{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RU2116-0GJ0","brand":"Siemens","brandSlug":"siemens","productSlug":"3RU2116-0GJ0","canonicalUrl":"https://aoctrl.com/siemens/3RU2116-0GJ0","factsUrl":"https://aoctrl.com/api/mcp/products/3RU2116-0GJ0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS thermal overload relay, 3RU2116-0GJ0, size S00, CLASS 10, 690 V rated, contactor mounting, 70 mm depth.","salesMarkdown":"## Part identity and deployment context It protects motors against overload and phase failure by monitoring the motor current and tripping the contactor when the thermal model reaches the trip threshold. The auxiliary contact ratings tell you what control voltage it can switch: 2 A at 24 V, 3 A at 120 V, 2 A at 230 V, and 1 A at 400 V. ## Integration notes Fastening is by contactor mounting — it snaps directly onto the matching SIRIUS 3RT2 contactor without additional hardware. Main circuit connections use ring cable lugs (M3 screws). The auxiliary switch is integrated into the relay body, so no separate auxiliary contact block is needed for the trip signal. Screwdriver shaft diameter 5 to 6 mm, Pozidriv PZ 2 tip for the terminal screws.","metaTitle":"Siemens 3RU2116-0GJ0 SIRIUS Thermal Overload Relay, Size S00","metaDescription":"Siemens 3RU2116-0GJ0 SIRIUS thermal overload relay, size S00, CLASS 10 trip, 690 V rated, contactor mounting. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Overload Relays"],"specifications":{"Note":"for message \"Tripped\"","Depth":"70 mm","Width":"45 mm","Height":"76 mm","at 24 V":"2 A","at 60 V":"0.3 A","Per Pole":"1.6 W","at 110 V":"0.22 A","at 120 V":"3 A","at 125 V":"0.22 A","at 220 V":"0.11 A","at 230 V":"2 A","at 400 V":"1 A","Trip Class":"CLASS 10","Rated Value":"690 V","During Storage":"-55 ... +80 °C","lifecycle_stage":"current","During Operation":"-40 ... +70 °C","During Transport":"-55 ... +80 °C","Fastening Method":"Contactor mounting","For Main Contacts":"M3","Mounting Position":"any","Product Brand Name":"SIRIUS","Product Designation":"thermal overload relay","at 400 V rated value":"0.18 kW","at 480 V rated value":"0.63 A","at 500 V rated value":"0.18 kW","at 600 V rated value":"0.63 A","at 690 V rated value":"0.25 kW","Size Of Overload Relay":"S00","For Main Current Circuit":"Ring cable lug connection","Temperature Compensation":"-40 ... +60 °C","MTTF with high demand rate":"2 280 y","Design Of Screwdriver Shaft":"Diameter 5 ... 6 mm","Size Of The Screwdriver Tip":"Pozidriv PZ 2","at AC-3e rated value maximum":"690 V","Substance Prohibitance (Date)":"10/01/2009","Design Of The Auxiliary Switch":"integrated","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"0.63 A","For Auxiliary And Control Circuit":"ring terminal lug connection","Between Main And Auxiliary Circuit":"440 V","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Slide switch","For Main Contacts For Ring Cable Lug":"1.2 ... 0.8 N·m","Surge Voltage Resistance Rated Value":"6 kV","Of The Auxiliary And Control Contacts":"M3","Between Auxiliary And Auxiliary Circuit":"440 V","reference code according to IEC 81346-2":"F","Number Of Poles For Main Current Circuit":"3","For Auxiliary Contacts For Ring Cable Lug":"0.8 ... 1.2 N·m","number of CO contacts for auxiliary contacts":"0","number of NC contacts for auxiliary contacts":"1","number of NO contacts for auxiliary contacts":"1","shock resistance according to IEC 60068-2-27":"8g / 11 ms","operational current at AC-3e at 400 V rated value":"0.63 A","Size Of Contactor Can Be Combined Company-Specific":"S00","Outer Diameter Of The Usable Ring Cable Lug Maximum":"7.5 mm","contact rating of auxiliary contacts according to UL":"B600 / R300","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gG: 6 A, quick: 10 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Product Component Removable Terminal For Auxiliary And Control Circuit":"No","power loss [W] for rated value of the current at AC in hot operating state":"4.8 W","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"0.45 ... 0.63 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/3e976129cc63b8246b5f1e764c54df27.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=504993&mlfb=3RU2116-0GJ0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RU2116-0GJ0/alternatives.json"},"ai":{"faq":[{"question":"What is the note 'for message Tripped' on this relay?","answer":"The note indicates that the auxiliary contacts change state when the relay has tripped due to an overload condition, providing a signal to the control system."},{"question":"What compliance documentation is available for this relay?","answer":"The listing includes a substance prohibition date of 10/01/2009, indicating RoHS compliance. Standard SIRIUS documentation includes CE, UL, and CSA certifications, though specific approval marks are not listed in this entry."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RU2116-0GJ0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RU2116-0GJ0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}