{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT7016-1AV02","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT7016-1AV02","canonicalUrl":"https://aoctrl.com/siemens/3RT7016-1AV02","factsUrl":"https://aoctrl.com/api/mcp/products/3RT7016-1AV02","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RT7016-1AV02, size S00 contactor, 3-pole, AC-3 rated operational voltage 690 V, AC coil, screw-type terminals, IP20.","salesMarkdown":"The AC coil draws 0.8 W on closing and holds at 0.27 W, so the control transformer can be sized accordingly without overspending on VA. Rated operational current depends on the voltage: 6 A at 230 V, 3 A at 400 V, and 1 A at 690 V, all at 50/60 Hz. The maximum AC-3 operating voltage is 690 V, and the insulation voltage is also rated 690 V. Switching frequency is rated at 750 operations per hour under AC-3 duty and 250 per hour under AC-4. For a conveyor or pump cycling every few minutes, that's plenty of headroom. The size S00 footprint is 45 mm wide, 57.5 mm tall, and 72 mm deep — a compact block that leaves room for auxiliary contact blocks on the side. Side-by-side mounting is allowed with no derating gap, so you can pack several in a row on the same rail. This helps when fitting into tight enclosures or angled subpanels. All main and auxiliary/control circuit connections use screw-type terminals. The terminals accept 2x (0.5 to 1.5 mm²) solid or stranded, or 2x (0.75 to 2.5 mm²) finely stranded with ferrules. ## Protection and coordination For type of coordination 2 (limited damage after short circuit), use a gL/gG NH 3NA fuse rated 20 A. For type 1 (no damage to the contactor), the same fuse type at 35 A is specified. This tells the panel builder exactly what upstream protection to spec. Auxiliary contacts are rated for PLC-level signals: 17 V, 5 mA, so they can switch digital inputs directly without a separate interface relay.","metaTitle":"Siemens 3RT7016-1AV02 SIRIUS Contactor, Size S00, 3-Pole, 69","metaDescription":"Siemens 3RT7016-1AV02 SIRIUS contactor, size S00, 3-pole, AC-3 rated for 690 V. Screw terminals, AC coil, IP20. Current production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"72 mm","Width":"45 mm","Height":"57.5 mm","at 50 Hz":"0.27","at 60 Hz":"0.27","On The Front":"IP20","During Storage":"-25 ... +70 °C","Of The Terminal":"IP20","at AC-3 maximum":"750 1/h","at AC-4 maximum":"250 1/h","lifecycle_stage":"current","During Operation":"-10 ... +55 °C","Fastening Method":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Mounting Position":"+/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface","Size Of Contactor":"S00","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Degree Of Pollution":"3","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 50 Hz rated value":"400 V","at 60 Hz rated value":"400 V","at 690 V rated value":"1 A","Side-By-Side Mounting":"Yes","For Main Current Circuit":"screw-type terminals","Insulation Voltage Rated Value":"690 V","For Auxiliary And Control Circuit":"screw-type terminals","Product Extension Auxiliary Switch":"Yes","With Type Of Assignment 2 Required":"gL/gG NH 3NA: 20 A","closing power of magnet coil at DC":"0.8 W","holding power of magnet coil at DC":"0.27 W","Surge Voltage Resistance Rated Value":"6 kV","With Type Of Coordination 1 Required":"gL/gG NH 3NA: 35 A","shock resistance with sine pulse at AC":"9.8g / 5 ms, 5.9g / 10 ms","number of NC contacts for main contacts":"0","number of NO contacts for main contacts":"3","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Contact Reliability Of Auxiliary Contacts":"acceptability for PLC control (17 V, 5 mA)","Type Of Voltage Of The Control Supply Voltage":"AC","operating voltage at AC-3 rated value maximum":"690 V","operational current at DC-13 at 220 V rated value":"0.3 A","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Required Spacing With Side-By-Side Mounting At The Side":"0 mm","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","number of NC contacts for auxiliary contacts instantaneous contact":"1","number of NO contacts for auxiliary contacts instantaneous contact":"0","Connectable Conductor Cross-Section For Main Contacts Finely Stranded With Core End Processing":"2.5 mm²","Connectable Conductor Cross-Section For Auxiliary Contacts Finely Stranded With Core End Processing":"0.5 ... 2.5 mm²"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b398148ad3c46bf19053a392bc244494.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1533878&mlfb=3RT7016-1AV02","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT7016-1AV02/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for this contactor?","answer":"It is a size S00, 3-pole contactor with AC coil. AC-3 rated operational voltage max is 690 V. Rated currents: 6 A at 230 V, 3 A at 400 V, 1 A at 690 V. Switching frequency: 750 ops/h AC-3, 250 ops/h AC-4. Surge voltage resistance: 6 kV."},{"question":"What are the mounting dimensions?","answer":"Width 45 mm, height 57.5 mm, depth 72 mm. Mounts on 35 mm DIN rail per DIN EN 50022 via screw and snap-on. Side-by-side mounting is permitted."},{"question":"What type of terminals does it use?","answer":"Screw-type terminals for both main current circuit and auxiliary/control circuit. Accepts 2x (0.5 to 1.5 mm²) solid/stranded or 2x (0.75 to 2.5 mm²) finely stranded with ferrules."},{"question":"What upstream fuse protection is required?","answer":"For type of coordination 2: gL/gG NH 3NA 20 A. For type of coordination 1: gL/gG NH 3NA 35 A."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT7016-1AV02","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT7016-1AV02 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}