{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RU2116-0CC1","brand":"Siemens","brandSlug":"siemens","productSlug":"3RU2116-0CC1","canonicalUrl":"https://aoctrl.com/siemens/3RU2116-0CC1","factsUrl":"https://aoctrl.com/api/mcp/products/3RU2116-0CC1","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS thermal overload relay, 3RU2116-0CC1, Class 10, S00 size, 690 V rated, spring-loaded terminals, 45 x 102 x 79 mm.","salesMarkdown":"The 3RU2116-0CC1: Class 10 means the relay trips within 10 seconds at 7.2× the set current — fast enough to protect standard induction motors during a locked-rotor event without nuisance tripping on normal starts. The S00 frame (45 mm wide, 102 mm tall, 79 mm deep) is the smallest Siemens overload relay footprint; it mounts stand-alone in any position, so it fits tight panels where every millimeter counts. Spring-loaded terminals accept 2× (0.5 to 2.5 mm²) solid or stranded wire, no ferrules required — speeds up wiring on a build.","metaTitle":"Siemens 3RU2116-0CC1 SIRIUS Thermal Overload Relay, Class 10","metaDescription":"Siemens 3RU2116-0CC1 SIRIUS thermal overload relay, Class 10, S00 size, 690 V rated, spring-loaded terminals. Current production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Overload Relays"],"specifications":{"Note":"for message \"Tripped\"","Depth":"79 mm","Width":"45 mm","Height":"102 mm","at 24 V":"2 A","at 60 V":"0.3 A","Per Pole":"1.6 W","at 110 V":"0.22 A","at 120 V":"3 A","at 125 V":"0.22 A","at 220 V":"0.11 A","at 230 V":"2 A","at 400 V":"1 A","Trip Class":"CLASS 10","Rated Value":"690 V","During Storage":"-55 ... +80 °C","lifecycle_stage":"current","During Operation":"-40 ... +70 °C","During Transport":"-55 ... +80 °C","Fastening Method":"stand-alone installation","Mounting Position":"any","Solid Or Stranded":"2x (0.5 ... 2.5 mm²)","Product Brand Name":"SIRIUS","Product Designation":"thermal overload relay","at 400 V rated value":"0.06 kW","at 480 V rated value":"0.25 A","at 500 V rated value":"0.09 kW","at 600 V rated value":"0.25 A","at 690 V rated value":"0.12 kW","Size Of Overload Relay":"S00","For Main Current Circuit":"spring-loaded terminals","Temperature Compensation":"-40 ... +60 °C","MTTF with high demand rate":"2 280 y","Design Of Screwdriver Shaft":"Diameter 3 mm","Size Of The Screwdriver Tip":"3,0 x 0,5 mm","at AC-3e rated value maximum":"690 V","Substance Prohibitance (Date)":"10/01/2009","Design Of The Auxiliary Switch":"integrated","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"0.25 A","at AWG cables for main contacts":"1x (20 ... 12)","For Auxiliary And Control Circuit":"spring-loaded terminals","Between Main And Auxiliary Circuit":"440 V","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Slide switch","Surge Voltage Resistance Rated Value":"6 kV","at AWG cables for auxiliary contacts":"2x (20 ... 14)","Between Auxiliary And Auxiliary Circuit":"440 V","reference code according to IEC 81346-2":"F","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Finely Stranded Without Core End Processing":"2x (0.5 ... 1.5 mm²)","number of CO contacts for auxiliary contacts":"0","number of NC contacts for auxiliary contacts":"1","number of NO contacts for auxiliary contacts":"1","shock resistance according to IEC 60068-2-27":"8g / 11 ms","operational current at AC-3e at 400 V rated value":"0.25 A","Size Of Contactor Can Be Combined Company-Specific":"S00","contact rating of auxiliary contacts according to UL":"B600 / R300","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gG: 6 A, quick: 10 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Product Component Removable Terminal For Auxiliary And Control Circuit":"No","power loss [W] for rated value of the current at AC in hot operating state":"4.8 W","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"0.18 ... 0.25 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/facaeb87ac58d3edfb3109b3520c9a05.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=134014&mlfb=3RU2116-0CC1","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RU2116-0CC1/alternatives.json"},"ai":{"faq":[{"question":"What is 3RU2116-0CC1's listed note (for message 'Tripped') on this component line?","answer":"The note is 'for message Tripped' — it indicates the auxiliary switch contact signals a tripped condition from the overload relay."},{"question":"What is 3RU2116-0CC1's listed depth?","answer":"The depth is 79 mm."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RU2116-0CC1","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RU2116-0CC1 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}