{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RU1116-0HB0-ZW96","brand":"Siemens","brandSlug":"siemens","productSlug":"3RU1116-0HB0-ZW96","canonicalUrl":"https://aoctrl.com/siemens/3RU1116-0HB0-ZW96","factsUrl":"https://aoctrl.com/api/mcp/products/3RU1116-0HB0-ZW96","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS thermal overload relay, Size S00, 3-pole, CLASS 10, screw-type terminals, IP20 front, ATEX certified, 3RU1116-0HB0-ZW96.","salesMarkdown":"It mounts directly onto a contactor (contactor mounting per), saving DIN-rail space in the panel. The relay comes with screw-type terminals for both the main current circuit and the auxiliary/control circuit. The terminal blocks accept solid conductors: 2x (0.5... 1.5 mm²) and 2x (0.75... 2.5 mm²) per, with the same range for finely stranded wire with core-end processing per. AWG equivalents are 2x (20... 16) and 2x (18... 14) for the main circuit, plus 2x (20... 16) and 2x (18... 14) for the auxiliary contacts per and. No separate accessory pack is needed for basic wiring — the terminals are integral. ## Clearances and mounting position Physical envelope: 87 mm high, 45 mm wide, 78 mm deep. Required clearances to adjacent components: 0 mm upwards, 0 mm forwards, 0 mm backwards, 0 mm downwards, and 6 mm at the side. The mounting position is flexible — the relay can be mounted on a vertical surface with ±135° rotation and ±45° tilt to the front and back. That covers most panel layouts without derating. ## Environmental and electrical ratings Relative humidity during operation can reach 100 %. Shock resistance is rated at 8g for 10 ms. Power loss per pole is 1.6 W. Rated operational currents vary by voltage: 1 A at 24 V, 0.22 A at 110 V, 3 A at 120 V, 0.22 A at 125 V, 0.11 A at 220 V, 2 A at 230 V, and 1 A at 400 V.","metaTitle":"Siemens 3RU1116-0HB0-ZW96 SIRIUS Thermal Overload Relay, Siz","metaDescription":"Siemens 3RU1116-0HB0-ZW96 SIRIUS thermal overload relay, Size S00, CLASS 10 trip, 3-pole, screw terminals, IP20 front, ATEX certified. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Overload Relays"],"specifications":{"Depth":"78 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Width":"45 mm","Height":"87 mm","Upwards":"0 mm","at 24 V":"1 A","Forwards":"0 mm","Per Pole":"1.6 W","at 110 V":"0.22 A","at 120 V":"3 A","at 125 V":"0.22 A","at 220 V":"0.11 A","at 230 V":"2 A","at 400 V":"1 A","Backwards":"0 mm","Downwards":"0 mm","Trip Class":"CLASS 10","At The Side":"6 mm","During Storage":"-55 ... +80 °C","lifecycle_stage":"current","During Operation":"-20 ... +70 °C","During Transport":"-55 ... +80 °C","Fastening Method":"Contactor mounting","Shock Resistance":"8g / 10 ms","Mounting Position":"with vertical mounting surface +/-135° rotatable, with vertical mounting surface +/- 45° tiltable to the front and back","Product Brand Name":"SIRIUS","Type Of Protection":"DMT 98 ATEX G 001","Product Designation":"thermal overload relay","Size Of Overload Relay":"S00","For Main Current Circuit":"screw-type terminals","Substance Prohibitance (Date)":"07/01/2006","at AWG cables for main contacts":"2x (20 ... 16), 2x (18 ... 14), 2x 12","protection class IP on the front":"IP20","For Auxiliary And Control Circuit":"screw-type terminals","Relative Humidity During Operation":"100 %","Surge Voltage Resistance Rated Value":"6 kV","at AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14)","reference code according to IEC 81346-2":"F","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Touch Protection Against Electrical Shock":"finger-safe","number of CO contacts for auxiliary contacts":"0","number of NC contacts for auxiliary contacts":"1","number of NO contacts for auxiliary contacts":"1","Size Of Contactor Can Be Combined Company-Specific":"S00","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 6 A, quick: 10 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Product Component Removable Terminal For Auxiliary And Control Circuit":"No","power loss [W] for rated value of the current at AC in hot operating state":"4.8 W","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"0.55 ... 0.8 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=486302&mlfb=3RU1116-0HB0-ZW96","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RU1116-0HB0-ZW96/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3RU1116-0HB0-ZW96?","answer":"Submit an RFQ through this listing. We source through independent distribution and confirm current pricing and lead time at quote time — no published stock or price figures here."},{"question":"What compliance documentation does this brand provide for 3RU1116-0HB0-ZW96 (RoHS, REACH, UL, IEC)?","answer":"The relay carries ATEX certification DMT 98 ATEX G 001 and a substance prohibition date of 07/01/2006, indicating RoHS-like compliance. The reference code per IEC 81346-2 is F. For full UL/CSA/REACH declarations, request the manufacturer's compliance package with your RFQ."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RU1116-0HB0-ZW96","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RU1116-0HB0-ZW96 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}