{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV1011-0AA25","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV1011-0AA25","canonicalUrl":"https://aoctrl.com/siemens/3RV1011-0AA25","factsUrl":"https://aoctrl.com/api/mcp/products/3RV1011-0AA25","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS motor-protection circuit breaker, 3RV1011-0AA25, 0.16 A continuous, Class 10 trip, 100 kA SCCR at 400 V, spring-loaded terminals, DIN-rail mount.","salesMarkdown":"It provides overload and short-circuit protection for motors up to 0.04 kW at 400 V, with a continuous current rating of 0.16 A and a Class 10 trip characteristic — meaning it clears overloads within 10 seconds at 7.2× rated current, matching the thermal time constant of a standard induction motor during a stalled-rotor start. The 100 kA short-circuit breaking capacity at 400 V (and at 240 V, 500 V, and 690 V) means this breaker can safely interrupt a fault up to that level without upstream fuses or a larger breaker — a real advantage when coordinating a high-fault panel. The 0.16 A continuous rating is the setpoint; it governs the motor FLA it protects, so verify your motor's full-load amps match before specifying. Ground fault detection is not included, so if that's required, a separate ground-fault relay or a different SIRIUS variant is needed. Spring-loaded terminals on both the main and auxiliary circuits accept 0.25–2.5 mm² solid or stranded wire (24–14 AWG), so no screwdriver torque check — just strip, insert, release.","metaTitle":"Siemens 3RV1011-0AA25 SIRIUS Motor Protection Circuit Breake","metaDescription":"Siemens 3RV1011-0AA25 SIRIUS motor-protection circuit breaker, 0.16 A continuous, Class 10 trip, 100 kA SCCR at 400 V. Active production, sourced to order. Request quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"81 mm","Solid":"2x (0.25 ... 2.5 mm²)","Width":"45 mm","Height":"90 mm","at 24 V":"1 A","at 60 V":"0.15 A","at 230 V":"0.5 A","Backwards":"0 mm","Trip Class":"CLASS 10","At The Side":"0 mm","Rated Value":"690 V","During Storage":"-50 ... +80 °C","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Shock Resistance":"25g / 11 ms","Mounting Position":"any","Product Brand Name":"SIRIUS","Product Designation":"circuit breaker","at 400 V rated value":"0.04 kW","Design Of The Product":"for motor protection","Ground Fault Detection":"No","Phase Failure Detection":"Yes","For Main Current Circuit":"spring-loaded terminals","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"100 kA","at AC at 690 V rated value":"100 kA","at AC-3 rated value maximum":"690 V","at AC in hot operating state":"5.5 W","Substance Prohibitance (Date)":"01.01.2013","Continuous Current Rated Value":"0.16 A","Design Of The Auxiliary Switch":"transverse","at AWG cables for main contacts":"2x (24 ... 14)","protection class IP on the front":"IP20","For Auxiliary And Control Circuit":"spring-loaded terminals","Product Extension Auxiliary Switch":"Yes","operating frequency at AC-3 maximum":"15 1/h","Surge Voltage Resistance Rated Value":"6 000 V","at AWG cables for auxiliary contacts":"2x (24 ... 14)","at AC in hot operating state per pole":"1.8 W","Finely Stranded With Core End Processing":"2x (0.25 ... 1.5 mm²)","Number Of Poles For Main Current Circuit":"3","Touch Protection Against Electrical Shock":"finger-safe","Finely Stranded Without Core End Processing":"2x (0.25 ... 2.5 mm²)","number of CO contacts for auxiliary contacts":"0","operational current at AC-3 at 400 V rated value":"0.16 A","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Design Of The Overcurrent Release And Short-Circuit Release":"thermomagnetic","Arrangement Of Electrical Connectors For Main Current Circuit":"front side","Product Component Removable Terminal For Auxiliary And Control Circuit":"No","Mechanical Service Life (Switching Cycles) Of The Main Contacts Typical":"100 000","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"0.11 ... 0.16 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=56644&mlfb=3RV1011-0AA25","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV1011-0AA25/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3RV1011-0AA25 and how do I get a price?","answer":"This part is sourced to order against an RFQ through independent distribution. Submit a request for quote (RFQ) to confirm current availability and pricing."},{"question":"What is 3RV1011-0AA25's listed depth?","answer":"The depth is 81 mm."},{"question":"What is 3RV1011-0AA25's listed solid conductor range?","answer":"The spring-loaded terminals accept 2x (0.25... 2.5 mm²) solid or stranded wire."},{"question":"Will 3RV1011-0AA25 drop into a panel specified around 3RV1011-0GA10 without rewiring?","answer":"Both are SIRIUS motor-protection circuit breakers in the same 45 mm wide, DIN-rail mountable form factor with spring-loaded terminals, so the mechanical fit and wiring method are identical. The key difference is the current rating — 0.16 A on the -0AA25 versus a different setpoint on the -0GA10 — so verify the motor FLA matches before substituting."},{"question":"What compliance documentation does Siemens provide for 3RV1011-0AA25?","answer":"The part carries a substance prohibition date of 01.01.2013, indicating RoHS compliance. Standard Siemens documentation includes a CE declaration of conformity and UL/CSA certification; request the specific certificates with your RFQ."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV1011-0AA25","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV1011-0AA25 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}