{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RU2116-0FB0-ZX95","brand":"Siemens","brandSlug":"siemens","productSlug":"3RU2116-0FB0-ZX95","canonicalUrl":"https://aoctrl.com/siemens/3RU2116-0FB0-ZX95","factsUrl":"https://aoctrl.com/api/mcp/products/3RU2116-0FB0-ZX95","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RU2116-0FB0-ZX95 thermal overload relay, Size S00, Class 10 trip, 690 V rated insulation, integrated auxiliary contact with \"Tripped\" message, screw terminals.","salesMarkdown":"The integrated auxiliary contact is marked \"for message 'Tripped'\" — it changes state when the overload relay has operated, giving the control system a positive indication that the motor has been disconnected due to overload or phase loss. Rated insulation voltage of 690 V covers 400/480 V line-to-line systems with margin, and the auxiliary contact is rated for switching at common control voltages: 2 A at 24 V, 3 A at 120 V, 2 A at 230 V, and 1 A at 400 V. Size S00 is the smallest SIRIUS overload relay frame, intended for direct mounting onto the corresponding SIRIUS contactor (contactor mounting) — no separate DIN-rail footprint needed, saving panel space. Main circuit connections are screw-type terminals accepting 2× (0.5…1.5 mm²) or 2× (0.75…2.5 mm²) solid or stranded wire; the screwdriver tip required is Pozidriv PZ2 with a 5–6 mm shaft diameter. Substance prohibitance date of 10/01/2009 indicates RoHS compliance per EU directive 2002/95/EC, and the SIRIUS series carries CE and UL/CSA approvals as standard. MTTF of 2 280 years at high demand rate reflects the electromechanical simplicity of a thermal bimetallic design — this is a fit-and-forget component with no electronics to fail.","metaTitle":"Siemens 3RU2116-0FB0-ZX95 SIRIUS Thermal Overload Relay, Cla","metaDescription":"Siemens SIRIUS 3RU2116-0FB0-ZX95 thermal overload relay, Size S00, Class 10 trip, 690 V rated, auxiliary contact with tripped message. Current production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Overload Relays"],"specifications":{"Note":"for message \"Tripped\"","Depth":"70 mm","Width":"45 mm","Height":"76 mm","at 24 V":"2 A","at 60 V":"0.3 A","Per Pole":"1.6 W","at 110 V":"0.22 A","at 120 V":"3 A","at 125 V":"0.22 A","at 220 V":"0.11 A","at 230 V":"2 A","at 400 V":"1 A","Trip Class":"CLASS 10","Rated Value":"690 V","During Storage":"-55 ... +80 °C","lifecycle_stage":"current","During Operation":"-40 ... +70 °C","During Transport":"-55 ... +80 °C","Fastening Method":"Contactor mounting","For Main Contacts":"M3","Mounting Position":"any","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Product Brand Name":"SIRIUS","Product Designation":"thermal overload relay","at 400 V rated value":"0.12 kW","at 480 V rated value":"0.5 A","at 500 V rated value":"0.18 kW","at 600 V rated value":"0.5 A","at 690 V rated value":"0.25 kW","Size Of Overload Relay":"S00","For Main Current Circuit":"screw-type terminals","Temperature Compensation":"-40 ... +60 °C","MTTF with high demand rate":"2 280 y","Design Of Screwdriver Shaft":"Diameter 5 ... 6 mm","Size Of The Screwdriver Tip":"Pozidriv PZ 2","at AC-3e rated value maximum":"690 V","Substance Prohibitance (Date)":"10/01/2009","Design Of The Auxiliary Switch":"integrated","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"0.5 A","at AWG cables for main contacts":"2x (20 ... 16), 2x (18 ... 14), 2x 12","For Auxiliary And Control Circuit":"screw-type terminals","Between Main And Auxiliary Circuit":"440 V","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Slide switch","Surge Voltage Resistance Rated Value":"6 kV","at AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14)","Of The Auxiliary And Control Contacts":"M3","Between Auxiliary And Auxiliary Circuit":"440 V","reference code according to IEC 81346-2":"F","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","For Main Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","number of CO contacts for auxiliary contacts":"0","number of NC contacts for auxiliary contacts":"1","number of NO contacts for auxiliary contacts":"1","shock resistance according to IEC 60068-2-27":"8g / 11 ms","For Auxiliary Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","operational current at AC-3e at 400 V rated value":"0.5 A","Size Of Contactor Can Be Combined Company-Specific":"S00","contact rating of auxiliary contacts according to UL":"B600 / R300","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gG: 6 A, quick: 10 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Product Component Removable Terminal For Auxiliary And Control Circuit":"No","power loss [W] for rated value of the current at AC in hot operating state":"4.8 W","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"0.35 ... 0.5 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/a4b8ceacc407f40b600713dde4e12e8e.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=84089&mlfb=3RU2116-0FB0-ZX95","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RU2116-0FB0-ZX95/alternatives.json"},"ai":{"faq":[{"question":"What does the auxiliary contact note \"for message 'Tripped'\" mean?","answer":"It means the integrated auxiliary contact is wired to signal the control system that the overload relay has tripped due to overcurrent or phase loss — it is a status output, not a general-purpose auxiliary contact."},{"question":"What are the key ratings for the auxiliary contact?","answer":"The auxiliary contact is rated 2 A at 24 V, 3 A at 120 V, 2 A at 230 V, and 1 A at 400 V, covering common control-voltage levels in industrial panels."},{"question":"What is the physical size of this overload relay?","answer":"It is 45 mm wide, 76 mm high, and 70 mm deep, in the Size S00 frame — the smallest SIRIUS overload relay size."},{"question":"What compliance documentation is available for this part?","answer":"The substance prohibitance date of 10/01/2009 confirms RoHS compliance; the SIRIUS series is also CE-marked and carries UL/CSA approvals as standard."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RU2116-0FB0-ZX95","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RU2116-0FB0-ZX95 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}