400 V three-phase, typical for small conveyors, pumps, or fans in a control panel. The coil draws 0.8 W on closing and holds at 0.27 W DC, which keeps the heat load low inside a crowded enclosure. Surge voltage resistance is rated at 6 kV, matching the insulation coordination for a 690 V insulated system (pollution degree 3). Operating temperature range is -10 to +55 °C, storage from -25 to +70 °C. ## Switching performance and protection Maximum switching frequency is 750 operations per hour under AC-3 duty (motor starting), and 250 ops/h under AC-4 (plugging/reversing). Shock resistance is 9.8g at 5 ms and 5.9g at 10 ms sine pulse — robust enough for most industrial machinery but not rated for continuous vibration environments like crushers or shakers without additional damping.","metaTitle":"Siemens 3RT7016-1AP01 Contactor, S00, 3-Pole, 230 VAC Coil,","metaDescription":"Siemens 3RT7016-1AP01 SIRIUS contactor, size S00, 3-pole, 230 V 50/60 Hz coil, rated 6 A at 400 V AC-3. Active production. IP20. DIN-rail mount. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"72 mm","Width":"45 mm","Height":"57.5 mm","at 50 Hz":"0.27","at 60 Hz":"0.27","On The Front":"IP20","During Storage":"-25 ... +70 °C","Of The Terminal":"IP20","at AC-3 maximum":"750 1/h","at AC-4 maximum":"250 1/h","lifecycle_stage":"current","During Operation":"-10 ... +55 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 50022","at AC-3e maximum":"750 1/h","Mounting Position":"+/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface","Size Of Contactor":"S00","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Degree Of Pollution":"3","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 50 Hz rated value":"230 V","at 60 Hz rated value":"230 V","at 690 V rated value":"1 A","Side-By-Side Mounting":"Yes","For Main Current Circuit":"screw-type terminals","at AC-3 rated value maximum":"690 V","at AC-3e rated value maximum":"690 V","Insulation Voltage Rated Value":"690 V","For Auxiliary And Control Circuit":"screw-type terminals","Product Extension Auxiliary Switch":"Yes","With Type Of Assignment 2 Required":"gL/gG NH 3NA: 20 A","closing power of magnet coil at DC":"0.8 W","holding power of magnet coil at DC":"0.27 W","Surge Voltage Resistance Rated Value":"6 kV","With Type Of Coordination 1 Required":"gL/gG NH 3NA: 35 A","shock resistance with sine pulse at AC":"9.8g / 5 ms, 5.9g / 10 ms","number of NC contacts for main contacts":"0","number of NO contacts for main contacts":"3","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Contact Reliability Of Auxiliary Contacts":"acceptability for PLC control (17 V, 5 mA)","Type Of Voltage Of The Control Supply Voltage":"AC","operational current at DC-13 at 220 V rated value":"0.3 A","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Required Spacing With Side-By-Side Mounting At The Side":"0 mm","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","number of NC contacts for auxiliary contacts instantaneous contact":"0","number of NO contacts for auxiliary contacts instantaneous contact":"1","Connectable Conductor Cross-Section For Main Contacts Finely Stranded With Core End Processing":"2.5 mm²","Connectable Conductor Cross-Section For Auxiliary Contacts Finely Stranded With Core End Processing":"0.5 ... 2.5 mm²"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1533871&mlfb=3RT7016-1AP01","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT7016-1AP01/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3RT7016-1AP01?","answer":"Submit an RFQ through this listing. Pricing and stock are confirmed at quote time through independent distribution channels."},{"question":"Will 3RT7016-1AP01 drop into a panel specified around 3RT6017-1AF01 without rewiring?","answer":"Both are S00 frame contactors with the same 45 mm width and DIN-rail footprint, so the mechanical fit is identical. The 3RT7016-1AP01 uses a 230 V AC coil versus the 3RT6017-1AF01's coil voltage — verify the control circuit voltage before swapping. Terminal layout and screw-type connections are the same, so no rewiring of the main circuit is needed if the coil voltage matches."},{"question":"What is 3RT7016-1AP01's listed depth?","answer":"72 mm."},{"question":"What is 3RT7016-1AP01's listed width?","answer":"45 mm."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT7016-1AP01","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT7016-1AP01 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}