{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV1011-0AA15-ZI45","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV1011-0AA15-ZI45","canonicalUrl":"https://aoctrl.com/siemens/3RV1011-0AA15-ZI45","factsUrl":"https://aoctrl.com/api/mcp/products/3RV1011-0AA15-ZI45","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RV1011-0AA15-ZI45 motor protection circuit breaker, size S00, CLASS 10, adjustable overload release 0.11...0.16 A, screw terminals, IP20, with transverse auxiliary switch 1 NO+1 NC.","salesMarkdown":"Its adjustable overload release spans 0.11 to 0.16 A, and the magnetic short-circuit trip responds at 2.1 A — so it protects a motor drawing 0.16 A at 400 V AC-3 (rated at 0.04 kW) against both sustained overload and bolted faults. The S00 footprint — 45 mm wide, 90 mm tall, 75 mm deep — leaves room for a contactor of the same S00 frame alongside in a motor starter combo. Clearance requirements: 20 mm above and below, 9 mm to the side, zero forward or backward. IP20 finger-safe front protection means it's suited for enclosed panels where operators reach in for maintenance.","metaTitle":"Siemens 3RV1011-0AA15-ZI45 SIRIUS Motor Protection Circuit B","metaDescription":"Siemens SIRIUS 3RV1011-0AA15-ZI45 motor protection circuit breaker, size S00, CLASS 10, adjustable overload 0.11-0.16 A, screw terminals, IP20, active production. Sourced to order","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Upwards":"20 mm","Forwards":"0 mm","Backwards":"0 mm","Downwards":"20 mm","Trip Class":"CLASS 10","At The Side":"9 mm","lifecycle_stage":"current","Fastening Method":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 60715","Mounting Position":"any","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 400 V rated value":"0.04 kW","Design Of The Product":"For motor protection","For Main Current Circuit":"screw-type terminals","Size Of The Circuit-Breaker":"S00","at AC in hot operating state":"5.5 W","Substance Prohibitance (Date)":"01.01.2013 00:00:00","Operational Current Rated Value":"0.16 A","at AC in hot operating state per pole":"1.8 W","touch protection on the front acc. to IEC 60529":"finger-safe, for vertical contact from the front","operational current at AC-3 at 400 V rated value":"0.16 A","protection class IP on the front acc. to IEC 60529":"IP20","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"0.11 ... 0.16 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=809393&mlfb=3RV1011-0AA15-ZI45","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV1011-0AA15-ZI45/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for the 3RV1011-0AA15-ZI45?","answer":"Adjustable overload release 0.11...0.16 A, CLASS 10 trip class, rated operational current 0.16 A at 400 V AC-3, motor power 0.04 kW at 400 V, IP20 front protection, size S00 with screw terminals."},{"question":"Where can I buy the 3RV1011-0AA15-ZI45 and get a price?","answer":"Sourced to order against an RFQ through independent industrial distribution. Submit a request for quote; availability and current pricing are confirmed at quote time."},{"question":"Will the 3RV1011-0AA15-ZI45 drop into a panel specified around the 3RV1011-0GA10?","answer":"Yes — both are size S00 with the same DIN-rail mounting and identical clearance requirements (20 mm up/down, 9 mm sides, 0 mm forward/backward). The difference is the overload adjustment range: the 0GA10 covers 0.45...0.63 A, while this unit covers 0.11...0.16 A. If your motor's full-load current falls in the lower band, it's a direct swap without rewiring."},{"question":"What compliance documentation does Siemens provide for this breaker?","answer":"The product carries a substance prohibitance date of 01.01.2013, indicating RoHS compliance. As a SIRIUS motor protection circuit breaker, it is designed to meet IEC 60947-2 and IEC 60947-4-1 standards. Specific UL/CSA certification status should be confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV1011-0AA15-ZI45","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV1011-0AA15-ZI45 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}