{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT7036-1AH00","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT7036-1AH00","canonicalUrl":"https://aoctrl.com/siemens/3RT7036-1AH00","factsUrl":"https://aoctrl.com/api/mcp/products/3RT7036-1AH00","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS S2 contactor, 3RT7036-1AH00, 3-pole NO main contacts, AC-3 rated voltage 690 V, screw terminals, IP20 front, 55 mm width, 115 mm depth, 112 mm height.","salesMarkdown":"## Key Ratings & Fit The 3RT7036-1AH00: The contactor is size S2, 55 mm wide, 115 mm deep, 112 mm high. The front carries IP20 protection; the terminal area is IP00 — standard for panel-mount contactors where the enclosure provides the overall IP rating. Pollution degree 3, surge voltage resistance 6 kV. For a 3-pole contactor switching motor loads, the AC-3 rating to 690 V is the key spec — it governs the motor circuit it can handle. Coil holding power is 0.36 W DC; closing power is 0.79 W DC. Side-by-side mounting is permitted, which saves panel width on multi-contactor groups.","metaTitle":"Siemens 3RT7036-1AH00 Contactor, S2, 3-Pole AC-3, 690V","metaDescription":"Siemens 3RT7036-1AH00 S2 contactor, 3-pole NO main contacts, AC-3 rated to 690V. Active production. Screw terminals, DIN rail mount. IP20 front. Sourced to order. Request quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"115 mm","Width":"55 mm","title":"3RT7036-1AH00","Height":"112 mm","at 50 Hz":"0.36","at 60 Hz":"0.38","description":"Contactor AC-3 50A/22kW 400V 48 VAC, 50 Hz 3-pole, Size S2 Screw terminal","On The Front":"IP20","During Storage":"-25 ... +70 °C","Of The Terminal":"IP00","at AC-3 maximum":"800 1/h","at AC-4 maximum":"250 1/h","lifecycle_stage":"current","During Operation":"-10 ... +55 °C","Fastening Method":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Mounting Position":"+/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface","Size Of Contactor":"S2","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Degree Of Pollution":"3","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 50 Hz rated value":"42 V","at 690 V rated value":"1 A","Side-By-Side Mounting":"Yes","For Main Current Circuit":"screw-type terminals","Insulation Voltage Rated Value":"690 V","For Auxiliary And Control Circuit":"screw-type terminals","Product Extension Auxiliary Switch":"Yes","With Type Of Assignment 2 Required":"gL/gG NH 3NA: 80 A","closing power of magnet coil at DC":"0.79 W","holding power of magnet coil at DC":"0.36 W","Surge Voltage Resistance Rated Value":"6 kV","With Type Of Coordination 1 Required":"gL/gG NH 3NA: 160 A","shock resistance with sine pulse at AC":"15g / 5 ms, 8g / 10 ms","number of NC contacts for main contacts":"0","number of NO contacts for main contacts":"3","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Contact Reliability Of Auxiliary Contacts":"acceptability for PLC control (17 V, 5 mA)","Type Of Voltage Of The Control Supply Voltage":"AC","operating voltage at AC-3 rated value maximum":"690 V","operational current at DC-13 at 220 V rated value":"0.3 A","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Required Spacing With Side-By-Side Mounting At The Side":"0 mm","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","number of NC contacts for auxiliary contacts instantaneous contact":"0","number of NO contacts for auxiliary contacts instantaneous contact":"0","Connectable Conductor Cross-Section For Main Contacts Finely Stranded With Core End Processing":"25 mm²","Connectable Conductor Cross-Section For Auxiliary Contacts Finely Stranded With Core End Processing":"0.5 ... 2.5 mm²"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/64934a35318460e1d1bbdb918ee89797.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1534076&mlfb=3RT7036-1AH00"},"ai":{"faq":[{"question":"Where can I buy 3RT7036-1AH00 and how do I get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"Will 3RT7036-1AH00 drop into a panel specified around 3RT5035-1AH00?","answer":"Both are SIRIUS contactors with similar DIN-rail mounting (35 mm rail per DIN EN 50022), but the 3RT7036-1AH00 is a size S2 frame while the 3RT5035-1AH00 is a different frame size. Verify panel cutout and terminal spacing before substituting; the screw terminals and auxiliary contact options may differ."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT7036-1AH00","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT7036-1AH00 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}