{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RU2116-1AC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3RU2116-1AC0","canonicalUrl":"https://aoctrl.com/siemens/3RU2116-1AC0","factsUrl":"https://aoctrl.com/api/mcp/products/3RU2116-1AC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS thermal overload relay, size S00, 3RU2116-1AC0, Trip Class 10, 690 V rated, spring-loaded terminals.","salesMarkdown":"It is rated for a maximum of 690 V and carries Trip Class 10, meaning it will trip within 10 seconds at 7.2× the set current — standard for protecting standard induction motors against stall or locked-rotor conditions without nuisance tripping during normal start. Current ratings are specified per voltage: 2 A at 24 V, 3 A at 120 V, 2 A at 230 V, 1 A at 400 V, and 0.75 A at 690 V. These are the continuous current values the relay can carry and switch at those voltages — match them to your motor full-load current and supply voltage. Mounts directly onto a contactor (fastening method: contactor mounting) in any orientation. The main circuit uses spring-loaded terminals (cage clamp) accepting 2× (0.5 … 2.5 mm²) solid or stranded wire. An integrated auxiliary switch provides the trip signal — no separate add-on block needed. Dimensions: 45 mm wide, 87 mm high, 70 mm deep — fits standard S00 contactor footprint. Temperature compensation operates from -40 to +60 °C, keeping the trip curve accurate across the panel ambient range.","metaTitle":"Siemens 3RU2116-1AC0 SIRIUS Thermal Overload Relay, S00, Cla","metaDescription":"Siemens 3RU2116-1AC0 SIRIUS thermal overload relay, size S00, Trip Class 10, 690 V rated, spring-loaded terminals, current-production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Overload Relays"],"specifications":{"Note":"for message \"Tripped\"","Depth":"70 mm","Width":"45 mm","title":"3RU2116-1AC0","Height":"87 mm","at 24 V":"2 A","at 60 V":"0.3 A","Per Pole":"1.9 W","at 110 V":"0.22 A","at 120 V":"3 A","at 125 V":"0.22 A","at 220 V":"0.11 A","at 230 V":"2 A","at 400 V":"1 A","at 690 V":"0.75 A","Trip Class":"CLASS 10","Rated Value":"690 V","description":"Overload relay 1.1...1.6 A Thermal For motor protection Size S00, Class 10 Contactor mounting Main circuit: Spring-type terminal Auxiliary circuit: spring-type terminal Manual-Automatic-Reset","During Storage":"-55 ... +80 °C","lifecycle_stage":"current","During Operation":"-40 ... +70 °C","During Transport":"-55 ... +80 °C","Fastening Method":"Contactor mounting","Mounting Position":"any","Solid Or Stranded":"2x (0.5 ... 2.5 mm²)","Product Brand Name":"SIRIUS","Product Designation":"thermal overload relay","at 400 V rated value":"0.55 kW","at 480 V rated value":"1.6 A","at 500 V rated value":"0.75 kW","at 600 V rated value":"1.6 A","at 690 V rated value":"1.1 kW","Size Of Overload Relay":"S00","For Main Current Circuit":"spring-loaded terminals","Temperature Compensation":"-40 ... +60 °C","MTTF with high demand rate":"2 280 a","Design Of Screwdriver Shaft":"Diameter 3 mm","Size Of The Screwdriver Tip":"3,0 x 0,5 mm","at AC-3e rated value maximum":"690 V","Substance Prohibitance (Date)":"10/01/2009","Design Of The Auxiliary Switch":"integrated","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"1.6 A","at AWG cables for main contacts":"1x (20 ... 12)","For Auxiliary And Control Circuit":"spring-loaded terminals","Between Main And Auxiliary Circuit":"440 V","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Slide switch","Surge Voltage Resistance Rated Value":"6 kV","at AWG cables for auxiliary contacts":"2x (20 ... 14)","Between Auxiliary And Auxiliary Circuit":"440 V","reference code according to IEC 81346-2":"F","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Finely Stranded Without Core End Processing":"2x (0.5 ... 1.5 mm²)","number of CO contacts for auxiliary contacts":"0","number of NC contacts for auxiliary contacts":"1","number of NO contacts for auxiliary contacts":"1","shock resistance according to IEC 60068-2-27":"8g / 11 ms","operational current at AC-3e at 400 V rated value":"1.6 A","Size Of Contactor Can Be Combined Company-Specific":"S00","contact rating of auxiliary contacts according to UL":"B600 / R300","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gG: 6 A, quick: 10 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Product Component Removable Terminal For Auxiliary And Control Circuit":"No","power loss [W] for rated value of the current at AC in hot operating state":"5.7 W","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"1.1 ... 1.6 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$96.02","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/de69592fa91eec1d78e661bb19c243b3.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=133361&mlfb=3RU2116-1AC0"},"ai":{"faq":[{"question":"What does the note 'for message Tripped' mean?","answer":"This relay has an integrated auxiliary switch that provides a 'Tripped' signal — a normally-open contact that closes when the overload trips, used for PLC or indicator lamp feedback."},{"question":"What is the depth of this relay?","answer":"70 mm depth, which matches the standard S00 contactor depth for direct mounting."},{"question":"What compliance documentation is available?","answer":"The evidence includes a substance prohibition date of 10/01/2009 (RoHS compliance date). Standard Siemens SIRIUS documentation covers UL, CSA, CE, and IEC 60947-4-1. Specific certificates are available on request."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RU2116-1AC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RU2116-1AC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}