{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT7017-1AP02","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT7017-1AP02","canonicalUrl":"https://aoctrl.com/siemens/3RT7017-1AP02","factsUrl":"https://aoctrl.com/api/mcp/products/3RT7017-1AP02","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RT7017-1AP02, Size S00 contactor, 3-pole, 3 NO main contacts, AC coil, screw terminals, IP20 front and terminal, 45 mm width, 72 mm depth.","salesMarkdown":"## Siemens 3RT7017-1AP02 — S00 Contactor, AC Coil Rated for AC-1 duty at 6 A on 230 V, 3 A at 400 V, and 1 A at 690 V. That resistive-load curve covers heater banks, lighting, and transformer primary switching. For motor loads (AC-3), the maximum operating rate is 750 operations per hour; for AC-4 (plugging/reversing), it's 250 operations per hour — per the datasheet, those are the thermal limits, not the electrical endurance. The control supply voltage is AC; closing power of the magnet coil is 0.8 W, holding power drops to 0.27 W DC. That low holding power means the coil runs cool in continuous duty — relevant for densely packed panels where heat rise is a concern. Auxiliary contacts are rated for PLC-level signals: the datasheet specifies contact reliability at 17 V, 5 mA, so you can wire them directly to a 24 VDC digital input without worrying about oxide-film failures at dry-circuit levels. The product extension auxiliary switch option is available if you need additional N/O or N/C contacts beyond the main poles. ## Protection and Coordination For type of coordination 2 (no-weld protection), the required upstream fuse is a gL/gG NH 3NA: 20 A. For type 1 coordination (no-fire protection), it's 35 A. Terminals are screw-type for both main and auxiliary circuits, accepting 2 x (0.5 to 1.5 mm²) solid or stranded, or 2 x (0.75 to 2.5 mm²) finely stranded with ferrule. Strip length per standard practice — no special tooling required. IP20 on the front and at the terminal — that's touch-safe but not washdown-rated. Storage temperature spans -25 to +70 °C; the operating range is -10 to +55 °C. Shock resistance is 9.8g for 5 ms sine pulse, 5.9g for 10 ms — adequate for most industrial machinery but not for high-vibration mobile equipment without additional damping.","metaTitle":"Siemens 3RT7017-1AP02 Contactor, S00, 3-Pole, AC Coil, 6A at","metaDescription":"Siemens 3RT7017-1AP02 Size S00 contactor, 3-pole, 3 NO main contacts, AC coil. Rated 6A at 230V, 3A at 400V. IP20. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"72 mm","Width":"45 mm","Height":"57.5 mm","at 50 Hz":"0.27","at 60 Hz":"0.27","On The Front":"IP20","During Storage":"-25 ... +70 °C","Of The Terminal":"IP20","at AC-3 maximum":"750 1/h","at AC-4 maximum":"250 1/h","lifecycle_stage":"current","During Operation":"-10 ... +55 °C","Fastening Method":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Mounting Position":"+/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface","Size Of Contactor":"S00","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Degree Of Pollution":"3","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 50 Hz rated value":"230 V","at 60 Hz rated value":"230 V","at 690 V rated value":"1 A","Side-By-Side Mounting":"Yes","For Main Current Circuit":"screw-type terminals","Insulation Voltage Rated Value":"690 V","For Auxiliary And Control Circuit":"screw-type terminals","Product Extension Auxiliary Switch":"Yes","With Type Of Assignment 2 Required":"gL/gG NH 3NA: 20 A","closing power of magnet coil at DC":"0.8 W","holding power of magnet coil at DC":"0.27 W","Surge Voltage Resistance Rated Value":"6 kV","With Type Of Coordination 1 Required":"gL/gG NH 3NA: 35 A","shock resistance with sine pulse at AC":"9.8g / 5 ms, 5.9g / 10 ms","number of NC contacts for main contacts":"0","number of NO contacts for main contacts":"3","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Contact Reliability Of Auxiliary Contacts":"acceptability for PLC control (17 V, 5 mA)","Type Of Voltage Of The Control Supply Voltage":"AC","operating voltage at AC-3 rated value maximum":"690 V","operational current at DC-13 at 220 V rated value":"0.3 A","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Required Spacing With Side-By-Side Mounting At The Side":"0 mm","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","number of NC contacts for auxiliary contacts instantaneous contact":"1","number of NO contacts for auxiliary contacts instantaneous contact":"0","Connectable Conductor Cross-Section For Main Contacts Finely Stranded With Core End Processing":"2.5 mm²","Connectable Conductor Cross-Section For Auxiliary Contacts Finely Stranded With Core End Processing":"0.5 ... 2.5 mm²"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/913b45498dde85d05817382444985daf.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1533896&mlfb=3RT7017-1AP02","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT7017-1AP02/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for 3RT7017-1AP02?","answer":"Three-pole, three normally open main contacts, Size S00 frame. AC-1 rated 6 A at 230 V, 3 A at 400 V, 1 A at 690 V. AC coil with 0.8 W closing power, 0.27 W holding. IP20 front and terminal. Dimensions 45 mm wide, 72 mm deep, 57.5 mm tall."},{"question":"Where can I buy 3RT7017-1AP02?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."},{"question":"What compliance documentation is available for 3RT7017-1AP02?","answer":"The part carries standard Siemens industrial approvals per the SIRIUS series — typically UL, CSA, CE, and CCC for the 3RT family. Specific certs should be verified against the unit's date code and regional variant; the datasheet lists the applicable standards."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT7017-1AP02","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT7017-1AP02 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}