{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT7017-1AQ02","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT7017-1AQ02","canonicalUrl":"https://aoctrl.com/siemens/3RT7017-1AQ02","factsUrl":"https://aoctrl.com/api/mcp/products/3RT7017-1AQ02","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RT7017-1AQ02, size S00 contactor, 3-pole, AC control supply, screw terminals, 6 A rated operating current at 230 V, IP20 front and terminal protection.","salesMarkdown":"It carries 6 A at 230 V, 3 A at 400 V, and 1 A at 690 V — these are the operating currents that govern motor load selection, not a thermal continuous rating. The AC coil draws 0.8 W on closing and holds at 0.27 W DC, which keeps the control transformer load modest in a multi-contactor panel. The 3RT7017-1AQ02 uses screw-type terminals for both the main current circuit and the auxiliary/control circuit. The main terminals accept 2x (0.5 to 1.5 mm²) solid or stranded, or 2x (0.75 to 2.5 mm²) — fine for the 6 A load but note the limited wire range if you are paralleling feeds. Side-by-side mounting is permitted, so no spacing gap is required between contactors on the rail, which saves panel width. The auxiliary switch extension is supported (product extension auxiliary switch: Yes), so you can add a side-mount block for status feedback without changing the contactor footprint. The contact reliability is specified as acceptable for PLC control at 17 V, 5 mA — meaning the auxiliary contacts can switch low-level signals directly into a digital input card without a separate interposing relay. For type of coordination 2 (the stricter standard for motor starters), the required upstream fuse is a gL/gG NH 3NA rated 20 A. For type of coordination 1, the fuse can be 35 A. This matters when designing a motor branch circuit that must clear a fault without damaging the contactor — type 2 coordination keeps the contactor usable after a short circuit.","metaTitle":"Siemens 3RT7017-1AQ02 SIRIUS Contactor, 3-Pole, AC Coil, 6A","metaDescription":"Siemens 3RT7017-1AQ02 SIRIUS contactor, size S00, 3-pole, AC coil. Rated 6A at 230V, 3A at 400V. IP20. DIN rail mount. Current lifecycle stage. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"72 mm","Width":"45 mm","Height":"57.5 mm","at 50 Hz":"0.27","at 60 Hz":"0.27","On The Front":"IP20","During Storage":"-25 ... +70 °C","Of The Terminal":"IP20","at AC-3 maximum":"750 1/h","at AC-4 maximum":"250 1/h","lifecycle_stage":"current","During Operation":"-10 ... +55 °C","Fastening Method":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Mounting Position":"+/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface","Size Of Contactor":"S00","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Degree Of Pollution":"3","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 50 Hz rated value":"380 V","at 60 Hz rated value":"380 V","at 690 V rated value":"1 A","Side-By-Side Mounting":"Yes","For Main Current Circuit":"screw-type terminals","Insulation Voltage Rated Value":"690 V","For Auxiliary And Control Circuit":"screw-type terminals","Product Extension Auxiliary Switch":"Yes","With Type Of Assignment 2 Required":"gL/gG NH 3NA: 20 A","closing power of magnet coil at DC":"0.8 W","holding power of magnet coil at DC":"0.27 W","Surge Voltage Resistance Rated Value":"6 kV","With Type Of Coordination 1 Required":"gL/gG NH 3NA: 35 A","shock resistance with sine pulse at AC":"9.8g / 5 ms, 5.9g / 10 ms","number of NC contacts for main contacts":"0","number of NO contacts for main contacts":"3","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Contact Reliability Of Auxiliary Contacts":"acceptability for PLC control (17 V, 5 mA)","Type Of Voltage Of The Control Supply Voltage":"AC","operating voltage at AC-3 rated value maximum":"690 V","operational current at DC-13 at 220 V rated value":"0.3 A","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Required Spacing With Side-By-Side Mounting At The Side":"0 mm","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","number of NC contacts for auxiliary contacts instantaneous contact":"1","number of NO contacts for auxiliary contacts instantaneous contact":"0","Connectable Conductor Cross-Section For Main Contacts Finely Stranded With Core End Processing":"2.5 mm²","Connectable Conductor Cross-Section For Auxiliary Contacts Finely Stranded With Core End Processing":"0.5 ... 2.5 mm²"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1533899&mlfb=3RT7017-1AQ02","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT7017-1AQ02/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT7017-1AQ02","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT7017-1AQ02 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}