{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV1011-0AA10-0FJ0-ZX95","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV1011-0AA10-0FJ0-ZX95","canonicalUrl":"https://aoctrl.com/siemens/3RV1011-0AA10-0FJ0-ZX95","factsUrl":"https://aoctrl.com/api/mcp/products/3RV1011-0AA10-0FJ0-ZX95","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS, motor protection circuit breaker, 3RV1011-0AA10-0FJ0-ZX95, 0.16 A continuous current, CLASS 10, 100 kA breaking capacity at 400 V AC.","salesMarkdown":"## Motor protection circuit breaker, 0.16 A, CLASS 10 The 100 kA breaking capacity holds across 240 V, 400 V, 500 V, and 690 V AC, so it can be placed upstream of a motor starter without worrying about fault-current escalation into the contactor. Occupies 45 mm width on the rail. Terminals accept solid or stranded conductors: 2× (0.5...1.5 mm²) or 2× (0.75...2.5 mm²) per clamp. Shock rated at 25g / 11 ms. Mountable in any position. IP20 front protection means it is suitable for enclosed panels, not washdown areas.","metaTitle":"Siemens 3RV1011-0AA10-0FJ0-ZX95 SIRIUS Motor Protection CB,","metaDescription":"Siemens SIRIUS 3RV1011-0AA10-0FJ0-ZX95 motor protection circuit breaker, 0.16 A continuous rating, CLASS 10 trip, 100 kA breaking capacity at 400 V. Current lifecycle stage. Quoted","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"81 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Width":"45 mm","Height":"90 mm","Maximum":"2 000 m","Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Backwards":"0 mm","Trip class":"CLASS 10","At The Side":"0 mm","Rated Value":"690 V","On The Front":"IP20","Mounting type":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","Auxiliary switch":"Yes","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Shock resistance":"25g / 11 ms","Mounting position":"any","Product brand name":"SIRIUS","Product designation":"circuit breaker","at 400 V rated value":"0.04 kW","Design of the product":"for motor protection","For Auxiliary Contacts":"0","Ground fault detection":"No","Phase failure detection":"Yes","For Main Current Circuit":"screw-type terminals","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"100 kA","at AC at 690 V rated value":"100 kA","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"100 000","at AC in hot operating state":"5.5 W","Continuous current rated value":"0.16 A","at AWG conductors for main contacts":"2x (18 ... 14)","Surge voltage resistance rated value":"6 000 V","at AC in hot operating state per pole":"1.8 W","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number of poles for main current circuit":"3","For Auxiliary And Control Current Circuit":"screw-type terminals","Removable Terminal For Auxiliary And Control Circuit":"No","Design of the overcurrent release and short-circuit release":"thermomagnetic","Arrangement of electrical connectors for main current circuit":"front side","Adjustable pick-up value current of the current-dependent overload release":"0.11 ... 0.16 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=40538&mlfb=3RV1011-0AA10-0FJ0-ZX95","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV1011-0AA10-0FJ0-ZX95/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3RV1011-0AA10-0FJ0-ZX95 and get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."},{"question":"What is the continuous current rating of 3RV1011-0AA10-0FJ0-ZX95?","answer":"The continuous current rating is 0.16 A. This is a very low setting, suitable for fractional-horsepower motors or small transformer primaries."},{"question":"What breaking capacity does this breaker have at 400 V?","answer":"It delivers 100 kA breaking capacity at 400 V AC, and the same 100 kA rating holds at 240 V, 500 V, and 690 V AC."},{"question":"Does 3RV1011-0AA10-0FJ0-ZX95 detect phase failure?","answer":"Yes, phase failure detection is included. The breaker will trip if one phase is lost, protecting the motor from single-phasing."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV1011-0AA10-0FJ0-ZX95","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV1011-0AA10-0FJ0-ZX95 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}