{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RU2116-1FC1","brand":"Siemens","brandSlug":"siemens","productSlug":"3RU2116-1FC1","canonicalUrl":"https://aoctrl.com/siemens/3RU2116-1FC1","factsUrl":"https://aoctrl.com/api/mcp/products/3RU2116-1FC1","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS thermal overload relay, 3RU2116-1FC1, CLASS 10, size S00, 690 V rated, spring-loaded terminals, stand-alone installation.","salesMarkdown":"The S00 frame size keeps it compact for 45 mm wide DIN-rail or panel mounting, and it is rated for a maximum of 690 V on the main circuit. The auxiliary contacts are integrated and rated for switching at various control voltages: 2 A at 24 V, 2 A at 230 V, 1 A at 400 V, and 0.75 A at 690 V, among others. This covers both 24 VDC PLC-level signals and 230 VAC pilot circuits without an extra interface relay. The relay is designed for stand-alone installation — it does not require a separate base or adapter. Spring-loaded terminals on the main current circuit accept 2 × (0.5... 2.5 mm²) solid or stranded wire, and the screwdriver tip size is specified at 3.0 × 0.5 mm. The relay carries a substance prohibitance date of 10/01/2009, aligning with early RoHS compliance. ## Sourcing posture This is a standard active catalog item, not a last-time-buy or surplus part.","metaTitle":"Siemens 3RU2116-1FC1 SIRIUS Thermal Overload Relay, CLASS 10","metaDescription":"Siemens 3RU2116-1FC1 SIRIUS thermal overload relay, CLASS 10, size S00, 690V rated, spring terminals. Sourced to order against RFQ. RoHS compliant.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Overload Relays"],"specifications":{"Note":"for message \"Tripped\"","Depth":"79 mm","Width":"45 mm","title":"3RU2116-1FC1","Height":"102 mm","at 24 V":"2 A","at 60 V":"0.3 A","Per Pole":"2.2 W","at 110 V":"0.22 A","at 120 V":"3 A","at 125 V":"0.22 A","at 220 V":"0.11 A","at 230 V":"2 A","at 400 V":"1 A","at 690 V":"0.75 A","Trip Class":"CLASS 10","Rated Value":"690 V","description":"Overload relay 3.5...5.0 A Thermal For motor protection Size S00, Class 10 Stand-alone installation Main circuit: Spring-type terminal Auxiliary circuit: spring-type terminal Manual-Automatic-Reset","During Storage":"-55 ... +80 °C","lifecycle_stage":"current","During Operation":"-40 ... +70 °C","During Transport":"-55 ... +80 °C","Fastening Method":"stand-alone installation","Mounting Position":"any","Solid Or Stranded":"2x (0.5 ... 2.5 mm²)","Product Brand Name":"SIRIUS","Product Designation":"thermal overload relay","at 400 V rated value":"1.5 kW","at 480 V rated value":"5 A","at 500 V rated value":"2.2 kW","at 600 V rated value":"5 A","at 690 V rated value":"4 kW","Size Of Overload Relay":"S00","For Main Current Circuit":"spring-loaded terminals","Temperature Compensation":"-40 ... +60 °C","MTTF with high demand rate":"2 280 a","Design Of Screwdriver Shaft":"Diameter 3 mm","Size Of The Screwdriver Tip":"3,0 x 0,5 mm","at AC-3e rated value maximum":"690 V","Substance Prohibitance (Date)":"10/01/2009","Design Of The Auxiliary Switch":"integrated","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"5 A","for AWG cables for main contacts":"1x (20 ... 12)","For Auxiliary And Control Circuit":"spring-loaded terminals","Between Main And Auxiliary Circuit":"440 V","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Slide switch","Surge Voltage Resistance Rated Value":"6 kV","for AWG cables for auxiliary contacts":"2x (20 ... 14)","Between Auxiliary And Auxiliary Circuit":"440 V","reference code according to IEC 81346-2":"F","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Finely Stranded Without Core End Processing":"2x (0.5 ... 1.5 mm²)","number of CO contacts for auxiliary contacts":"0","number of NC contacts for auxiliary contacts":"1","number of NO contacts for auxiliary contacts":"1","shock resistance according to IEC 60068-2-27":"8g / 11 ms","operational current at AC-3e at 400 V rated value":"5 A","Size Of Contactor Can Be Combined Company-Specific":"S00","contact rating of auxiliary contacts according to UL":"B600 / R300","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gG: 6 A, quick: 10 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Product Component Removable Terminal For Auxiliary And Control Circuit":"No","power loss [W] for rated value of the current at AC in hot operating state":"6.6 W","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"3.5 ... 5 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$34.29","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/d4c3261af7de53ea3ba1314887e21444.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=80755&mlfb=3RU2116-1FC1"},"ai":{"faq":[{"question":"Where can I buy 3RU2116-1FC1 and how do I get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ to confirm current availability and pricing at quote time."},{"question":"Will 3RU2116-1FC1 drop into a panel specified around 3RT2015-2AP02?","answer":"The 3RU2116-1FC1 is a thermal overload relay, while 3RT2015-2AP02 is a contactor. They are designed to work together in the same SIRIUS system and share the S00 frame size, so the relay mounts directly onto the contactor or alongside it on the DIN rail without rewiring the main power circuit."},{"question":"What is the note 'for message Tripped' on this component line?","answer":"The note indicates that the auxiliary contact position on the 3RU2116-1FC1 is labeled for the 'Tripped' message — the normally-closed contact that opens when the relay has tripped on overload, used to signal a fault condition to the PLC or annunciator."},{"question":"What is 3RU2116-1FC1's listed depth?","answer":"The depth is 79 mm. Combined with a width of 45 mm and height of 102 mm, this is the standard S00 footprint."},{"question":"What compliance documentation does Siemens provide for 3RU2116-1FC1?","answer":"The part carries a substance prohibitance date of 10/01/2009, indicating RoHS compliance from that date. Standard Siemens documentation includes the declaration of conformity and CE marking for the Low Voltage Directive."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RU2116-1FC1","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RU2116-1FC1 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}