{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RU2116-0EB1","brand":"Siemens","brandSlug":"siemens","productSlug":"3RU2116-0EB1","canonicalUrl":"https://aoctrl.com/siemens/3RU2116-0EB1","factsUrl":"https://aoctrl.com/api/mcp/products/3RU2116-0EB1","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS thermal overload relay, 3RU2116-0EB1, Class 10, S00 frame, 690 V rated, screw terminals, integrated auxiliary switch.","salesMarkdown":"The relay uses a bimetallic thermal release, temperature-compensated from -40 to +60 °C, so ambient shifts in the panel don't drift the trip point. It mounts in any position, standalone, and accepts screw-type terminals for the main circuit — 2× (0.5 to 2.5 mm²) solid or stranded per pole. The integrated auxiliary switch provides a normally-open and normally-closed contact for signaling the tripped state to a PLC or contactor coil; the 'Note for message Tripped' on the nameplate confirms the NO/NC assignment for that status. The auxiliary contacts are rated for 2 A at 24 V, 3 A at 120 V, and 2 A at 230 V — enough to drive a small PLC input or a contactor coil directly, but check the inrush if you're switching a DC coil with a high holding current. At 400 V the rating drops to 1 A, and at 690 V to 0.18 kW — the contacts are sized for control, not power switching. Size S00 fits the standard DIN-rail footprint for Siemens SIRIUS contactors in the same frame. Screw terminals accept Pozidriv PZ2 bits; the screwdriver shaft diameter should be 5 to 6 mm.","metaTitle":"Siemens 3RU2116-0EB1 SIRIUS Thermal Overload Relay, Class 10","metaDescription":"Siemens 3RU2116-0EB1 SIRIUS thermal overload relay, Class 10 trip, S00 frame, 690 V rated. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Overload Relays"],"specifications":{"Note":"for message \"Tripped\"","Depth":"80 mm","Width":"45 mm","Height":"89 mm","at 24 V":"2 A","at 60 V":"0.3 A","Per Pole":"1.6 W","at 110 V":"0.22 A","at 120 V":"3 A","at 125 V":"0.22 A","at 220 V":"0.11 A","at 230 V":"2 A","at 400 V":"1 A","Trip Class":"CLASS 10","Rated Value":"690 V","During Storage":"-55 ... +80 °C","lifecycle_stage":"current","During Operation":"-40 ... +70 °C","During Transport":"-55 ... +80 °C","Fastening Method":"stand-alone installation","For Main Contacts":"M3","Mounting Position":"any","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Product Brand Name":"SIRIUS","Product Designation":"thermal overload relay","at 400 V rated value":"0.09 kW","at 480 V rated value":"0.4 A","at 500 V rated value":"0.12 kW","at 600 V rated value":"0.4 A","at 690 V rated value":"0.18 kW","Size Of Overload Relay":"S00","For Main Current Circuit":"screw-type terminals","Temperature Compensation":"-40 ... +60 °C","MTTF with high demand rate":"2 280 y","Design Of Screwdriver Shaft":"Diameter 5 ... 6 mm","Size Of The Screwdriver Tip":"Pozidriv PZ 2","at AC-3e rated value maximum":"690 V","Substance Prohibitance (Date)":"10/01/2009","Design Of The Auxiliary Switch":"integrated","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"0.4 A","at AWG cables for main contacts":"2x (20 ... 16), 2x (18 ... 14), 2x 12","For Auxiliary And Control Circuit":"screw-type terminals","Between Main And Auxiliary Circuit":"440 V","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Slide switch","Surge Voltage Resistance Rated Value":"6 kV","at AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14)","Of The Auxiliary And Control Contacts":"M3","Between Auxiliary And Auxiliary Circuit":"440 V","reference code according to IEC 81346-2":"F","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","For Main Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","number of CO contacts for auxiliary contacts":"0","number of NC contacts for auxiliary contacts":"1","number of NO contacts for auxiliary contacts":"1","shock resistance according to IEC 60068-2-27":"8g / 11 ms","For Auxiliary Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","operational current at AC-3e at 400 V rated value":"0.4 A","Size Of Contactor Can Be Combined Company-Specific":"S00","contact rating of auxiliary contacts according to UL":"B600 / R300","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gG: 6 A, quick: 10 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Product Component Removable Terminal For Auxiliary And Control Circuit":"No","power loss [W] for rated value of the current at AC in hot operating state":"4.8 W","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"0.28 ... 0.4 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=536906&mlfb=3RU2116-0EB1","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RU2116-0EB1/alternatives.json"},"ai":{"faq":[{"question":"What compliance documentation does Siemens provide for 3RU2116-0EB1?","answer":"The relay carries a substance prohibition date of 10/01/2009, indicating RoHS compliance. No specific UL or IEC certification numbers are listed in this record, but as a SIRIUS product it is designed to meet IEC 60947-4-1."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RU2116-0EB1","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RU2116-0EB1 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}