{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV1011-0AA10-ZW97","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV1011-0AA10-ZW97","canonicalUrl":"https://aoctrl.com/siemens/3RV1011-0AA10-ZW97","factsUrl":"https://aoctrl.com/api/mcp/products/3RV1011-0AA10-ZW97","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS motor protection circuit breaker, 3RV1011-0AA10-ZW97, Class 10 trip, 100 kA breaking capacity at 400 V, 45 mm wide, screw and snap-on DIN rail mount.","salesMarkdown":"The unit includes phase failure detection, which prevents single-phasing damage on a three-phase motor. Clearance requirements are 20 mm upward, 20 mm downward, 9 mm to the side, and zero forward or backward. That means it fits into a typical motor control center bucket or sub-panel without needing extra gland-plate space; the zero forward clearance is notable for tight enclosures where the breaker sits flush against the backplane. The 100 kA breaking capacity at 400 V (and also at 240 V, 500 V, 690 V) means this breaker can be used in high-fault-current installations — common in industrial distribution where the transformer is close to the panel. The Class 10 trip curve is the default for most IEC motor starters; if you are replacing a competitor's Class 10 breaker, this is a direct thermal match.","metaTitle":"Siemens 3RV1011-0AA10-ZW97 SIRIUS Motor Protection Circuit B","metaDescription":"Siemens 3RV1011-0AA10-ZW97 SIRIUS motor protection circuit breaker, Class 10 trip, 100 kA at 400 V, 45 mm wide. DIN rail mount. Current production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"75 mm","Width":"45 mm","Height":"90 mm","Upwards":"20 mm","Forwards":"0 mm","at 240 V":"none required","at 400 V":"None required","at 500 V":"None required","at 690 V":"None required","Backwards":"0 mm","Downwards":"20 mm","Trip Class":"CLASS 10","At The Side":"9 mm","Rated Value":"20 ... 690 V","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","at AC-3e maximum":"15 1/h","For Main Contacts":"M3","Mounting Position":"any","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"0 kW","at 240 V rated value":"100 kA","at 400 V rated value":"100 kA","at 480 V rated value":"0.16 A","at 500 V rated value":"100 kA","at 600 V rated value":"0.16 A","at 690 V rated value":"100 kA","Design Of The Product":"For motor protection","Ground Fault Detection":"No","Phase Failure Detection":"Yes","For Main Current Circuit":"screw-type terminals","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"100 kA","at AC at 690 V rated value":"100 kA","Size Of The Circuit-Breaker":"S00","Size Of The Screwdriver Tip":"Pozidriv size 2","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"100 000","at AC in hot operating state":"5.5 W","at AC-3 at 400 V rated value":"0.16 A","at AC-3e rated value maximum":"690 V","Of Auxiliary Contacts Typical":"100 000","Substance Prohibitance (Date)":"01/01/2013","at AC-3e at 400 V rated value":"0.16 A","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"0.16 A","Design Of The Short-Circuit Trip":"magnetic","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Rocker switch","Surge Voltage Resistance Rated Value":"6 kV","at AC in hot operating state per pole":"1.8 W","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","with low demand rate according to SN 31920":"50 FIT","For Main Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","with high demand rate according to SN 31920":"50 %","number of CO contacts for auxiliary contacts":"0","Electrical Endurance (Operating Cycles) Typical":"100 000","For Auxiliary Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","Size Of Contactor Can Be Combined Company-Specific":"S00","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"2.1 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"0.11 ... 0.16 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=66138&mlfb=3RV1011-0AA10-ZW97","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV1011-0AA10-ZW97/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3RV1011-0AA10-ZW97 and get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."},{"question":"What is the closest functional second-source — 3RV1011-0GA10?","answer":"The 3RV1011-0GA10 is a sibling in the same SIRIUS 3RV10 series with the same 45 mm width and Class 10 trip. The difference is the 0GA10 has a different thermal setting range and possibly a different breaking capacity at some voltages — verify the specific setting range against your motor FLA before substituting. The 3RV1011-0AA10-ZW97 drops into the same DIN-rail footprint and wiring pattern as the 0GA10."},{"question":"Will 3RV1011-0AA10-ZW97 drop into a panel specified around 3RV1011-0GA10 without rewiring?","answer":"Yes — both are 45 mm wide, mount on 35 mm DIN rail, and use the same screw-type terminals for the main circuit. The terminal wire ranges are identical: 2x (0.5 to 1.5 mm²) and 2x (0.75 to 2.5 mm²) solid or stranded. No rewiring needed for the power connections; verify the auxiliary contact configuration if your panel uses one."},{"question":"What compliance documentation does Siemens provide for 3RV1011-0AA10-ZW97?","answer":"As a Siemens SIRUS product, this circuit breaker carries IEC/EN 60947-2 and 60947-4-1 compliance. RoHS and REACH declarations are standard from Siemens. UL and CSA listings are typical for the 3RV10 series, but verify the specific file number for this order code variant (ZW97 suffix may indicate a special version)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV1011-0AA10-ZW97","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV1011-0AA10-ZW97 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}