{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RU6116-0JB0","brand":"Siemens","brandSlug":"siemens","productSlug":"3RU6116-0JB0","canonicalUrl":"https://aoctrl.com/siemens/3RU6116-0JB0","factsUrl":"https://aoctrl.com/api/mcp/products/3RU6116-0JB0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS thermal overload relay, 3RU6116-0JB0, adjustable 0.7-1.0 A, Trip Class 10, size S00, screw-type terminals for main and auxiliary circuits, contactor-mount design.","salesMarkdown":"It's the part that sits between the contactor and the motor — watches the current draw, trips if the motor pulls too long. Adjustable current response from 0.7 A up to 1 A, Trip Class 10, meaning it'll clear a stall before the windings cook. For a small motor — fractional to about 0.37 kW at 400 V — this is the right thermal partner. ## Mounting and wiring reality Fastens directly onto the contactor. S00 frame size mates with S00-frame contactors. Screw terminals for main and aux circuits. Rated operational current is 1 A — that's the continuous motor FLA this relay is designed to protect at the top of its adjustment range. The 0.7–1 A window lets you dial in the exact trip point for the motor nameplate. Rated insulation voltage 690 V, surge withstand 6 kV — fine for 400 V line supplies. Shock rated at 8 g / 11 ms per IEC 60068-2-27, which covers most industrial vibration environments.","metaTitle":"Siemens 3RU6116-0JB0 SIRIUS Overload Relay, 0.7-1 A, Class 1","metaDescription":"Siemens 3RU6116-0JB0 SIRIUS thermal overload relay, 0.7-1 A adjustable, Class 10, S00 size, screw terminals. Active production, available to order. RFQ for pricing.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Overload Relays"],"specifications":{"Depth":"70 mm","Width":"45 mm","title":"3RU6116-0JB0","Height":"76 mm","at 24 V":"2 A","Per Pole":"1.6 W","at 110 V":"0.22 A","at 230 V":"2 A","Trip Class":"CLASS 10","description":"Overload relay 0.70...1.0 A size S00, class 10, for motor protection for mounting onto contactors main circuit: screw terminal AUX. circuit: screw terminal manual automatic reset","lifecycle_stage":"current","During Operation":"-40 ... +70 °C","During Transport":"-55 ... +80 °C","Fastening Method":"Contactor mounting","Mounting Position":"any","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Thermal overload relay","For Main Current Circuit":"screw-type terminals","power loss [W] total typical":"4.5 W","Operating Voltage Rated Value":"690 V","Substance Prohibitance (Date)":"05/01/2012","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"1 A","at AWG cables for main contacts":"2x (20 ... 16), 2x (20 ... 18), 2x 12","For Auxiliary And Control Circuit":"screw-type terminals","Relative Humidity During Operation":"0 ... 90 %","Surge Voltage Resistance Rated Value":"6 kV","at AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14)","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","shock resistance according to IEC 60068-2-27":"8g / 11 ms","Required Spacing For Grounded Parts At The Side":"6 mm","Size Of Contactor Can Be Combined Company-Specific":"S00","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","Tightening Torque For Main Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","insulation voltage with degree of pollution 3 at AC rated value":"690 V","power loss [W] for rated value of the current at AC in hot operating state":"4.8 W","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"0.7 ... 1 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/ff0c8af6d1639c8d00ac0f063774ad74.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=621506&mlfb=3RU6116-0JB0"},"ai":{"faq":[{"question":"What compliance documentation does Siemens provide for 3RU6116-0JB0?","answer":"RoHS compliance is confirmed with a substance prohibitance date of 05/01/2012. The relay carries a rated insulation voltage of 690 V and surge voltage resistance of 6 kV per IEC standards. For specific UL, CSA, or CE declarations, request the manufacturer's declaration of conformity with your RFQ."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RU6116-0JB0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RU6116-0JB0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}